![]() |
guy wire for the ground wire
I don't recall seeing it anywhere, but is there any problem with using some
left over guy wire (3/16 EHS) to go from the tower to a ground rod at the base of a tower. Planning on going to about 60 feet with Rohn 25 and will probably use a ground rod at the tower and maybe one at each of the guy points. Just seems to me that if the correct clamps are used the wires and tower would be the same material and not have a galvonic reaction. |
guy wire for the ground wire
I'd avoid it. The conductivity of steel (stainless?) guy wire is much
lower than copper, maybe 40 times lower, so your 3/16th EHS is maybe something like 20 gauge copper equivalent. Dan Ralph Mowery wrote: I don't recall seeing it anywhere, but is there any problem with using some left over guy wire (3/16 EHS) to go from the tower to a ground rod at the base of a tower. Planning on going to about 60 feet with Rohn 25 and will probably use a ground rod at the tower and maybe one at each of the guy points. Just seems to me that if the correct clamps are used the wires and tower would be the same material and not have a galvonic reaction. |
guy wire for the ground wire
On 1 Nov 2006 19:44:24 -0800, "
wrote: I'd avoid it. The conductivity of steel (stainless?) guy wire is much lower than copper, maybe 40 times lower, so your 3/16th EHS is maybe something like 20 gauge copper equivalent. 3/16" is approximately 5 AWG. The ITT handbook gives the resistance of copper-clad steel (a good enough approximation to zinc plated steel) as about 1 ohm/1000'. Compared to the resistance of a ground rod to Earth "connection" I think that a few feet of steel wire resistance is in the noise. I'd watch out for a zinc to copper connection tho. Dan Ralph Mowery wrote: I don't recall seeing it anywhere, but is there any problem with using some left over guy wire (3/16 EHS) to go from the tower to a ground rod at the base of a tower. Planning on going to about 60 feet with Rohn 25 and will probably use a ground rod at the tower and maybe one at each of the guy points. Just seems to me that if the correct clamps are used the wires and tower would be the same material and not have a galvonic reaction. |
guy wire for the ground wire
On Tue, 31 Oct 2006 23:45:05 GMT, "Ralph Mowery"
wrote: I don't recall seeing it anywhere, but is there any problem with using some left over guy wire (3/16 EHS) to go from the tower to a ground rod at the base of a tower. Planning on going to about 60 feet with Rohn 25 and will probably use a ground rod at the tower and maybe one at each of the guy points. Just seems to me that if the correct clamps are used the wires and tower would be the same material and not have a galvonic reaction. Do you have codes or standards that provide guidance, or requirements? The standard applicable here in Australia suggests that it is likely that earthing conductors need to be 35mm^2 copper or better (~ 2AWG). The conductor used for lightning protection should be sufficient to carry the anticipated current without deterioration and without risk of fire. People often design for a scenario like 20kA for 0.1s. I don't know how 3/16EHS performs in that scenario, but I venture that it probably has csa of about 10mm^2, conductivity of a tenth of copper, higher inductance than copper (which affects the voltage rise), higher specific heat and higher melting point. Perhaps it is safer to use copper of adequate size. Owen -- |
guy wire for the ground wire
Compared to the resistance of a ground rod to Earth "connection" I
think that a few feet of steel wire resistance is in the noise. But the power-handling capability of that wire is much less than that of the earth below the tower ;-) It would be a tad better at not exploding than a 20AWG wire would, because it's more massive, mostly, but I don't know that I'd want to use it as a primary grounding conductor anyway. Dan |
All times are GMT +1. The time now is 10:10 PM. |
Powered by vBulletin® Copyright ©2000 - 2025, Jelsoft Enterprises Ltd.
RadioBanter.com