RadioBanter

RadioBanter (https://www.radiobanter.com/)
-   Antenna (https://www.radiobanter.com/antenna/)
-   -   Strange question about SWR on HV lines (https://www.radiobanter.com/antenna/2721-re-strange-question-about-swr-hv-lines.html)

Richard Harrison December 13th 04 09:33 PM

Richard Clark wrote:
"The trig is identical as are the results."

Yes, but the equipment often takes different forms. The best place to
get rid of circulating current in the transmission line is at the load,
before it causes additional line loss.

For signal lines a capicitance or an inductance often is formed by a
line stub.

For power lines a capacitance is often produced by an over-excited
synchronous motor or motors. Some constant speed loads are suitable for
sychronous machines. Such a machine drawing a leading current has been
called a rotary capacitor. Its current draw and capacitance are
controlled by its excitation.
Most induction motors and industrial loads have lagging currents. Power
factor correction requires the production of an offsetting leadng
current.

Best regards, Richard Harrison, KB5WZI


Richard Clark December 13th 04 11:49 PM

On Mon, 13 Dec 2004 15:33:51 -0600, (Richard
Harrison) wrote:

Yes, but the equipment often takes different forms. The best place to
get rid of circulating current in the transmission line is at the load,
before it causes additional line loss.


Hi Richard,

One of my old references offers support to this in the terms you
expressed following this quote above:
"Power factor correction may be made on transmission
lines, whereby the voltage regulation may be materially improved,
the generating capacity increased and the copper losses
reduced. This correction may be made by the over and under
excitation of synchronous apparatus at the receiving end of
the line. When used for this purpose exclusively, such
apparatus is called a synchronous condenser. ...its sole
function being to regulate the power-factor...."

The difference between this matching to the load, and say Gamma
matching to an antenna is in name only - same problem for both
disciplines, same approach to a solution. It stands to reason that
when this technique is performed at the source end, that it is still
the same "synchronous condenser" metaphor; hence we have
electro-mechanical artifices to construct a phase offset to a reactive
load.

If everyone could afford gold-plated rigs, then they might consider
paying for the same artifice of the "synchronous condenser" metaphor
in place of their tuners. In this regard they would be using Gyrators
(artificial reactors). Through the use of feedback in an operational
amplifier dedicated solely to this purpose, you can invert the use of
a capacitor to appear to be an inductor (or t'other way 'round). Here,
this particular circuit probably outnumbers all examples of tuners AND
power line correction (it is exceedingly commonplace in switchers).

73's
Richard Clark, KB7QHC

Nick Kennedy December 14th 04 02:28 AM

Hello Roy,

Good question and one I had considered addressing in my already over long
post. In general "the grid" is viewed as an idealized source or sink of
both real and reactive power. So we can theoretically supply it as much
power as we wish, and supply or take in as much reactive power as we wish.
No reactive load banks needed.

So when I said generation (of both watts and VARs) is matched to demand,
that's not necessarily *exactly* the case when it comes to VARs, as you
guessed. Generators can both supply and absorb them to meet the need, and
the net VAR output doesn't necessarily have to equal whatever the customers
are offering as the load at any given time. BTW, in the power biz, we have
the convention of "supplying", "outgoing", or positive VARs to describe
reactive power out from the generator to a lagging (inductive) load and
incoming, or negative VARs to leading (capacitive) loads. Incidentally,
real power must flow *out* only. We have reverse power (anti-motoring)
relays to trip the unit off line if this rule is broken.

The tendency of generators to exchange VARs when in parallel leads to a
stability problem in excitation control. A slight mismatch in excitation
systems can lead to a huge exchange of VARs and resulting overcurrent. So
excitations system incorporate what is known as a "droop" feature which
essentially provides a negative feedback based on reactive current.
Increased VARs out tends to reduce excitation, stabilizing the system.
Droop is typically switched "off" in isochronous (one generator isolated)
mode. There's an analogous "droop" feature on the governor for speed
control when in parallel.

Not sure if your question included this, but it's interesting to consider
just how a generator produces out of phase current when connected to what
we're essentially considering to be equivalent to an ideal voltage source,
since by definition the generator's terminal voltage must equal that of the
source (grid). As I see it, the key is that the generated voltage, Eg, is n
ot the same as the generator's terminal voltage, Et. There's a drop across
the armature reactance, so Et equals Eq minus that drop. Interesting that
out of phase currents produce drops in phase with Eg ... Well, I thought so
anyway. Current is Et minus Eg divided by Za (armature impedance).
Changing excitation changes the magnitude of Eg (Et is fixed by the grid and
so is an anchor point). By fooling with the phasors, I think you can see
how changing excitation changes the phase angle and therefore controls VARs.

How *power* is controlled is beyond the scope of this discussion (and maybe
of my understanding). But it actually is related to the angle of the
rotor's physical position relative to the rotating field of the armature.
That angle is dependent upon the torque supplied by the driver.

73--Nick, WA5BDU
in Arkansas


"Roy Lewallen" wrote in message
...
Thanks very much for the interesting and informative tutorial from
someone in the industry. I have one question:

Nick wrote:
. . .
Another possibly relevant story. We connect our emergency diesel
generator to the grid for testing and load it to about 3000 kW and
typically from 0 to 100 kVAR. But to fully test the excitation system,
the kVAR is at some point raised to 1400. . .


If your customers' loads were, for the sake of argument, purely
resistive as seen at your power plant output, then the voltage and
current would be in phase at that point. But in order to make your
generator produce "reactive power", the voltage and current have to be
forced out of phase at the generator. How is this resolved? Is that
reactive power "delivered" to (actually swapped back and forth between)
other generators in the system -- that is, do the other generators in
the system shift their own phase angles so that the V and I can be at
some angle other than zero at your generator output (and, necessarily,
also at the outputs at other generators in the system) yet in phase at
your customers' loads? Or do you have some local bank of reactance that
you can switch in to feed the "reactive power" back and forth to when
you run this test?

Roy Lewallen, W7EL




Nick December 14th 04 01:59 PM


Richard Clark wrote:


The conjugate argument is unnecessary and in error as a response to

my
posting.


Good. Glad we've come to an agreement on that one.

In the isochronous mode, varying field current changes the terminal
voltage of the generator. In parallel mode, varying field current
can't significantly change grid voltage. But it does change the
reactive power output (MVAR or kVAR) of the generator, as you said.


This is matching explicitly. Not quantifying the load does not make
it something other than R =B1iX Ohms

When quantified, it would undoubtedly lead to very small Rs and Xs,
but all the while, the angles they resolve to are always significant.

In every sense of the term Matching, there is not a jot of difference
between these applications (AC/RF) except frequency and magnitudes of
voltage and current (and not always that).

This isn't impedance matching, it's simply supplying the demand.


Absolutely no difference between applications.


Yes there is. The operator of the generator has the freedom to adjust
power output from 0 to 100% of rated and VAR output between the maximum
incoming and outgoing rated values. No matching required. I sense
that you are beginning to argue my side of the case for me. Please
give me appropriate credit.


not to cause any
kind of mathematical match between the generator's internal X and

the
system's X.


Not demonstrated, in fact your entire recitation argues to the
contrary. My Power Transmission handbooks say quite explicitly that
manual or automatic operation attends to the phase shift by

necessity.
Even if you don't calculate any quantified value it remains as a
mismatch until intervention.

Trying to draw this back into the Conjugate is, again, a misread of
the distinctions between Conjugate and Z Matching. The two are
frequently mixed in discussion (through error), but they are not the
same.


Agreed; please stop bringing conjugate matching into this. You've
already accepted the fact that it doesn't apply.

So we're not matching to any specific
impedance, but supplying load and maintaining voltage.


This statement is simply unquantified Matching.

A story transmission guys like to tell is how they may use open

ended
transmission lines as a kind of capacitor bank. Say there's a line

100
miles long from my plant to somewhere that's not needed to carry

load.
The system controller might connect it at my plant's end but leave

the
breakers open at the far end. A line has both capacitive and

inductive
reactance of course, but when unloaded, the capacitive dominates.


This is classic matching technique at ANY frequency and has been part
of the canon for more than 100 years.


No it is not. You are making oblique reference to the use of stubs in
RF matching. In that application, the length of the stub in degrees is
critical. In the one I describe, the length of the line is random; it
is being used for its capacitance only. It could be replaced by an
equivalent capacitor to produce the same effect. The same is not true
of a matching stub.


So
the trick of the trade is to use it to supply reactive MVARs. The
point of the story in this context is that the controller isn't
concerned about SWR on this extremely mismatched line.


Actually, the concern is quite fundamental and has also been part of
the canon for more than 100 years.

Who would want a generator that was
constrained to operate at some fixed ratio of real to reactive

power?

Hi Nick,

Who would want a generator that was constrained to supply only
toasters? Such strawmen arguements can be lined up from here to the
moon.


Kind of like canons and "known for more than 100 years"? Empty
supercilious statements that say nothing?


One of my Power distribution handbooks (ca. 1907) is not shy to the
matter of Generators seeing the products of mismatches:
"Thus a wave passing from one part of a circuit to another
having a greater ratio of inductance to capacity will develop
an increased voltage and decreased current. This
explains the breaking down of windings, due to
surges entering them."

I don't have to say SWR for it to be evident in the nature of the
description above. I don't have to say Z matching for it to be
evident in the nature of the corrective action. I don't have to say

X
for it to be evident in the myriad of phase drawings and calculations
that are offered page after page.

The old practices could measure Gamma or Rho as we describe it in

this
forum. Calling it VAR does not make it a mysterious process confined
to 50/60 Hz, it is simply a term that describes the same thing and
follows the same dynamics and is reduced by the same operations. We
shift the phase using a variable capacitor or a variable inductor.

In
the plant the same thing is done through adjusting field excitation
(or any number of tricks that are available to the RF craft too).

The
trig is identical as are the results.


Finally, the use of the term VARs is not a power engineer's sly attempt
at obfuscation. It is a common and well defined term in daily use.
73--Nick, WA5BDU


=20
73's
Richard Clark, KB7QHC



Reg Edwards December 14th 04 05:41 PM


A device usually described as a 1-to-1 choke balun is amongst the most
simple of all radio components.

Actually, 1-to-1 has nothing to do with impedance-matching or
transformation, or anything else.

The choke simply allows a balanced circuit, of no particular impedance, to
be connected to an unbalanced circuit, of another no particular impedance,
without any significant interaction between them.

It is just a very short length of balanced-twin transmission line, like
speaker cable, of no particular impedance, wound on a ferrite ring to behave
as a bifilar-wound RF choke.

Loss is negligible. There's only copper loss. The ferrite plays no part in
transmission along the short line, only in the longitudinal choking action.

If there are any ferrite losses they only occur due to the very small
longitudinal current - which is what the choke is doing its best to get rid
of anyway.

When used at the end of an antenna feedline a choke balun is just a short
continuation of that line, albeit of a different impedance. Which is of no
consequence.

At the junction of the balanced-to-unbalanced lines, such as coax to
open-wire, there's going to be a large mismatch anyhow. But that's what the
tuner is for.

The balun does indeed have an impedance transforming property as does any
other short length of line. But in the case of multiband antenna systems it
merely transforms one set of random-value impedances to another random set.
Which, in effect, leaves things as they were.

The average impedance of speaker type cable is about 140 ohms which, for
perfectionists, fits very nicely between 50-ohm coax and 450-ohm ladder
line. But it hardly matters.

The length of line wound on a balun should not exceed 1/8 wavelength at the
highest frequency of interest, at the lines own velocity. Choke action at
the lowest frequency of interest depends on number of turns and permeabilty
of the ferrite.

For multi-band operation a choke balun should be used. It is far better than
fixed-ratio 4:1 and 9:1 baluns which involve wishful thinking and are best
used over relatively narrow bands.

Choke baluns also make balanced tuners redundent. Who wants to crank two
roller-coasters when one will do.
----
Reg, G4FGQ



Reg Edwards December 15th 04 11:36 AM

Sorry, my previous message was placed in the wrong thread.

I can add that 4:1 and 9:1 fixed-ratio baluns should be used only between
known, well-defined, relatively narrow impedance ranges.

They are best NOT used on the transmission line side of tuners. Otherwise
the tuner is forced into dealing with reactances in the balun itself. This
restricts the range of antenna impedances which can be handled by the tuner.

Fixed-ratio baluns, with their excellent frequency response, are ideal on
the transmitter side of tuners, i.e., between precisely known impedances.
However they are seldom needed in that unusual position if the required
impedance transformation takes place in the tuner itself. As it always is
with a standard type of tuner and a 50-ohm transmitter.
----
Reg, G4FGQ



Roy Lewallen December 16th 04 10:45 AM

Thanks once again for the excellent explanation. What little I absorbed
in the required year of power systems coursework has pretty much faded
completely out, so I appreciate your taking the time to educate me and
the other readers.

Roy Lewallen, W7EL

Nick Kennedy wrote:
Hello Roy,

Good question and one I had considered addressing in my already over long
post. In general "the grid" is viewed as an idealized source or sink of
both real and reactive power. So we can theoretically supply it as much
power as we wish, and supply or take in as much reactive power as we wish.
No reactive load banks needed.
. . .


Reg Edwards December 17th 04 03:47 PM

The last chapter.

There's yet another point in favour of twin-balanced line rather than coax
for a choke balun.

As previously stated, the length of line wound on it is best not allowed to
exceed about 1/8-wavelength at the highest frequency of interest at the
line's own velocity factor.

Solid polyethylene coax has an appreciably lower velocity factor than twin
line such as figure-of-eight speaker cable. Or two separate wires wound
alongside each other.

Consequently, for the same length of balun line in wavelengths, more
twin-line turns can wound on the ferrite core than coax turns. This
increases LF inductance and extends the lower frequency downwards.

Or alternatively, with a shorter physical length of line on the balun, the
higher frequency is extended upwards.

The usable bandwidth of the twin-line version therefore increases roughly in
the ratio of the two velocity factors.

A choke balun may indeed be amongst the most simple of radio components to
construct - its true complexity being hidden.

But as always with radio, almost anything will work!
----
Reg, G4FGQ




All times are GMT +1. The time now is 10:38 PM.

Powered by vBulletin® Copyright ©2000 - 2025, Jelsoft Enterprises Ltd.
RadioBanter.com