![]() |
Richard Clark wrote:
Cecil Moore wrote: Ever notice how many SWR meters have 3.0 at half scale? Amateur grade - 1 in 4; Even my double-needle meters have 3:1 as a vertical line at the center. All of my single-needle SWR meters have 3.0 at half scale since they are actually reading |rho|. Check out this humoungous one. Click on the small meter picture for a full-size picture. http://www.mfjenterprises.com/produc...prodid=MFJ-868 -- 73, Cecil http://www.qsl.net/w5dxp |
But how does the attenuation length of non-TEM modes relate to the Zo of
a transmission line? ac6xg Cecil Moore wrote: Actually, it is called an argumentum ad verecundiam, an appeal to authority - a technical authority in this case. I don't know Kevin G. Rhodes at Dartmouth. He merely answered my question on s.p.e. that didn't find an answer on this newsgroup. Exactly what did you find technically wrong with the following evidence? ****Quote**** Newsgroups: sci.physics.electromag From: "Kevin G. Rhoads" Date: Tue, 07 Oct 2003 12:49:14 -0400 Subject: Transmission Line Question For 10 MHz I would expect that all other modes would be non-propagating (i.e., evanescent) even though RG-213 is a large coax (improved RG-8 apparently). The speed of propagation is listed as 66%, so the nominal wavelength is 3/2 times the free space wavelength for the TEM mode. 3/2 x 30m = 45m, which implies the decay rate in space for non-TEM modes is going to be large as the cable diameter is .405" (jacket) which implies the spacing from inner to outer conductors will be less than .203". For order of magnitude estimate, assuming the lowest non-TEM mode can be approximated using a characteristic equation that really is only applicable in Cartesian geometries: (1/45m)**2 = (1/.203")**2 + kz**2 Clearly, kz must be imaginary to make this work. thus an evanescant, non-propagating wave: kz**2 = (1/45m)**2 - (1/.203")**2 To the accuracy used to date, the first term on the right is negligible, so the decay rate, alpha, can be estimated: alpha**2 = - (kz)**2 = (1/2.03")**2 Or, the lowest order undesired mode should reduce intensity by a factor of 1/e (0.37) in about 2.03"; power will reduce by that factor squared in the same distance (.135). In about four inches, undesired mode power is down to about 0.018, in six inches, .00248, and after a foot, 6.14x10-6 You should double check my algebra, but I think the estimate is reasonable. To put it into other terms, since the wavelength in the coax dielectric is 45m and the conductor to conductor spacing is about 2", any non-TEM mode will suffer attenuation in E-field intensity with a space-rate constant rounghly equal to the conductor to conductor spacing. INtensity drops by 1/e = 1/2.71828 every 2 inches. Power availalbe drops faster, being square of intensity. So unless almost all the power diverts into an undesireable mode (by a factor of more than a million to one), one foot of cable should see pure TEM at the end. ***End Quote*** |
On Tue, 11 Oct 2005 16:57:51 GMT, Cecil Moore wrote:
I dug up some calculations from sci.physics.electromag which you recite here; then in sci.physics.electromag you can quote their use by authorities (sic both times) in rec.radio.amateur.antenna.... This appeal is called a circle of friendship - not evidence. Actually, it is called an argumentum ad verecundiam, an appeal to authority - a technical authority in this case. Actually - you have said nothing that removes this from a circle of old wives sitting around the stove in the kitchen. Name dropping is not an appeal to authority, nor are third hand quotes. |
On Tue, 11 Oct 2005 17:11:15 GMT, Cecil Moore wrote:
Even my double-needle meters have 3:1 as a vertical line You have a rather limited exposure to the field of instrumentation. |
Jim Kelley wrote:
But how does the attenuation length of non-TEM modes relate to the Zo of a transmission line? And to whether it's parallel or coaxial? Good question. Kevin Rhodes' email address can be had from Google. -- 73, Cecil http://www.qsl.net/w5dxp |
Richard Clark wrote:
Name dropping is not an appeal to authority, nor are third hand quotes. Exactly what did you find technically wrong with that third hand quote? -- 73, Cecil http://www.qsl.net/w5dxp |
I would then assume you disregard anything written in books as it falls in
the same category. "Richard Clark" wrote in message ... On Tue, 11 Oct 2005 16:57:51 GMT, Cecil Moore Name dropping is not an appeal to authority, nor are third hand quotes. |
"Cecil Moore" wrote Reg, I dug up some calculations from sci.physics.electromag from about a year ago that indicate one foot of 50 ohm coax on each side of the Bird is enough to make the line real, i.e. not imaginary, and that's a conservative estimate. =========================================== Cec, I still have a 30-watt, 160m, portable transceiver which I made about 20 years back. It's in an aluminium attache case and still works. In my travelling days I used to toss a wire out of the hotel bedroom window. Lift the lid and on the front panel is a 1.5"-square moving-coil meter. It is used as a TLI on transmit and as an S-meter on receive. The meter scale is calibrated 0-500 microamps. But my imagination doesn't fool ME. On receive, when the meter indicates 50% of full-scale deflection I know that the meter is actually measuring 250 microamps. And on transmit, when the meter indicates 90% of full scale deflection I know that the meter is actually measuring 450 microamps. Let this little anecdote be a friendly warning to they who use meters with a 0 to infinity SWR scale, or scaled in terms of forward and reverse power. ---- Reg, G4FGQ. |
Richard Clark wrote:
On Tue, 11 Oct 2005 09:11:19 +0100, Ian White G/GM3SEK wrote: The subsequent conversion to VSWR is a mathematical relationship only. Hi Ian, This seems to be a particularly notable difference - to which absolutely NO ONE has ever deviated from in ANY determination of SWR! That is to say, this "mathematical" distinction that some rely on to differentiate their arguments has not got one scintilla of difference over any other method. The only way to claim you "directly" measure SWR is to find some way to place two probes of a meter along the line such that one probe goes into the trough and the other into the peak and the meter reads SWR directly. Unfortunately for rhetoric's sake, this STILL renders the determination in terms of a mathematical relationship. It cannot be escaped. Thank you, you're right. The key difference between direct and indirect measurements is not about the need for mathematics; it's about the need for additional input from theory. What I should have said is: When you calculate the VSWR from measurements of maximum and minimum voltage on the line, that simple division formula comes directly from the definition of VSWR. The measurement is direct and completely self-contained, needing no further input from transmission-line theory. But you cannot calculate VSWR from a single-point measurement of reflection coefficient unless without some additional input from transmission-line theory which connects them together. This dependence on additional theory is what makes the measurement an indirect one. Why this keeps on being revisited must be to allow the new lurkers to observe my correction. Yes, by all means. -- 73 from Ian G/GM3SEK 'In Practice' columnist for RadCom (RSGB) http://www.ifwtech.co.uk/g3sek |
Reg Edwards wrote:
Let this little anecdote be a friendly warning to they who use meters with a 0 to infinity SWR scale, or scaled in terms of forward and reverse power. This lesson is easier to remember if your first transmitter had an anode current meter scaled in "Gallons Gone". -- 73 from Ian G/GM3SEK 'In Practice' columnist for RadCom (RSGB) http://www.ifwtech.co.uk/g3sek |
"Cecil Moore" wrote Reg, I dug up some calculations from sci.physics.electromag from about a year ago that indicate one foot of 50 ohm coax on each side of the Bird is enough to make the line real, i.e. not imaginary, and that's a conservative estimate. ============================================ Cec, you forgot to say sci.physics.electromag were working at 500 MHz and above. The one and only so-called SWR meter I have stops at 30 MHz. ;o) ---- Reg. |
Cecil Moore wrote:
Ian White G/GM3SEK wrote: All agreed. Along with the math that Cecil has retrieved and quoted again, everything points towards the distance in question being a function of coax diameter only; and not wavelength. Please forgive my previous senior moment. It was ~2% of a wavelength at 10 MHz for RG-213. It appears that one foot of coax on each side of a Bird wattmeter is enough to establish Z0 at 50 ohms which forces Vfor/Ifor=Vref/Iref=50, the necessary Bird boundary conditions. The Bird doesn't require any upstream and downstream boundary conditions. You can insert the instrument between any source impedance and any load impedance, and what it reports is entirely about the load impedance, unaffected by the source impedance. However, it was scaled and calibrated assuming a 50 ohm system reference impedance, so in order to read correctly, it requires you to agree that your system reference impedance is 50 ohms too. The element is trying to sample the voltage and current at a single point along the instrument's internal line. Because that line is physically quite long, it is built as an accurate 50-ohm line so that the instrument will cause minimal disturbance when inserted somewhere along a 50-ohm cable. -- 73 from Ian G/GM3SEK 'In Practice' columnist for RadCom (RSGB) http://www.ifwtech.co.uk/g3sek |
On Tue, 11 Oct 2005 16:57:51 GMT, Cecil Moore wrote:
****Quote**** Newsgroups: sci.physics.electromag From: "Kevin G. Rhoads" Date: Tue, 07 Oct 2003 12:49:14 -0400 Subject: Transmission Line Question .... So unless almost all the power diverts into an undesireable mode (by a factor of more than a million to one), one foot of cable should see pure TEM at the end. ***End Quote*** But Cecil, nowhere in the analysis you quoted does it estimate how much power is diverted from the dominant mode at the discontinuity. If the explanation of the discontinuity is that some power is converted from dominant propagation mode to another mode, and that those other modes are evanescent, it seems that this analysis of the impact of the discontinuity considers only estimating the decay rate of the evanescent modes without estimation of the relative magnitude of the power diverted to those modes in the first place. Owen -- |
Reg Edwards wrote:
Let this little anecdote be a friendly warning to they who use meters with a 0 to infinity SWR scale, or scaled in terms of forward and reverse power. If the scale were linearly calibrated for |rho| = 0 to 1, would you still be objecting? SWR = (1+|rho|)/(1-|rho|) for 0 = |rho| = 1 When SWR = infinity, it doesn't mean infinite current through the meter. It just means that Vref = Vfor where |Vref|/|Vfor| = |rho|. My Heathkit HM-15 allows for full scale to equal Vfor. Then Vref is applied. The scale is a linear indication for |rho|. The corresponding SWR scale just follows the above equation. -- 73, Cecil http://www.qsl.net/w5dxp |
Reg Edwards wrote:
Cec, you forgot to say sci.physics.electromag were working at 500 MHz and above. Not true, Reg. My question was specified using RG-213 at 10 MHz. -- 73, Cecil http://www.qsl.net/w5dxp |
Ian White G/GM3SEK wrote:
The Bird doesn't require any upstream and downstream boundary conditions. When Bird requires a 50 ohm environment, they are requiring 50 ohm boundary conditions for the reading to be valid. If you install the Bird in a 450 ohm environment on both sides of the wattmeter, for instance, it will NOT read a valid forward power and reflected power. In a matched-line 450 ohm environment with absolutely zero reflected power, the Bird will indicate an SWR of 9:1, a |rho| of 0.8 and a ratio of reflected power to forward power of 0.64 even when the reflected power is zero. -- 73, Cecil http://www.qsl.net/w5dxp |
Owen Duffy wrote:
If the explanation of the discontinuity is that some power is converted from dominant propagation mode to another mode, and that those other modes are evanescent, it seems that this analysis of the impact of the discontinuity considers only estimating the decay rate of the evanescent modes without estimation of the relative magnitude of the power diverted to those modes in the first place. I've always had a rule of thumb that 100 times the diameter of the coax was enough length to 99% establish the TEM mode so Kevin's explaination made sense to me. Apparently, you are not satisfied with Kevin's explaination. Kevin Rhodes email address is available on Google. The reason not to publish it here is to avoid spaming his email account. -- 73, Cecil http://www.qsl.net/w5dxp |
On Tue, 11 Oct 2005 21:15:22 GMT, Cecil Moore wrote:
Not true, Reg. My question was specified using RG-213 at 10 MHz. True enough, but in the context of the question as to whether the Bird 43 reads sufficiently accurately, the transmission line on which one is interested in the decay of the evanescent modes is the Bird Thruline coupler section, not Rg-213 or any other cable that might be attached to the Bird. Owen -- |
On Tue, 11 Oct 2005 21:25:53 GMT, Cecil Moore wrote:
Ian White G/GM3SEK wrote: The Bird doesn't require any upstream and downstream boundary conditions. When Bird requires a 50 ohm environment, they are requiring 50 ohm boundary conditions for the reading to be valid. If you install the Bird in a 450 ohm environment on both sides of the wattmeter, for instance, it will NOT read a valid forward power and reflected power. In a matched-line 450 ohm environment with absolutely zero reflected power, the Bird will indicate an SWR of 9:1, a |rho| of 0.8 and a ratio of reflected power to forward power of 0.64 even when the reflected power is zero. (I am assuming your 450 ohm line to be an unbalanced line, impractical as that is, but the issues of balance to unbalanced transition are just noise to the discussion.) Is this about whether the Bird readings are correct for the conditions on the Bird Thruline, or whether the meter readings are extensible to the adjacent transmission line without further interpretation / modelling? The Bird readings should be correct for the conditions on the Bird Thruline. You can safely extend those measurements literally to the adjacent line where the adjacent line is the same as the Bird Thruline and of negligible loss. In other cases, knowing the line parameters, you may be able to use the measurements to some extent to calculating some conditions on the other line. Though the Bird readings in your example for Forward and Reflect Power cannot be assumed valid for the adjacent line, the net power should be correct. I don't think anyone is suggesting that the Bird could be used in a general sense to estimate the VSWR on your 450 ohm line. Owen -- |
On Tue, 11 Oct 2005 14:09:03 -0400, "Fred W4JLE"
wrote: I would then assume you disregard anything written in books as it falls in the same category. Hi Fred, Certainly anything that is third hand and name dropping - but you already knew that from my previous posting. 73's Richard Clark, KB7QHC |
On Tue, 11 Oct 2005 17:45:51 GMT, Cecil Moore wrote:
Exactly what did you find technically wrong with that third hand quote? Why would I bother? It reveals any one of several many problems: 1. Incorrect reporting through poor transcription; 2. Presumed ascription of source; 3. No access to the original (as third hand offers no citations, or if it did, it renders third hand reporting as immaterial); 4. No access to the presumed source of the third hand-off; 5. No access to the original (op. cit.) author; 6. Discussion does not attend the topic (and is of no interest to me, nor others barring their continuing that line of inquiry - I won't hold my breath for that); 7. Third hand-off reporting is the lame equivalent of celebrity news. |
Cecil Moore wrote:
Ian White G/GM3SEK wrote: The Bird doesn't require any upstream and downstream boundary conditions. When Bird requires a 50 ohm environment, they are requiring 50 ohm boundary conditions for the reading to be valid. No, they're not. They are requiring a 50-ohm system reference impedance. What you call the "impedance environment" consists of physical things like the source impedance, line impedance and load impedance. You're confusing those with the system reference impedance, which something completely different. System reference impedance is purely a matter of definition. The most common choice is 50 ohms... and by definition, that means 50 ohms exactly. Having made that choice, then you obviously design and calibrate your instruments to give correct readings in an impedance environment that is as close to your chosen reference impedance as you can practically make it. Your example shows the difference between impedance environment and reference impedance most clearly. If you install the Bird in a 450 ohm environment on both sides of the wattmeter, for instance, it will NOT read a valid forward power and reflected power. In a matched-line 450 ohm environment with absolutely zero reflected power, the Bird will indicate an SWR of 9:1, a |rho| of 0.8 and a ratio of reflected power to forward power of 0.64 even when the reflected power is zero. You have changed the impedance environment to 450 ohms, and that's fine... but all of the Bird's readings are perfectly correct if the system reference impedance remains defined at 50 ohms. The reason why say they are incorrect is that you also changed your definition of system reference impedance to 450 ohms, without acknowledging that you did it. It's like doing a financial calculation without mentioning that you switched into another base currency... darn right the results are not valid. -- 73 from Ian G/GM3SEK 'In Practice' columnist for RadCom (RSGB) http://www.ifwtech.co.uk/g3sek |
On Tue, 11 Oct 2005 21:11:55 +0100, Ian White G/GM3SEK
wrote: Thank you, you're right. The key difference between direct and indirect measurements is not about the need for mathematics; it's about the need for additional input from theory. What I should have said is: Hi Ian, Remarkable touch of admission - especially to my over-arching method of criticism. Another point needs to be attended; the discussion of the measurement of SWR seems quite, and absurdly, drawn in kindergarten terms of mathematics as if the determination were king and the numbers simply fell out be virtue of cranking the equation. Nothing could be further from the truth. As much as Reg pines away about what a SWR does not measure, absolutely the same could be said for his unspoken inference that probe measurement along a line does measure it. True, probing the line reveals a pattern that in the mind conforms to the expectation of standing waves, but this is simply trying to measure your own shadow when each time you stretch out the rule your shadow moves further out. What size is your shadow - when? Using the formula everyone here leans upon as the archetypal equation for SWR, and claiming they've measured at the appropriate points along the line (undoubtedly only in their imagination) easily leads to errors above 20%. Worse yet is that this same formula fails utterly at the bench (am I embarrassing anyone?) for any but the most pedestrian of SWRs which are easily resolved by a SWR meter in the first place. Beyond this issue of accuracy (certainly no one is interested in that are they?) stands the fictions of requiring slightly more than a quarterwave length, or access along the line to both the trough and the peak. Anyone so hamstrung to NEED these criteria, hasn't ever really faced the problem of measuring SWR on an open line in the first place. The double-minima method offers an exceptional accuracy for high SWRs and occupies a smaller region of line than otherwise demanded. Measuring at the minima also reduces the error introduced in the very act of measuring SWR. To this last, how many here can guarantee their probes will approach the line with the same offset? There's a very good reason why SWR probes are mounted on vernier carriages. How many would recognize when the probes were too deep, or not deep enough to justify the measurement? To imagine any approaching the line with hand held leads raises the prospect of shooting marbles without thumbs. As to these meters that everyone is rushing to use - Square Law or Linear? Don't know the difference? You don't know accuracy or how to obtain it when you have no choice. How do you render a Square Law detector linear? How do you linearize a Square Law detector measurement? No concern? You aren't measuring SWR then either. The method of measurement for low, medium, and high SWRs is not the same. One size does not fit all as the discussion in this group might imply (from that same lack of actually having done it). Even the math is different - and if any argue that this observation flies in the face of simple transmission line equations, then these casual tourists are comfortably remote from actually measuring the rough terrain of SWR. However, none of this practicality is going to disturb the armchair SWR analyzer. It comes to their great fortune that one simple instrument will probably offer far more accuracy than they could ever obtain by trying to be literal about SWR "on the line." 73's Richard Clark, KB7QHC |
Owen Duffy wrote:
Cecil Moore wrote: Not true, Reg. My question was specified using RG-213 at 10 MHz. True enough, but in the context of the question as to whether the Bird 43 reads sufficiently accurately, the transmission line on which one is interested in the decay of the evanescent modes is the Bird Thruline coupler section, not Rg-213 or any other cable that might be attached to the Bird. I didn't read it that way, Owen. IMO, the real question is: What length of 50 ohm coax needs to be attached to the Bird input and output to ensure that a 50 ohm environment is present? -- 73, Cecil http://www.qsl.net/w5dxp |
Owen Duffy wrote:
I don't think anyone is suggesting that the Bird could be used in a general sense to estimate the VSWR on your 450 ohm line. I thought that was the subject of the discussion. -- 73, Cecil http://www.qsl.net/w5dxp |
Richard Clark wrote:
Certainly anything that is third hand and name dropping - but you already knew that from my previous posting. It's obvious that you cannot bring yourself to believe that e=mc^2. -- 73, Cecil http://www.qsl.net/w5dxp |
On Wed, 12 Oct 2005 02:04:52 GMT, Cecil Moore wrote:
Owen Duffy wrote: I don't think anyone is suggesting that the Bird could be used in a general sense to estimate the VSWR on your 450 ohm line. I thought that was the subject of the discussion. From an earlier post: In the case of the Bird 43, I suggest that if had, say, at 1MHz, 75 ohm line and a 75 ohm load on the load side, that the V/I raio for the travelling waves in the region of the sampling element would be so close to 50 ohms as to not materially affect the accuracy of measurements on the 50 ohms coupler section, irrespective of the fact that the sampling element has only 0.02% of a wavelength of 50 ohm line on its load side. (For avoidance of doubt, nothing in the foregoing is to imply the Bird 43 would be directly measuring or indicating the conditions on the 75 ohm line.) Owen -- |
Ian White G/GM3SEK wrote:
You have changed the impedance environment to 450 ohms, and that's fine... but all of the Bird's readings are perfectly correct if the system reference impedance remains defined at 50 ohms. I have changed the system reference impedance to 450 ohms. Assuming a tube PA with a pi-net output, 50 ohms doesn't exist anywhere anymore. The system reference impedance is no longer 50 ohms so the Bird wattmeter is being abused and misused. You can do the same thing by using a DC voltmeter on an RF voltage or by using a hammer on a screw. If you want to know the SWR on 450 ohm line, use a 450 ohm SWR meter. -- 73, Cecil http://www.qsl.net/w5dxp |
Owen Duffy wrote:
In the case of the Bird 43, I suggest that if had, say, at 1MHz, 75 ohm line and a 75 ohm load on the load side, that the V/I raio for the travelling waves in the region of the sampling element would be so close to 50 ohms as to not materially affect the accuracy of measurements on the 50 ohms coupler section, irrespective of the fact that the sampling element has only 0.02% of a wavelength of 50 ohm line on its load side. If there is 75 ohm coax on the input of the Bird, the reflected power reported by the Bird on the coax will be off by an infinite percent. That's pretty inaccurate. -- 73, Cecil http://www.qsl.net/w5dxp |
On Wed, 12 Oct 2005 02:06:22 GMT, Cecil Moore wrote:
It's obvious that you cannot bring yourself to believe that e=mc^2. If "that is obvious" to you, then such are your problems of a third hand education resulting in uncontrolled topic inflation. |
On Wed, 12 Oct 2005 02:03:10 GMT, Cecil Moore wrote:
What length of 50 ohm coax needs to be attached to the Bird input and output to ensure that a 50 ohm environment is present? None. |
On Wed, 12 Oct 2005 02:25:33 GMT, Cecil Moore wrote:
Owen Duffy wrote: In the case of the Bird 43, I suggest that if had, say, at 1MHz, 75 ohm line and a 75 ohm load on the load side, that the V/I raio for the travelling waves in the region of the sampling element would be so close to 50 ohms as to not materially affect the accuracy of measurements on the 50 ohms coupler section, irrespective of the fact that the sampling element has only 0.02% of a wavelength of 50 ohm line on its load side. If there is 75 ohm coax on the input of the Bird, the reflected power reported by the Bird on the coax will be off by an infinite percent. That's pretty inaccurate. The Bird does not measure or report the conditions on the coax, it measures and reports the conditions in the immediate region of the sampling element which is some 40mm inside the Thruline coupler section. Owen -- |
Owen Duffy wrote:
The Bird does not measure or report the conditions on the coax, it measures and reports the conditions in the immediate region of the sampling element which is some 40mm inside the Thruline coupler section. I don't know what this argument is all about. Consider the following: XMTR---75 ohm coax---Bird---75 ohm load Are you saying the Bird's placement will result in a reflection coefficient of 0.2? I seriously doubt that is true. -- 73, Cecil http://www.qsl.net/w5dxp |
On Wed, 12 Oct 2005 04:06:07 GMT, Cecil Moore wrote:
I seriously doubt that is true. We are genuinely grateful that you don't list all the combinations and permutations of those topics of invention you "seriously doubt" being true... .... or false. |
On Wed, 12 Oct 2005 04:06:07 GMT, Cecil Moore wrote:
Owen Duffy wrote: The Bird does not measure or report the conditions on the coax, it measures and reports the conditions in the immediate region of the sampling element which is some 40mm inside the Thruline coupler section. I don't know what this argument is all about. Consider the following: XMTR---75 ohm coax---Bird---75 ohm load Are you saying the Bird's placement will result in a reflection coefficient of 0.2? I seriously doubt that is true. I don't have the equipment at hand to do that experiment, but I have done another experiment. XMTR -- 2m of RG58 -- Bird43 -- 1.2m of RG213 Bird43 -- 20m RG6 (75 ohms) -- antenna. 1.2m of 50 ohm coax between the Birds is 4.2% of an electrical (wavelength.) I have made measurements with only one 100W slug which is moved from instrument to instrument. The tx was adjusted to 100W forward on the first instrument. Both instruments read 100W forward. Both instruments read 2W reflected. When I swap the instruments around, I get the same results. It is only a simple test, but I am not convinced that measurements from one position are signficantly different to the other position, despite the transmission line "environment" being different. I am not surprised that both instruments read similarly, despite the fact that one doesn't have any 50 ohm coax on the load side of itself, whereas the other one does. Owen -- |
Owen Duffy wrote:
XMTR -- 2m of RG58 -- Bird43 -- 1.2m of RG213 Bird43 -- 20m RG6 (75 ohms) -- antenna. I don't have any argument with your results. Try this instead. XMTR -- 2m of RG58 -- Bird43 -- 1.2m of RG6 Bird 43 -- 20m RG6 -- antenna The second Bird will NOT indicate the actual SWR on the RG6. -- 73, Cecil http://www.qsl.net/w5dxp |
On Wed, 12 Oct 2005 05:36:38 GMT, Cecil Moore wrote:
Owen Duffy wrote: XMTR -- 2m of RG58 -- Bird43 -- 1.2m of RG213 Bird43 -- 20m RG6 (75 ohms) -- antenna. I don't have any argument with your results. Try this instead. XMTR -- 2m of RG58 -- Bird43 -- 1.2m of RG6 Bird 43 -- 20m RG6 -- antenna I won't waste the time, I can predict that they will most likely be different. Transmission line theory tells me that the Z in the region of each Bird will be different, and that will probably result in a different indicated VSWR. It is a sidetrack, just noise. The measurements I reported were identical, although one Bird was surrounded by 50 ohm line, and the other had 75 ohm line on one side of it. The 75 ohm line did not cause a measureable difference in meter readings in that simple trial. Owen -- |
Owen Duffy wrote:
It is a sidetrack, just noise. The main point of the discussion has been: An SWR meter calibrated for Z0=50 ohms will not accurately report the actual SWR on a line that is not Z0=50 ohms. Of the four following configurations, in a lossless situation, which one accurately reports the SWR on both sides of the SWR meter? 1. XMTR---50 ohm coax---SWR meter---50 ohm coax---load 2. XMTR---50 ohm coax---SWR meter---75 ohm coax---load 3. XMTR---75 ohm coax---SWR meter---50 ohm coax---load 4. XMTR---75 ohm coax---SWR meter---75 ohm coax---load -- 73, Cecil http://www.qsl.net/w5dxp |
Cecil Moore wrote: If there is 75 ohm coax on the input of the Bird, the reflected power reported by the Bird on the coax will be off by an infinite percent. That's pretty inaccurate. Why wouldn't the meter correctly indicate the reflection resulting from the mismatch between the 50 ohm wattmeter and the 75 ohm transmission line? ac6xg |
On Wed, 12 Oct 2005 11:56:44 GMT, Cecil Moore wrote:
Owen Duffy wrote: It is a sidetrack, just noise. The main point of the discussion has been: An SWR meter calibrated for Z0=50 ohms will not accurately report the actual SWR on a line that is not Z0=50 ohms. No Cecil, the thread subject and the quote of your text in the first message of the post was the main point of discussion: The transmission line length must only be long enough such that the V/I ratio is forced to the Z0 value. According to some pretty smart guys I asked, that's about 2% of a wavelength. It seems that the statement you have quoted is not born out in practice, though I note that you "seriously doubt that is true". I have found out what I needed to know, thanks... Owen -- |
All times are GMT +1. The time now is 07:42 AM. |
Powered by vBulletin® Copyright ©2000 - 2025, Jelsoft Enterprises Ltd.
RadioBanter.com