RadioBanter

RadioBanter (https://www.radiobanter.com/)
-   Boatanchors (https://www.radiobanter.com/boatanchors/)
-   -   getting bit by my FT-101EE chassis (https://www.radiobanter.com/boatanchors/83148-getting-bit-my-ft-101ee-chassis.html)

[email protected] November 30th 05 05:47 AM

getting bit by my FT-101EE chassis
 
All,

I don't know if I am grounding my station correctly.

The radials of my 20m vertical are connected to my trailer's electrical
system ground rod. My coax shield is connected both to the radials and
the ground rod. I plug my antenna into the Yaesu and turn it on. I
can hear stations just fine, and I have no problems touching the
chassis. However, the instant I disconnected the antenna but hang onto
the coax, I got a mild shock on both arms if I should momentarily
touch the chassis of the Yaesu. So, I understand I have a problem.

Now I noticed that the Yaesu uses a 2-prong AC cord adapter, which is
"before code" and therefore is unsafe by today's standards. If I
rewrire the AC cord to 3-prong, should that remove the hazard? If so,
what pinout do I use? The FT-101 Shop service manual does not list
where positive, negative, and neutral should be on the Yaesu power
plug.in Figure 1-2.

Thanks,

The Eternal Squire

P.S. I hope I have not long-term defibrillated myself. Should I visit
a hospital for cardiac system damage even if the shock was mild? I now
realize that I probably could have been killed. Right now I have
everything unplugged and disconnected until I can get better advice.


Bill November 30th 05 07:24 AM

getting bit by my FT-101EE chassis
 
wrote:

All,

I don't know if I am grounding my station correctly.


You should probably connect the rig (chassis/cabinet) to your ground
system somehow. Is there a grounding lug provision on the rear of the
chassis itself?

3-wire cord should do the trick - *IF* your trailer electrical ground is
connected to its frame, etc.

-Bill

Roger November 30th 05 09:41 AM

getting bit by my FT-101EE chassis
 
On 29 Nov 2005 21:47:59 -0800, wrote:

All,

I don't know if I am grounding my station correctly.


Years ago I had a FT101B try to kill me.

I had the system grounded, but it was a minimal ground. The
transceiver was about 50 feet to the East of the service entrance
ground. The coax tied to a 40 meter vertical out into he west yard
which was about 100 feet to the west of the service entrance. There
was a single ground round and a number of bare #10 radials tied to the
ground rod.

It was spring, the snow had melted and the ground was wet and soggy.
One of the radials had come loose and curled up around the base of the
antenna, so I picked it up, pulled it straight, bent a kink in the end
to stick in the ground. I knelt down to stick that end in the ground.
When my knees touched the wet ground that sucker didn't tickle, it
grabbed me and held on *really* tight.

I fell backwards and when I went over backwards my knees broke
contact. I threw that wire as hard as I could under the circumstances.

I brought out my Simpson 260, stuck one probe in the ground about 6
inches out from the ground rod under the vertical and stuck the other
probe in as far out as I could reach. I measured 90 volts with that
VOM across about 5 or 6 feet of wet top soil.

A close inspection turned up a liberal solder joint at the power
connector on the back of the rig (inside) which under the right
conditions could contact the chassis. The cord was one of the un
polarized type.
It passed plenty of current, but not enough to trip the breaker. (this
was before the days of GFIs)

I removed a bit of solder and never had another problem with the rig.
Actually, I'd like to find another, nice, clean, FT101B to recreate
my old station, but I'll never forget that one.

Roger Halstead (K8RI & ARRL life member)
(N833R, S# CD-2 Worlds oldest Debonair)
www.rogerhalstead.com

The radials of my 20m vertical are connected to my trailer's electrical
system ground rod. My coax shield is connected both to the radials and
the ground rod. I plug my antenna into the Yaesu and turn it on. I
can hear stations just fine, and I have no problems touching the
chassis. However, the instant I disconnected the antenna but hang onto
the coax, I got a mild shock on both arms if I should momentarily
touch the chassis of the Yaesu. So, I understand I have a problem.

Now I noticed that the Yaesu uses a 2-prong AC cord adapter, which is
"before code" and therefore is unsafe by today's standards. If I
rewrire the AC cord to 3-prong, should that remove the hazard? If so,
what pinout do I use? The FT-101 Shop service manual does not list
where positive, negative, and neutral should be on the Yaesu power
plug.in Figure 1-2.

Thanks,

The Eternal Squire

P.S. I hope I have not long-term defibrillated myself. Should I visit
a hospital for cardiac system damage even if the shock was mild? I now
realize that I probably could have been killed. Right now I have
everything unplugged and disconnected until I can get better advice.


Scott Dorsey November 30th 05 02:43 PM

getting bit by my FT-101EE chassis
 
wrote:

I don't know if I am grounding my station correctly.

The radials of my 20m vertical are connected to my trailer's electrical
system ground rod. My coax shield is connected both to the radials and
the ground rod. I plug my antenna into the Yaesu and turn it on. I
can hear stations just fine, and I have no problems touching the
chassis. However, the instant I disconnected the antenna but hang onto
the coax, I got a mild shock on both arms if I should momentarily
touch the chassis of the Yaesu. So, I understand I have a problem.


So, DON'T DO THAT.

Now I noticed that the Yaesu uses a 2-prong AC cord adapter, which is
"before code" and therefore is unsafe by today's standards. If I
rewrire the AC cord to 3-prong, should that remove the hazard? If so,
what pinout do I use? The FT-101 Shop service manual does not list
where positive, negative, and neutral should be on the Yaesu power
plug.in Figure 1-2.


A three-prong plug will make the radio safe, but in fact as long as
the radio is plugged into the antenna, it's already safely grounded
by the anntena system. A three-prong plug will make it meet code,
though.

BUT, the real problem is that you have current leaking to chassis, and
your chassis has become hot. Look for an AC line filter or some
ceramic disc capacitors between the AC line and the chassis, used to
keep RF out of the power line (and out of the radio). It will be
leaky. Replace it, even if you think it's good.

P.S. I hope I have not long-term defibrillated myself. Should I visit
a hospital for cardiac system damage even if the shock was mild? I now
realize that I probably could have been killed. Right now I have
everything unplugged and disconnected until I can get better advice.


Keep your left hand in your pocket next time.

The thing about electrical injuries is that there is really nothing doctors
can do. When there is damage due to electrical power, cells become
elongated and the cell membranes break down. As this process continues,
the cell membranes break, the resistance of the tissue drops, and more
and more current flows. All the doctors can see is the surface burn,
they can't tell how bad the tissue damage is. So even in the case of
very serious electrical injury, the normal procedure is basically to wait
and see how much tissue dies. RF burns really terrify doctors, because
they look like serious electrical burns but have little or no actual
tissue damage (due to skin effect). So they look a lot worse than they
really are.
--scott
--
"C'est un Nagra. C'est suisse, et tres, tres precis."

Uncle Peter November 30th 05 11:18 PM

getting bit by my FT-101EE chassis
 

wrote in message
ups.com...
All,

I


If the radio has bypass caps on the line to chassis, and many do, you can
develop sixty or so volts AC from chassis to ground because the two
caps form a voltage divider. Measure the DC resistance between each
of the power lugs to the chassis, you should see infinite resistance.
Don't relay on the coax shell to provide a safety ground, you're only going
to end up getting knocked on your butt repeatedly when working on the
rig. The best bet is a three wire cord with safety ground.

Pete



[email protected] December 1st 05 04:52 AM

getting bit by my FT-101EE chassis
 
This is indeed the case for the FT-101E whose schematic I just
examined. What I did was remove the 2-wire cord, and then connect a
3-wire cord where plus and minus hot were in former locations, then
soldered the neutral wire of the cord to the plug's ground pin. Hope
that would work. The voltage divider effect bears out in the fact that
my original exposure to the AC was not immediately fatal.

I think from now on, I should NEVER operate a rig powered by a 2 wire
cord.... I should always replace with 3-wire on general principles.

The Eternal Squire


Chuck Harris December 1st 05 05:06 AM

getting bit by my FT-101EE chassis
 
wrote:
This is indeed the case for the FT-101E whose schematic I just
examined. What I did was remove the 2-wire cord, and then connect a
3-wire cord where plus and minus hot were in former locations, then
soldered the neutral wire of the cord to the plug's ground pin. Hope
that would work. The voltage divider effect bears out in the fact that
my original exposure to the AC was not immediately fatal.

I think from now on, I should NEVER operate a rig powered by a 2 wire
cord.... I should always replace with 3-wire on general principles.

The Eternal Squire


NO! Don't do that! The hot goes to the + hot, and the neutral goes
to the - hot, and the green wire goes to the chassis.

Never, never, never connect the neutral and the green wire together!
(Did I mention never?)

The only place in the whole house where that is supposed to happen is
in the service panel where the power comes into the house. Everywhere
else, it must remain separate. The bond wire (green) is purely for
safety. It saves your butt when currents accidentally leak out to
the chassis. If you have the bond connected to the neutral side of the
powerline, it can energize the chassis in certain wiring failure modes.

Please don't leave it that way, save some poor soul's bacon, and go back
and fix it correctly.

Thanks,

-Chuck

Ron December 1st 05 06:29 AM

getting bit by my FT-101EE chassis
 
I believe the important thing here is that a three wire plug be used and
that it gets wired correctly. I will never see why the neutral which is
grounded and green wire which is ground cannot be tied together. The
key here is that the plug can not get reversed like it could with the
two wire plug so getting hot AC on the chassis can never happen. If the
socket is miswired than as soon as you plug in your radio with the green
and neutral tied together your main fuse will blow. I sure would like to
know what certain wiring failure modes could energize the chassis ?
Ground is Ground period. If the original two wire plug would have been
polarized in the very beginning I expect that three wire plug would have
never happened.


Chuck Harris wrote:

wrote:

This is indeed the case for the FT-101E whose schematic I just
examined. What I did was remove the 2-wire cord, and then connect a
3-wire cord where plus and minus hot were in former locations, then
soldered the neutral wire of the cord to the plug's ground pin. Hope
that would work. The voltage divider effect bears out in the fact that
my original exposure to the AC was not immediately fatal.

I think from now on, I should NEVER operate a rig powered by a 2 wire
cord.... I should always replace with 3-wire on general principles.

The Eternal Squire


NO! Don't do that! The hot goes to the + hot, and the neutral goes
to the - hot, and the green wire goes to the chassis.

Never, never, never connect the neutral and the green wire together!
(Did I mention never?)

The only place in the whole house where that is supposed to happen is
in the service panel where the power comes into the house. Everywhere
else, it must remain separate. The bond wire (green) is purely for
safety. It saves your butt when currents accidentally leak out to
the chassis. If you have the bond connected to the neutral side of the
powerline, it can energize the chassis in certain wiring failure modes.

Please don't leave it that way, save some poor soul's bacon, and go back
and fix it correctly.

Thanks,

-Chuck



[email protected] December 1st 05 06:30 AM

getting bit by my FT-101EE chassis
 
I believe the important thing here is that a three wire plug be used and
that it gets wired correctly. I will never see why the neutral which is
grounded and green wire which is ground cannot be tied together. The
key here is that the plug can not get reversed like it could with the
two wire plug so getting hot AC on the chassis can never happen. If the
socket is miswired than as soon as you plug in your radio with the green
and neutral tied together your main fuse will blow. I sure would like to
know what certain wiring failure modes could energize the chassis ?
Ground is Ground period. If the original two wire plug would have been
polarized in the very beginning I expect that three wire plug would have
never happened.


Chuck Harris wrote:

wrote:

This is indeed the case for the FT-101E whose schematic I just
examined. What I did was remove the 2-wire cord, and then connect a
3-wire cord where plus and minus hot were in former locations, then
soldered the neutral wire of the cord to the plug's ground pin. Hope
that would work. The voltage divider effect bears out in the fact that
my original exposure to the AC was not immediately fatal.

I think from now on, I should NEVER operate a rig powered by a 2 wire
cord.... I should always replace with 3-wire on general principles.

The Eternal Squire


NO! Don't do that! The hot goes to the + hot, and the neutral goes
to the - hot, and the green wire goes to the chassis.

Never, never, never connect the neutral and the green wire together!
(Did I mention never?)

The only place in the whole house where that is supposed to happen is
in the service panel where the power comes into the house. Everywhere
else, it must remain separate. The bond wire (green) is purely for
safety. It saves your butt when currents accidentally leak out to
the chassis. If you have the bond connected to the neutral side of the
powerline, it can energize the chassis in certain wiring failure modes.

Please don't leave it that way, save some poor soul's bacon, and go back
and fix it correctly.

Thanks,

-Chuck



Bill December 1st 05 07:15 AM

getting bit by my FT-101EE chassis
 
Ron wrote:


and neutral tied together your main fuse will blow. I sure would like to
know what certain wiring failure modes could energize the chassis ?
Ground is Ground period.


No, not really.
You're thinking like an electrician saying the chassis is energized.
That can happen too in a failure mode but the original poster's gist was
that he got that normal low ma bite that one gets when one creates
different ground points as opposed to a common ground.

The answer here is to tie the grounds together as short as possible. Of
course the OP is going to get a tingle when his rig is 'grounded' only
via the AC with inherent leakage of caps/yadda/yadda versus his external
antenna/trailer ground. Thats normal.

Sorry to belabour but this has been addressed in most every electronic
publication since electricity was 'invented'.

I could ground all my stuff to the hilt but you would have to pay me to
pound a separate ground rod and lick my fingers and put my hand between
the rig and the new rod. Ground ISNT ground unless they are at the same
potential.

If OP wants a no-bite situation he should visualize the ground path via
his coax versus the radio ground via the trailer AC wiring. Until the
two are essentially the same a difference in potential exists.

-Bill

Roger December 1st 05 09:10 AM

getting bit by my FT-101EE chassis
 
On Wed, 30 Nov 2005 18:18:48 -0500, " Uncle Peter"
wrote:


wrote in message
oups.com...
All,

I


If the radio has bypass caps on the line to chassis, and many do, you can
develop sixty or so volts AC from chassis to ground because the two
caps form a voltage divider. Measure the DC resistance between each
of the power lugs to the chassis, you should see infinite resistance.
Don't relay on the coax shell to provide a safety ground, you're only going
to end up getting knocked on your butt repeatedly when working on the
rig. The best bet is a three wire cord with safety ground.


Yup, as I said when in the earlier post where my FT101B tried to kill
me with a bare copper wire tied to a ground rod.

Roger Halstead (K8RI & ARRL life member)
(N833R, S# CD-2 Worlds oldest Debonair)
www.rogerhalstead.com

Pete

Roger

Chuck Harris December 1st 05 02:34 PM

getting bit by my FT-101EE chassis
 
Ron wrote:
I believe the important thing here is that a three wire plug be used and
that it gets wired correctly. I will never see why the neutral which is
grounded and green wire which is ground cannot be tied together. The
key here is that the plug can not get reversed like it could with the
two wire plug so getting hot AC on the chassis can never happen. If the
socket is miswired than as soon as you plug in your radio with the green
and neutral tied together your main fuse will blow. I sure would like to
know what certain wiring failure modes could energize the chassis ?
Ground is Ground period. If the original two wire plug would have been
polarized in the very beginning I expect that three wire plug would have
never happened.



Hi Ron,

You are thinking like a newbie engineer... you haven't yet discovered
multiple failures, and mistakes. If nothing fails, you are right, there
is no harm in tieing the safety ground and neutral together.

But let's first discuss the purpose of the safety ground: It
is there to make it very unlikely that the cases of appliances could ever
become elevated above earth ground. This is to protect a barefooted doofus
from getting electrocuted when he is standing on the cement floor in the
basement, and trys to operate his FT-101E. The *secondary* purpose of the
safety ground is to provide a return that will blow the circuit breaker if
the hot lead accidentally becomes shorted to the case of the FT-101E.

The way the safety ground provides these protections is by being
connected to the centertap of the pole pig (neutral), and to a grounding
rod that sticks into the earth at the house. This connection is done
at the service panel where power service enters the house. The grounding
rod is there to make sure that the safety ground, and thus the cases of
the appliances, stays at the same potential as the cement floor in your
basement.

Back in the old 2 wire days, when the neutral side of the plug wire was
connected to the chassis, and you were expected to turn the plug around
until it didn't tingle, if the cord's neutral wire broke, current would
pass through the appliance's circuitry to the chassis connection, and
as a result the chassis would become hot relative to the earth ground
(Doofus's feet on the concrete slab). Doofus would be pushing up daisies.

Let's move forward to the days of the 3 wire plug, and the safety ground...

Saint Chuck has wired Doofus's FT101E so that the hot lead goes to Hot+,
and the neutral lead goes to Hot-, and the safety ground lead goes to the
chassis:

Doofus, likes to unplug his FT101E whenever he isn't using it, and he likes to
windup the cord to look just like it did when the radio was new-in-the-box.
After doing this for a while, the hot, or neutral lead breaks. Doofus plugs
in his radio, and turns it on, and it doesn't work! So he asks Saint Chuck
to fix his radio, and life marches on. If, on the other hand, it wasn't the
hot, or neutral lead that was broken, but rather it was the safety ground lead,
Doofus wouldn't know it was broken, and would continue to operate, a little
less safe, but still safe, because the radio was wired correctly... and if
somewhere down the path, we added an additional wire to the broken safety
ground, the radio would stop working, but would still be safe.

Now, lets suppose that instead of Saint Chuck wiring Doofus's FT101E, it was
wired by some squire. This squire wired the hot lead to Hot+, and then wired
the neutral lead, safety ground lead, and chassis to Hot-.

Back to Doofus:

Doofus, likes to unplug his FT101E whenever he isn't using it, and he likes to
windup the cord to look just like it did when the radio was new-in-the-box.
After doing this for a while, the neutral lead breaks. Doofus plugs
in his radio, and trys it out, and it works just fine! Doofus continues
operating this way, and eventually, another wire in the cord breaks. If
that wire happens to be the hot lead, the radio will quit, and barefoot
Doofus will take the radio back to the squire for a rewire job. If that wire
happens to be the safety ground lead, the chassis of the FT101E will now be
at full power line potential (current passing from hot lead through the radio's
circuits, to the chassis/hot- connection), and barefoot Doofus will be
pushing up daisies.

The safety ground must NEVER be connected to the neutral at the load!
NEVER!

Be safe, allow for multiple failures, and fix the cord so that the hot lead
goes to hot+, the neutral goes to hot-, and the safety ground lead goes to
the chassis.

-Chuck Harris

Ron December 1st 05 03:14 PM

getting bit by my FT-101EE chassis
 
OK that is one case where your need two failures to cause a hot chassis.
Now for Doofus to get electrocuted he will also have to have one
hand on this deaf radio and one hand on the radio that has a metal
chassis that is plugged into a socket with a good ground. The problem
you could also have a similar problem even if the neutral was wired
correctly (not tied to ground). If the ground wire broke in the cord or
inside the radio and then a capacitor or a transformer had an internal
short to the chassis or there was a resistor from hot to chassis ground
then the chassis would become hot. The so called safety ground is not a
100% sure thing in the case of a failure. Because safety grounds are as
prone to fail as anything a third external wire tying all metal cabinet
radios together is the only safety measure if one has a table full of
these old AC powered beasts.

Yes it is not a good policy to tie the ground and neutral together. I
just felt that a good explanation of why not to do so was required
instead of just a blanket statement stating "The safety ground must
NEVER be connected to the neutral at the load !NEVER! "

But he on the safe side and ground those boatanchors together. (you can
buy a bigger boat that way).


Thanks
Ron WA0KDS









Doofus, likes to unplug his FT101E whenever he isn't using it, and he
likes to
windup the cord to look just like it did when the radio was new-in-the-box.
After doing this for a while, the neutral lead breaks. Doofus plugs
in his radio, and trys it out, and it works just fine! Doofus continues
operating this way, and eventually, another wire in the cord breaks. If
that wire happens to be the hot lead, the radio will quit, and barefoot
Doofus will take the radio back to the squire for a rewire job. If that
wire
happens to be the safety ground lead, the chassis of the FT101E will now be
at full power line potential (current passing from hot lead through the
radio's
circuits, to the chassis/hot- connection), and barefoot Doofus will be
pushing up daisies.





Chuck Harris December 1st 05 04:17 PM

getting bit by my FT-101EE chassis
 
Ron wrote:
OK that is one case where your need two failures to cause a hot chassis.
Now for Doofus to get electrocuted he will also have to have one hand
on this deaf radio and one hand on the radio that has a metal chassis
that is plugged into a socket with a good ground.


He won't know the radio is "deaf" until he trys to turn it on... and you
know Doofus, he broke the on/off knob years ago, and he always turns the
bare aluminum shaft while he is standing barefoot on the cement floor.

The problem you
could also have a similar problem even if the neutral was wired
correctly (not tied to ground). If the ground wire broke in the cord or
inside the radio and then a capacitor or a transformer had an internal
short to the chassis or there was a resistor from hot to chassis ground
then the chassis would become hot. The so called safety ground is not a
100% sure thing in the case of a failure.


Nothing is ever 100% perfectly safe. But you do try and improve the odds
as much as you can comfortably afford. Adding a safety wire system gives
you much more bang for the buck in terms of safety than the simple addition
of 33% more wire would appear to offer.

Because safety grounds are as
prone to fail as anything a third external wire tying all metal cabinet
radios together is the only safety measure if one has a table full of
these old AC powered beasts.

Yes it is not a good policy to tie the ground and neutral together. I
just felt that a good explanation of why not to do so was required
instead of just a blanket statement stating "The safety ground must
NEVER be connected to the neutral at the load !NEVER! "


The problem here is I could write for the next week describing all of the
failure modes I know about that can and do happen with power distribution
grounds, and grounding. But I really don't have that kind of time. It
is far easier for me to tell you that doing such a thing is unsafe, and
that you should NEVER connect the safety ground to the neutral at the load.

If I tell you that E = I * R are you going to make me prove it? Or can I
just tell you from a position of assumed authority that this is a true
relationship? You can go and find a book that will tell you E = I*R, and
likewise, you can find a book, or do a google search, to find out why you
should NEVER connect the safety ground to the neutral at the load.

-Chuck

Don Bowey December 1st 05 04:44 PM

getting bit by my FT-101EE chassis
 
On 11/30/05 10:29 PM, in article , "Ron"
wrote:

I believe the important thing here is that a three wire plug be used and
that it gets wired correctly. I will never see why the neutral which is
grounded and green wire which is ground cannot be tied together.


You declare that you will never understand the requirement, and obviously
have not searched for information about it, so why do you waste space with
such a post?

(snip)


Chuck Harris December 1st 05 05:40 PM

getting bit by my FT-101EE chassis
 
Ron wrote:
The so called safety ground is not a
100% sure thing in the case of a failure. Because safety grounds are as
prone to fail as anything a third external wire tying all metal cabinet
radios together is the only safety measure if one has a table full of
these old AC powered beasts.


I forgot to mention one additional tidbit: Safety ground wires are *not* as
prone to failure as are the current carrying hot and neutral leads.

I have repaired numerous power cords on portable appliances, drills, saws,
etc. There is one type of failure that I see over and over again, a broken
power lead inside of the cord, with no sign of failure on the outside.
The failure is usually at a point of stress, such as just after the strain
relief for the cord. When I take the cord apart (usually to shorten it,
and reconnect it inside the appliance) I have always found the break to be
one that looks as if someone snipped the wire off clean and square! There
is some blackening from the arcing that invariably occurs, but the break is
clean and square. This is not at all like the way a twisted rope fails.

I believe the reason for this, is a single strand breaks due to flexing, a
mfr. flaw, or stress. When this strand breaks, it increases the current density
of the wire at that point. The wire now gets hotter at the break, and this
makes it more prone to stress failures, and another strand breaks... then another,
and pretty soon the wire is seriously overloaded, and the rest of the strands
pop.

If I find a break in the safety ground wire, it is always a physical failure
caused by the wire getting wound up in the drill bit, or cut off by the saw, or
sheared off by a tool box in the bed of the truck.

-Chuck

Ron December 1st 05 06:07 PM

getting bit by my FT-101EE chassis
 


Chuck Harris wrote:

Ron wrote:
The so called safety ground is not a

100% sure thing in the case of a failure. Because safety grounds are
as prone to fail as anything a third external wire tying all metal
cabinet radios together is the only safety measure if one has a table
full of these old AC powered beasts.



I forgot to mention one additional tidbit: Safety ground wires are *not* as
prone to failure as are the current carrying hot and neutral leads.

I have repaired numerous power cords on portable appliances, drills, saws,
etc. There is one type of failure that I see over and over again, a broken
power lead inside of the cord, with no sign of failure on the outside.
The failure is usually at a point of stress, such as just after the strain
relief for the cord. When I take the cord apart (usually to shorten it,
and reconnect it inside the appliance) I have always found the break to be
one that looks as if someone snipped the wire off clean and square! There
is some blackening from the arcing that invariably occurs, but the break is
clean and square. This is not at all like the way a twisted rope fails.

I believe the reason for this, is a single strand breaks due to flexing, a
mfr. flaw, or stress. When this strand breaks, it increases the current
density
of the wire at that point. The wire now gets hotter at the break, and this
makes it more prone to stress failures, and another strand breaks...
then another,
and pretty soon the wire is seriously overloaded, and the rest of the
strands
pop.

If I find a break in the safety ground wire, it is always a physical
failure
caused by the wire getting wound up in the drill bit, or cut off by the
saw, or
sheared off by a tool box in the bed of the truck.

-Chuck



Good point and thanks I think a few others understand the problem now
more than they did.



Ron December 1st 05 06:15 PM

getting bit by my FT-101EE chassis
 


Don Bowey wrote:

On 11/30/05 10:29 PM, in article , "Ron"
wrote:


I believe the important thing here is that a three wire plug be used and
that it gets wired correctly. I will never see why the neutral which is
grounded and green wire which is ground cannot be tied together.



You declare that you will never understand the requirement, and obviously
have not searched for information about it, so why do you waste space with
such a post?

(snip)


Just thought a little more info would be good for the group. I fully
understand the issue of grounds.

Have a good day and hope someone got a better feel for why AC grounds
are important.

Ron


Ron December 1st 05 06:20 PM

getting bit by my FT-101EE chassis
 


Chuck Harris wrote:

Ron wrote:

OK that is one case where your need two failures to cause a hot
chassis. Now for Doofus to get electrocuted he will also have to
have one hand on this deaf radio and one hand on the radio that has a
metal chassis that is plugged into a socket with a good ground.



He won't know the radio is "deaf" until he trys to turn it on... and you
know Doofus, he broke the on/off knob years ago, and he always turns the
bare aluminum shaft while he is standing barefoot on the cement floor.

The problem you

could also have a similar problem even if the neutral was wired
correctly (not tied to ground). If the ground wire broke in the cord
or inside the radio and then a capacitor or a transformer had an
internal short to the chassis or there was a resistor from hot to
chassis ground then the chassis would become hot. The so called
safety ground is not a 100% sure thing in the case of a failure.



Nothing is ever 100% perfectly safe. But you do try and improve the odds
as much as you can comfortably afford. Adding a safety wire system gives
you much more bang for the buck in terms of safety than the simple addition
of 33% more wire would appear to offer.

Because safety grounds are as

prone to fail as anything a third external wire tying all metal
cabinet radios together is the only safety measure if one has a table
full of these old AC powered beasts.

Yes it is not a good policy to tie the ground and neutral together. I
just felt that a good explanation of why not to do so was required
instead of just a blanket statement stating "The safety ground must
NEVER be connected to the neutral at the load !NEVER! "



The problem here is I could write for the next week describing all of the
failure modes I know about that can and do happen with power distribution
grounds, and grounding. But I really don't have that kind of time. It
is far easier for me to tell you that doing such a thing is unsafe, and
that you should NEVER connect the safety ground to the neutral at the load.

If I tell you that E = I * R are you going to make me prove it? Or can I
just tell you from a position of assumed authority that this is a true
relationship? You can go and find a book that will tell you E = I*R, and
likewise, you can find a book, or do a google search, to find out why you
should NEVER connect the safety ground to the neutral at the load.

-Chuck




Chuck I think you did a very good job and hope a few others good a
better understand of the problem. I just thought a little more info for
the group would no hurt. Being an Engineer I fully understand the
problem and Ohms law put most on this group I am sure are not and if a
new person who is us to solidstate circuit starts playing with
boatanchors it is totally different then being raised with them.

Again thanks and have a good day.
Ron
..



[email protected] December 1st 05 09:20 PM

getting bit by my FT-101EE chassis
 
Okay, I fail to understand.

Formerly, the 2-wire cord was connected to pins 2 and 4 of the Yaesu
connector. These I assume correspond to the +hot and -hot of the 120V
input winding to the step up transformer, leaving the ground floating.
I looked at my 3-wire cord and determined that my hot wires were the
black and white ones for the 3-wire cord, and that neutral (chassis
ground) was green. So I connected wall ground through ground line of
the cord to chassis ground pin of the plug, leaving the hot connections
unchanged.

Is there something I should be doing different?

Thanks,

The Eternal Squire


Chuck Harris December 1st 05 10:56 PM

getting bit by my FT-101EE chassis
 
wrote:
Okay, I fail to understand.

Formerly, the 2-wire cord was connected to pins 2 and 4 of the Yaesu
connector. These I assume correspond to the +hot and -hot of the 120V
input winding to the step up transformer, leaving the ground floating.
I looked at my 3-wire cord and determined that my hot wires were the
black and white ones for the 3-wire cord, and that neutral (chassis
ground) was green. So I connected wall ground through ground line of
the cord to chassis ground pin of the plug, leaving the hot connections
unchanged.

Is there something I should be doing different?

Thanks,

The Eternal Squire


Hi Squire,

The black wire is called Line, or we can call it hot+
The white wire is called neutral, or we can call it hot-
The green wire is the safety ground, and it goes to pretty
much any screw on a permanent part of the metal chassis.
(eg. don't use a cover screw, if you can avoid it.)

Technically, the green wire is supposed to have a crimped on
lug that is a closed circle, rather than a fork. This is
so that if the screw loosens, it won't fall off right away.

If the FT101 doesn't have markings for line and neutral, it is
usually a good idea to make sure that the line (black) goes to
the fuse. If Yuasu did things correctly, the other side of the
fuse should go to a switch, or relay contact.

[Note, if the fuse is one of the type with a screw in, or
bayonetted cap, the side of the fuse that goes closest to the
power line should be the hidden center pin. This prevents
you from getting zapped when you change the fuse. I have seen
a lot of manufacturers get this wrong.]

-Chuck

Uncle Peter December 2nd 05 01:09 AM

getting bit by my FT-101EE chassis
 

"Ron" wrote in message ...
OK that is one case where your need two failures to cause a hot chassis.


NEVER NEVER NEVER connect safety ground and neutral together on an
exposed metal chassis, PERIOD! NEVER.

What if some duffus uses a hardware store cheater on the radio, because he
house ONLY has the older two slot wall sockets? 50/50 shot that the chassis
and cabinet are hot with 120 VAC!!!

The white neutral and black hot should go to the load, the green safety
ground
goes to the metal cabinet. Also, tieing the neutral and hot together
defeats
GFIs.

Pete



Uncle Peter December 2nd 05 01:11 AM

getting bit by my FT-101EE chassis
 

wrote in message
...
I believe the important thing here is that a three wire plug be used and
that it gets wired correctly. I will never see why the neutral which is
grounded and green wire which is ground cannot be tied together.


That's why you're dangerous. Sorry. Lot's of people use hardware store
cheaters on safety cords so they can be plugged into older outlets.
You REALLY want an AC hot chassis, or to kill some unsuspecting
future user? Neutral and safety ground ARE NOT the same thing.

Pete



Uncle Peter December 2nd 05 01:16 AM

getting bit by my FT-101EE chassis
 

" Uncle Peter" wrote in message
news:o8Njf.2627$4v.2258@fed1read03...


One final comment, never assume that someone hasn't replaced older outlets
with modern safety ground devices where no safety ground was available in
the
older two conductor cables! A second fatal assumption would be that the
same outlet wasn't wired with the hot and neutral reversed. That's another
reason
why the neutral and ground aren't tied together at the load.

Pete



gb December 2nd 05 01:51 AM

getting bit by my FT-101EE chassis
 
wrote in message
oups.com...
This is indeed the case for the FT-101E whose schematic I just
examined. What I did was remove the 2-wire cord, and then connect a
3-wire cord where plus and minus hot were in former locations, then
soldered the neutral wire of the cord to the plug's ground pin. Hope
that would work.


Well keep wiring items like this and we may need to send flowers. Do you
really understand what you are doing here? Sounds like you need an elmer -
berfore you kill yourself.

gb




[email protected] December 2nd 05 04:21 AM

getting bit by my FT-101EE chassis
 
Hi Chuck,

I'm sorry I caused such a panic with my 'alien' terminology. In my
physics class 'neutral' was the name of the wire in a circuit whose
potential was midway between the peaks of an AC signal.

In any case I had wired it as you said now that I understand standard
terms and you understand alien terms :)

Thanks,

The Eternal Squire


Michael A. Terrell December 2nd 05 04:28 AM

getting bit by my FT-101EE chassis
 
Ron wrote:

OK that is one case where your need two failures to cause a hot chassis.
Now for Doofus to get electrocuted he will also have to have one
hand on this deaf radio and one hand on the radio that has a metal
chassis that is plugged into a socket with a good ground. The problem
you could also have a similar problem even if the neutral was wired
correctly (not tied to ground). If the ground wire broke in the cord or
inside the radio and then a capacitor or a transformer had an internal
short to the chassis or there was a resistor from hot to chassis ground
then the chassis would become hot. The so called safety ground is not a
100% sure thing in the case of a failure. Because safety grounds are as
prone to fail as anything a third external wire tying all metal cabinet
radios together is the only safety measure if one has a table full of
these old AC powered beasts.

Yes it is not a good policy to tie the ground and neutral together. I
just felt that a good explanation of why not to do so was required
instead of just a blanket statement stating "The safety ground must
NEVER be connected to the neutral at the load !NEVER! "

But he on the safe side and ground those boatanchors together. (you can
buy a bigger boat that way).

Thanks
Ron WA0KDS


Ok, Ron here is another possible failure mode: The neutral from the
pole pig goes high resistance or completely open. if both halves of the
240 VAC service are not balanced and the imbalance will cause a current
to flow from the neutral wire, to the radio and back to the ground rod.
If that current is very high the cord will smoke or burn. I had to
replace a breaker box a few years ago after the neutral corroded to the
point it exploded. I was outside at three in the morning repairing the
damn thing to cool my bedroom down so i could go to work the next day,
but nothing had the suggested wiring, or I could have lost my home.
Also, you could have trouble collecting from your insurance company
after a fire caused by your own work.

--
?

Michael A. Terrell
Central Florida

Michael A. Terrell December 2nd 05 04:43 AM

getting bit by my FT-101EE chassis
 
Chuck Harris wrote:

The black wire is called Line, or we can call it hot+
The white wire is called neutral, or we can call it hot-
The green wire is the safety ground, and it goes to pretty
much any screw on a permanent part of the metal chassis.
(eg. don't use a cover screw, if you can avoid it.)

Technically, the green wire is supposed to have a crimped on
lug that is a closed circle, rather than a fork. This is
so that if the screw loosens, it won't fall off right away.

If the FT101 doesn't have markings for line and neutral, it is
usually a good idea to make sure that the line (black) goes to
the fuse. If Yuasu did things correctly, the other side of the
fuse should go to a switch, or relay contact.

[Note, if the fuse is one of the type with a screw in, or
bayonetted cap, the side of the fuse that goes closest to the
power line should be the hidden center pin. This prevents
you from getting zapped when you change the fuse. I have seen
a lot of manufacturers get this wrong.]

-Chuck



Chuck, I worked as a production test tech at Microdyne on everything
except the Scientific Atlanta telemetry product we subcontracted. A new
employee in assembly mis-wired the round metal power connector and QA
missed it: The white and green wires went to the main power switch, and
the black was connected to the chassis. Another tech ignored the written
test procedure and plugged it in for initial testing to see that it
didn't come on. He leaned over to unplug it with one hand on the
aluminum case and his other hand brushed against the bare metal outlet
box where the radio was plugged in. He got a nasty shock and if it
hadn't caused his muscles to contract violently, he would probably be
dead. After that he never questioned the step that required the power
cord to be checked with an ohm meter BEFORE the radio was plugged in.


--
?

Michael A. Terrell
Central Florida

Chuck Harris December 2nd 05 01:53 PM

getting bit by my FT-101EE chassis
 
Michael A. Terrell wrote:


Yes it is not a good policy to tie the ground and neutral together. I
just felt that a good explanation of why not to do so was required
instead of just a blanket statement stating "The safety ground must
NEVER be connected to the neutral at the load !NEVER! "

But he on the safe side and ground those boatanchors together. (you can
buy a bigger boat that way).

Thanks
Ron WA0KDS



Ok, Ron here is another possible failure mode: The neutral from the
pole pig goes high resistance or completely open. if both halves of the
240 VAC service are not balanced and the imbalance will cause a current
to flow from the neutral wire, to the radio and back to the ground rod.
If that current is very high the cord will smoke or burn. I had to
replace a breaker box a few years ago after the neutral corroded to the
point it exploded. I was outside at three in the morning repairing the
damn thing to cool my bedroom down so i could go to work the next day,
but nothing had the suggested wiring, or I could have lost my home.
Also, you could have trouble collecting from your insurance company
after a fire caused by your own work.


Hi Michael,

Yep, that is yet another good example of why you shouldn't break the rules.

I could write all week, and still not cover all of the stupid dangerous things
that have happened with ground failures and grounding errors. The NEC
is the result of 100 years of experience with power distribution, and use.
Their collective authors have seen some of the most bizarre failures, and the
code has been designed to help prevent these types of failures.

It is rather unsettling to have a line cord catch fire in the bedroom
when your wife puts a piece of toast in the toaster oven in the kitchen.

And we haven't even broached the subject of what happens when your antenna
gets hit by lightning, and you have invited the ground currents into your
neutral circuits!

In case anyone thinks that losing the connection to the center tap (neutral)
at the pole pig is an unlikely problem. Bear in mind that virtually all
of these connections are to aluminum wire. The power companies make their
own rules. They don't have to follow NEC, they have their own code.
When they started using aluminum wire exclusively in the '60s,
they didn't think about the corrosion and cold flowing characteristics of
aluminum. The power companies use aluminum exclusively for all of the wiring
on their side because aluminum has the highest conductivity per pound, and per
dollar, of any known material.

After they gained experience with aluminum, and knew all about its problems,
I bet you think they went out, and upgraded all of the older connections,
right? Nope! They left them alone. Power companies are profit driven, they
didn't want to have to explain to their share holders why they would have to
shoulder a billion dollar loss to fix a problem of the power company's making.
So, they only fix the problem when *you* discover it.

-Chuck

Michael A. Terrell December 3rd 05 08:34 AM

getting bit by my FT-101EE chassis
 
Chuck Harris wrote:

Hi Michael,

Yep, that is yet another good example of why you shouldn't break the rules.

I could write all week, and still not cover all of the stupid dangerous things
that have happened with ground failures and grounding errors. The NEC
is the result of 100 years of experience with power distribution, and use.
Their collective authors have seen some of the most bizarre failures, and the
code has been designed to help prevent these types of failures.

It is rather unsettling to have a line cord catch fire in the bedroom
when your wife puts a piece of toast in the toaster oven in the kitchen.

And we haven't even broached the subject of what happens when your antenna
gets hit by lightning, and you have invited the ground currents into your
neutral circuits!

In case anyone thinks that losing the connection to the center tap (neutral)
at the pole pig is an unlikely problem. Bear in mind that virtually all
of these connections are to aluminum wire. The power companies make their
own rules. They don't have to follow NEC, they have their own code.
When they started using aluminum wire exclusively in the '60s,
they didn't think about the corrosion and cold flowing characteristics of
aluminum. The power companies use aluminum exclusively for all of the wiring
on their side because aluminum has the highest conductivity per pound, and per
dollar, of any known material.

After they gained experience with aluminum, and knew all about its problems,
I bet you think they went out, and upgraded all of the older connections,
right? Nope! They left them alone. Power companies are profit driven, they
didn't want to have to explain to their share holders why they would have to
shoulder a billion dollar loss to fix a problem of the power company's making.
So, they only fix the problem when *you* discover it.

-Chuck


After the hurricanes last year her in Florida they finally went through
the whole subdivision and replaced every splice in the secondaries, as
well as the 7200 volt primaries. I found a number of them on the ground
and it was amazing that I even had electricity. Between the corrosion
and the thermal expansion you could pull strands out of the crimps.
After they finished my line voltage went up 10 volts, and is a lot more
stable.
--
?

Michael A. Terrell
Central Florida


All times are GMT +1. The time now is 10:10 AM.

Powered by vBulletin® Copyright ©2000 - 2025, Jelsoft Enterprises Ltd.
RadioBanter.com