Yes, very possible !
Exide models as well at the other big boys Liebert etc.
use this configuration.

They use torrid transformers, very compact,
the entire assy about the size of a loaf of white bread !

The ups w batteries about 36" cubed. 12 KVA 3 phased.

dude



216 volt battery pack??? I don't think so.


No, quite possible and makes some design sense - they would not need
a heavy output transformer in the unit boosting the voltage of a 36V
or 48V battery string after converting it to a sine wave AC, as 216V
would be right around the sine wave peak voltage of 120VAC. Just run
the battery DC through two sets of power transistors to let through a
reconstituted sine wave - one for the positive half of the output
waveform, the other negative.

And it cuts the current the transistors have to pass.

-- Bruce --

--