Grounding for Gable end bracket & mast.
Tom Horne wrote:
Owen
The NEC only requires 5.261 (mm)2 for the protective down conductor
and 13.30 (mm)2 for the bonding conductor between electrodes. Since
those sizes are at best a bad joke
Perhaps you could explain why you think it's a bad joke? Do you think a
13 square mm conductor couldn't carry the strike current? (it can)
Or, perhaps, you're thinking that there are some other design criteria
that might push one towards a larger conductor (mechanical strength in
the face of icing and storms might be one).
|