RadioBanter

RadioBanter (https://www.radiobanter.com/)
-   Antenna (https://www.radiobanter.com/antenna/)
-   -   Standing Wave Phase (https://www.radiobanter.com/antenna/127904-standing-wave-phase.html)

Keith Dysart[_2_] December 10th 07 12:45 PM

Standing Wave Phase
 
On Dec 9, 10:59 pm, "AI4QJ" wrote:
I do not understand why people will not accept that, when one connects a
length of transmission line of Zo1 to another length of transmission line
with Zo2, there can/will be a phase change at the discontinuity.

If there is a phase change on the Zo1 line by itself when the discontinuity
is 0 + j0 impedance (short) or 0 +j0 conductance (open), shouldn't there be
a phase shift between 0 and pi/2 when the impedance (or as you say,
"impedor") is added somewhere in between, i.e. when connecting the line of
Zo2, such as -j567 ohms at the electrical degree point of the termination?


This argument does seem to have a certain attractiveness.

It is partially understood in terms of a lumped component of -j567 but that
model describes the mismatch at the discontinuity only. It must be corrected
at the system level to also accouint for the known 10 degree additional
transmission line contribution of the 100 ohm line.


It seems to me that if connecting a -j567 impedance
produces a certain response, it should not matter how
that -j567 impedance is produced. Consider the following
cases:

- produce the -j567 with a lumped capacitor
- produce the -j567 with 10 degrees of 100 ohm line
- produce the -j567 with 46.6 degrees of 600 ohm line

The claim appears to be that despite the 43.4 degrees
of 600 ohm line being terminated in the exact same
-j567 impedance in all cases, the phase shift
experienced at the interface is different in each
case.

Does this really make sense?

....Keith

Cecil Moore[_2_] December 10th 07 01:33 PM

Standing Wave Phase
 
Keith Dysart wrote:
It seems to me that if connecting a -j567 impedance
produces a certain response, it should not matter how
that -j567 impedance is produced. Consider the following
cases:

(1) - produce the -j567 with a lumped capacitor
(2) - produce the -j567 with 10 degrees of 100 ohm line
(3) - produce the -j567 with 46.6 degrees of 600 ohm line

The claim appears to be that despite the 43.4 degrees
of 600 ohm line being terminated in the exact same
-j567 impedance in all cases, the phase shift
experienced at the interface is different in each
case.


They are terminated in the same value of impedance
but they are not terminated in identical impedances.
Please see the IEEE Dictionary for the three different
definitions of impedance. Each case involves a different
reflection coefficient at the -j567 point.
(I added a number to each case above.)

(1) involves an *impedor* with a reflection coefficient
of 1.0 at -93.2 degrees when connected to the 600
ohm line. The reflected wave at the feedpoint lags
the forward wave by 43.4 + 93.2 + 43.4 = 180 degrees.
The impedance is a real impedor, not a virtual impedance.

(2) involves an impedance discontinuity with a
reflection coefficient of -0.7143. With 10 degrees
of 100 ohm line, the reflected wave lags the forward
wave by 2(43.4 + 36.6 + 10) = 180 degrees. The phase
shift at the discontinuity is 36.6 degrees each way.
The impedance is caused by superposition of component
waves at the impedance discontinuity.

(3) with 46.6 degrees of 600 ohm line, the reflected
wave lags the forward wave by 2(43.4 + 0 + 46.6) = 180
degrees. The phase shift at the 600 to 600 ohm junction
is zero. The reflection coefficient at the 600 to 600
ohm junction is 0, different from (1) and (2) above.
The impedance is completely virtual and thus cannot
cause anything.
--
73, Cecil http://www.w5dxp.com

Richard Clark December 11th 07 07:40 AM

Standing Wave Phase
 
On Mon, 10 Dec 2007 23:43:58 -0500, "AI4QJ" wrote:

A lumped component is not enough to make the model correct.
Comments welcome.


Hi Dan,

It works both ways. However, lines can appear to be equivalent to
lumped components until you, say, double the frequency. The two
models clearly diverge. Where you could place a series resonant
lumped circuit in place of a resonant line (or versa vice) at a
fundamental frequency, the lumped series circuit would rarely
demonstrate parallel resonance at twice that frequency, but the line
would.

But it appears the model hasn't been constrained to less than an
octave bandwidth - until after Keith submitted the winning ticket to
the lottery commission. Cecil's lotteries are like that. To date
(more than 12 years now) you are the only winner, and I haven't seen
your prize awarded yet.

73's
Richard Clark, KB7QHC

Cecil Moore[_2_] December 11th 07 12:19 PM

Standing Wave Phase
 
AI4QJ wrote:
Once you get to -j567 at the discontinuity (travelling
10 degrees along the 100 ohm line), now you interface with the 600 ohm line.
At that point you have to normalize the -j567 ohms to -j(567/600) = -j0.945
on the smith chart (you normalize to Zo for it to calculate properly). This
abrupt switch increases the angle from 10 degrees to arctan (0.945)) or 43
degrees. I think the effect to look for is that the abrupt impedance change
when Zo changes.


Exactly. Plot -j567/100 and -j567/600 on a Smith Chart and
read the phase shift directly from the wavelength scale
around the outside of the chart.
--
73, Cecil http://www.w5dxp.com

Cecil Moore[_2_] December 11th 07 01:47 PM

Standing Wave Phase
 
Cecil Moore wrote:
Exactly. Plot -j567/100 and -j567/600 on a Smith Chart and
read the phase shift directly from the wavelength scale
around the outside of the chart.


Well, not exactly directly. One must multiply the
delta-wavelength by 360 degrees to get the phase
shift. If the angle of reflection coefficient
degree scale is used, it must be divided by two
to get the actual phase shift.
--
73, Cecil http://www.w5dxp.com

Keith Dysart[_2_] December 12th 07 03:00 AM

Standing Wave Phase
 
On Dec 10, 11:43 pm, "AI4QJ" wrote:
I may have misspoken. Once you get to -j567 at the discontinuity (travelling
10 degrees along the 100 ohm line), now you interface with the 600 ohm line.
At that point you have to normalize the -j567 ohms to -j(567/600) = -j0.945
on the smith chart (you normalize to Zo for it to calculate properly). This
abrupt switch increases the angle from 10 degrees to arctan (0.945)) or 43
degrees. I think the effect to look for is that the abrupt impedance change
when Zo changes. A lumped component is not enough to make the model correct.
Comments welcome


I follow the arithmetic, and it still has a certain attractiveness
but how can it make such a difference how the -j567 is produced.

What if you were offerred 3 black boxes, each labelled -j567?
Would it make much difference what was in them?
How does one compute the phase shift at the terminals?

....Keith

Keith Dysart[_2_] December 12th 07 03:00 AM

Standing Wave Phase
 
On Dec 10, 8:33 am, Cecil Moore wrote:
Keith Dysart wrote:
It seems to me that if connecting a -j567 impedance
produces a certain response, it should not matter how
that -j567 impedance is produced. Consider the following
cases:


(1) - produce the -j567 with a lumped capacitor
(2) - produce the -j567 with 10 degrees of 100 ohm line
(3) - produce the -j567 with 46.6 degrees of 600 ohm line


The claim appears to be that despite the 43.4 degrees
of 600 ohm line being terminated in the exact same
-j567 impedance in all cases, the phase shift
experienced at the interface is different in each
case.


They are terminated in the same value of impedance
but they are not terminated in identical impedances.
Please see the IEEE Dictionary for the three different
definitions of impedance. Each case involves a different
reflection coefficient at the -j567 point.
(I added a number to each case above.)

(1) involves an *impedor* with a reflection coefficient
of 1.0 at -93.2 degrees when connected to the 600
ohm line. The reflected wave at the feedpoint lags
the forward wave by 43.4 + 93.2 + 43.4 = 180 degrees.
The impedance is a real impedor, not a virtual impedance.

(2) involves an impedance discontinuity with a
reflection coefficient of -0.7143. With 10 degrees
of 100 ohm line, the reflected wave lags the forward
wave by 2(43.4 + 36.6 + 10) = 180 degrees. The phase
shift at the discontinuity is 36.6 degrees each way.
The impedance is caused by superposition of component
waves at the impedance discontinuity.

(3) with 46.6 degrees of 600 ohm line, the reflected
wave lags the forward wave by 2(43.4 + 0 + 46.6) = 180
degrees. The phase shift at the 600 to 600 ohm junction
is zero. The reflection coefficient at the 600 to 600
ohm junction is 0, different from (1) and (2) above.
The impedance is completely virtual and thus cannot
cause anything.


I see how you have done the arithmetic, and if I
understand correctly, you would claim these are
all systems with 90 "electical degrees".

What about the following...

Open circuit 46.6 degrees of 600 ohm line attached
to 80 degrees of 100 ohm line. The drive point impedance
will be 0 ohms. And the impedance at the junction will
be the same -j567. Using your arithmetic, there is
90-46.6-80 - -36.6 degrees of phase shift at the
junction. The physical length is 126.6 degrees
while the system is 90 "electrical degrees".

Is the definition of a system with 90 "electrical degrees"
becoming any system where the drive point impedance
has no reactive component?

....Keith

Cecil Moore[_2_] December 12th 07 03:48 AM

Standing Wave Phase
 
Keith Dysart wrote:
Open circuit 46.6 degrees of 600 ohm line attached
to 80 degrees of 100 ohm line. The drive point impedance
will be 0 ohms. And the impedance at the junction will
be the same -j567. Using your arithmetic, there is
90-46.6-80 - -36.6 degrees of phase shift at the
junction. The physical length is 126.6 degrees
while the system is 90 "electrical degrees".


Yes, you have just discovered that a 100 to 600 ohm
impedance discontinuity *loses degrees* when the 600
ohm end is open. That's why a center-loaded mobile
antenna takes more coil than a base-loaded mobile
antenna. Think about it.

Hint: if the stub is open, the low Z0 needs to be
placed at the open end to make the stub physically
shorter.

If the stub is shorted, the high Z0 needs to be
placed at the shorted end to make the stub
physically shorter.

You seem to be surprised at that. One wonders why?
--
73, Cecil http://www.w5dxp.com

Roy Lewallen December 12th 07 07:21 AM

Standing Wave Phase
 
AI4QJ wrote:
"Keith Dysart" wrote in message
...
On Dec 10, 11:43 pm, "AI4QJ" wrote:
I may have misspoken. Once you get to -j567 at the discontinuity
(travelling
10 degrees along the 100 ohm line), now you interface with the 600 ohm
line.
At that point you have to normalize the -j567 ohms to -j(567/600)
= -j0.945
on the smith chart (you normalize to Zo for it to calculate properly).
This
abrupt switch increases the angle from 10 degrees to arctan (0.945)) or
43
degrees. I think the effect to look for is that the abrupt impedance
change
when Zo changes. A lumped component is not enough to make the model
correct.
Comments welcome

I follow the arithmetic, and it still has a certain attractiveness
but how can it make such a difference how the -j567 is produced.

What if you were offerred 3 black boxes, each labelled -j567?
Would it make much difference what was in them?
How does one compute the phase shift at the terminals?


I use the smith chart in my response.

If you have 3 black boxes each labeled "input impedance = -j567", they could
contain a number of different things but since I am using the smith chart,
they will contain 3 different lengths of open transmission lines.

Box 1 contains 10 degrees length at 4MHz of 100 ohm transmission line. Based
on VF=1, this line would be 3/4*E10E2*10/360 = 2.08m long.

On the smith chart, plot from circle 10 degrees (transmission coefficient)
and read -j5.67. Normalize to 1 = 100. The impedance at the input of the
line is -j567. Label this box "input impedance = -j567".

Box 2 contains 19.2 degrees length at 4MHz of 200 ohm transmission line.
Based on VF=1, this line would be 3/4*10E2*19.2/360 = 4.0m long

On the smith chart, plot from infinte impedance circle 19.2 degrees
(transmission coefficient) and read -j2.84. Normalize to 1 = 200. The
impedance at the input of the line is -j(200*2.84) = -j567. Label this box
"input impedance = -j567".

Box 3 contains 27.2 degrees at 4MHz of 300 ohm transmission line. Based on
VF=1, this line would be 3/4*10E2*27.2/360 = 5.67m long.

On the smith chart, plot from infinte impedance circle 27.2 degrees
(transmission coefficient) and read -j1.89. Normalize to 1 = 300. The
impedance at the input of the line is -j(300*1.89) = -j567. Label this box
"input impedance = -j567".

So, do all boxres labeled "input impedance =-j567 ohm" transmission lines
behave the same when connected to the 600 ohm transmission line?

No.

For each of these, impedance at the discontinuity will be -j567. However,
each has different electrical lengths, thus the 600 ohm line connecting to
it will have to be cut to different electrical lengths, for all of the
degrees to add to 90 total.

You can only say that all -j567 of a given Zo will affect phase shifts in
connected 600 ohms lines in the same way.

So far, I find this very interesting. Not all -j567 impedors are equal when
it comes to transmission lines.


Wait a second.

You have three black boxes, all of which present an impedance of -j567
ohms at some frequency.

And you say that you can tell the difference between these boxes by
connecting a 600 ohm line to each one? If so, please detail exactly what
you would measure, and where, which would be different for the three
boxes. I maintain that there is no test you can devise at steady state
at one frequency (where they're all -j567 ohms) which would enable you
to tell them apart. I'll add a fourth box containing only a capacitor
and include that in the challenge.

If you agree with me that you can't tell them apart but that connecting
a 600 ohm line gives different numbers of "electrical degrees", then I'd
like to hear your definition of "electrical degrees" because it would
have to be something that's different for the different boxes yet you
can't tell the difference by any measurement or observation.

Roy Lewallen, W7EL

John Smith December 12th 07 07:28 AM

Standing Wave Phase
 
Roy Lewallen wrote:

...
You have three black boxes, ...
...
Roy Lewallen, W7EL


Hey!

Those ain't illegal citizens band (or, Chicken Band--for you
wanna-be-amateurs) linears (or leen-e-airs--as those properly schooled
in Chicken Banding would say/pronounce) are they? ;-)

And, three? Crud, I'd think a single 5kw would get ya by! Just turn
off the "foot warmer" and use the exciter for QRP! wink

Regards,
JS

Cecil Moore[_2_] December 12th 07 11:54 AM

Standing Wave Phase
 
AI4QJ wrote:
So far, I find this very interesting. Not all -j567 impedors are

equal when
it comes to transmission lines.


An impedor has an impedance but all impedances are not
impedors. The IEEE Dictionary gives three different
definitions for "impedance".
--
73, Cecil http://www.w5dxp.com

Keith Dysart[_2_] December 12th 07 12:26 PM

Standing Wave Phase
 
On Dec 11, 11:24 pm, "AI4QJ" wrote:
"Keith Dysart" wrote in message

...





On Dec 10, 11:43 pm, "AI4QJ" wrote:
I may have misspoken. Once you get to -j567 at the discontinuity
(travelling
10 degrees along the 100 ohm line), now you interface with the 600 ohm
line.
At that point you have to normalize the -j567 ohms to -j(567/600)
= -j0.945
on the smith chart (you normalize to Zo for it to calculate properly).
This
abrupt switch increases the angle from 10 degrees to arctan (0.945)) or
43
degrees. I think the effect to look for is that the abrupt impedance
change
when Zo changes. A lumped component is not enough to make the model
correct.
Comments welcome


I follow the arithmetic, and it still has a certain attractiveness
but how can it make such a difference how the -j567 is produced.


What if you were offerred 3 black boxes, each labelled -j567?
Would it make much difference what was in them?
How does one compute the phase shift at the terminals?


I use the smith chart in my response.

If you have 3 black boxes each labeled "input impedance = -j567", they could
contain a number of different things but since I am using the smith chart,
they will contain 3 different lengths of open transmission lines.

Box 1 contains 10 degrees length at 4MHz of 100 ohm transmission line. Based
on VF=1, this line would be 3/4*E10E2*10/360 = 2.08m long.

On the smith chart, plot from circle 10 degrees (transmission coefficient)
and read -j5.67. Normalize to 1 = 100. The impedance at the input of the
line is -j567. Label this box "input impedance = -j567".

Box 2 contains 19.2 degrees length at 4MHz of 200 ohm transmission line.
Based on VF=1, this line would be 3/4*10E2*19.2/360 = 4.0m long

On the smith chart, plot from infinte impedance circle 19.2 degrees
(transmission coefficient) and read -j2.84. Normalize to 1 = 200. The
impedance at the input of the line is -j(200*2.84) = -j567. Label this box
"input impedance = -j567".

Box 3 contains 27.2 degrees at 4MHz of 300 ohm transmission line. Based on
VF=1, this line would be 3/4*10E2*27.2/360 = 5.67m long.

On the smith chart, plot from infinte impedance circle 27.2 degrees
(transmission coefficient) and read -j1.89. Normalize to 1 = 300. The
impedance at the input of the line is -j(300*1.89) = -j567. Label this box
"input impedance = -j567".

So, do all boxres labeled "input impedance =-j567 ohm" transmission lines
behave the same when connected to the 600 ohm transmission line?

No.

For each of these, impedance at the discontinuity will be -j567. However,
each has different electrical lengths, thus the 600 ohm line connecting to
it will have to be cut to different electrical lengths, for all of the
degrees to add to 90 total.

You can only say that all -j567 of a given Zo will affect phase shifts in
connected 600 ohms lines in the same way.

So far, I find this very interesting. Not all -j567 impedors are equal when
it comes to transmission lines.- Hide quoted text -


To find the length of the 600 ohm line, do I not just plot -j567/600
and work from there? It seems to me that it yields the same
answer regardless of the content of the black box.

....Keith

Cecil Moore[_2_] December 12th 07 01:21 PM

Standing Wave Phase
 
Keith Dysart wrote:
To find the length of the 600 ohm line, do I not just plot -j567/600
and work from there? It seems to me that it yields the same
answer regardless of the content of the black box.


Double the frequency and see what happens.
--
73, Cecil http://www.w5dxp.com

Keith Dysart[_2_] December 12th 07 02:43 PM

Standing Wave Phase
 
On Dec 12, 8:21 am, Cecil Moore wrote:
Keith Dysart wrote:
To find the length of the 600 ohm line, do I not just plot -j567/600
and work from there? It seems to me that it yields the same
answer regardless of the content of the black box.


Double the frequency and see what happens.


There are certainly many experiments one can conduct
to deduce an equivalent circuit for the interior of the black
box.

But for this sub-thread, which started with 90 "electical degrees",
a single frequency seems to me to be strongly implied.

....Keith

Keith Dysart[_2_] December 12th 07 03:49 PM

Standing Wave Phase
 
On Dec 11, 10:48 pm, Cecil Moore wrote:
Keith Dysart wrote:
Open circuit 46.6 degrees of 600 ohm line attached
to 80 degrees of 100 ohm line. The drive point impedance
will be 0 ohms. And the impedance at the junction will
be the same -j567. Using your arithmetic, there is
90-46.6-80 - -36.6 degrees of phase shift at the
junction. The physical length is 126.6 degrees
while the system is 90 "electrical degrees".


Yes


So this means I could take an antenna element
which is longer than 90 physical degrees, i.e.
greater than 1/4WL, and with the appropriate
matching network make a system that was
90 "electrical degrees".

I detect progress on the definition.

....Keith

Richard Clark December 12th 07 04:00 PM

Standing Wave Phase
 
On Wed, 12 Dec 2007 07:21:21 -0600, Cecil Moore
wrote:

Double the frequency and see what happens.


Hi Dan,

The Lottery Commission is asking to re-examine your Ticket. Not to
worry, winners WILL be notified at a later date. All that is asked is
that you be patient as some have been waiting longer than you.

73's
Richard Clark, KB7QHC

Cecil Moore[_2_] December 12th 07 04:19 PM

Standing Wave Phase
 
Keith Dysart wrote:
But for this sub-thread, which started with 90 "electical degrees",
a single frequency seems to me to be strongly implied.


Of course, but handicapping oneself to a steady-state
single sinusoidal frequency is like target shooting
while blindfolded and spinning on a Lazy Susan. Why
enforce a silly arbitrary handicap?
--
73, Cecil http://www.w5dxp.com

Cecil Moore[_2_] December 12th 07 04:43 PM

Standing Wave Phase
 
Keith Dysart wrote:
So this means I could take an antenna element
which is longer than 90 physical degrees, i.e.
greater than 1/4WL, and with the appropriate
matching network make a system that was
90 "electrical degrees".


Of course, if you reverse the position of the
600 ohm line and 100 ohm line in the previous
open-stub example, you will *lose* 8.3 degrees
of phase shift at the impedance discontinuity.
The transmission line will have to be physically
98.3 degrees long to get an electrical 90 degree
phase shift.

In like manner, if you have a straight (Hustler)
base rod and make the rest of the antenna a
helical coil with no stinger, you will wind up
with a resonant mobile antenna that is more than
90 degrees long physically.

If the Z0 of the base rod is 400 ohms, the
Z0 of the loading coil is 4000 ohms, and the
length of the base rod is 10 degrees, you will
lose 9 degrees at the base rod-to-coil impedance
discontinuity. The coil will need to be 89 degrees
long, i.e. almost self-resonant. The antenna will
be 99 degrees long physically.
--
73, Cecil http://www.w5dxp.com

Roy Lewallen December 12th 07 05:55 PM

Standing Wave Phase
 
Keith Dysart wrote:

To find the length of the 600 ohm line, do I not just plot -j567/600
and work from there? It seems to me that it yields the same
answer regardless of the content of the black box.

...Keith


It darn well better.

Roy Lewallen, W7EL

Cecil Moore[_2_] December 12th 07 06:34 PM

Standing Wave Phase
 
Keith Dysart wrote:
I detect progress on the definition.


Are you ready to find out why center-loading takes
more coil in a mobile antenna than does base loading?

Take the 10 degrees of 100 ohm line and move 5
degrees of it to the other end of the stub.

From this:

---43.4 deg 600 ohm line---+---10 deg 100 ohm line---open

To this:

--5 deg 100 ohm line--+--600 ohm line--+--5 deg 100 ohm line--open

Now how many physical degrees of 600 ohm line is needed
to make the stub electrically 1/4 wavelength?
--
73, Cecil http://www.w5dxp.com

[email protected] December 12th 07 08:33 PM

Standing Wave Phase
 
On Dec 12, 2:21 am, Roy Lewallen wrote:
AI4QJwrote:
"Keith Dysart" wrote in message
...
On Dec 10, 11:43 pm, "AI4QJ" wrote:
I may have misspoken. Once you get to -j567 at the discontinuity
(travelling
10 degrees along the 100 ohm line), now you interface with the 600 ohm
line.
At that point you have to normalize the -j567 ohms to -j(567/600)
= -j0.945
on the smith chart (you normalize to Zo for it to calculate properly).
This
abrupt switch increases the angle from 10 degrees to arctan (0.945)) or
43
degrees. I think the effect to look for is that the abrupt impedance
change
when Zo changes. A lumped component is not enough to make the model
correct.
Comments welcome
I follow the arithmetic, and it still has a certain attractiveness
but how can it make such a difference how the -j567 is produced.


What if you were offerred 3 black boxes, each labelled -j567?
Would it make much difference what was in them?
How does one compute the phase shift at the terminals?


I use the smith chart in my response.


If you have 3 black boxes each labeled "input impedance = -j567", they could
contain a number of different things but since I am using the smith chart,
they will contain 3 different lengths of open transmission lines.


Box 1 contains 10 degrees length at 4MHz of 100 ohm transmission line. Based
on VF=1, this line would be 3/4*E10E2*10/360 = 2.08m long.


On the smith chart, plot from circle 10 degrees (transmission coefficient)
and read -j5.67. Normalize to 1 = 100. The impedance at the input of the
line is -j567. Label this box "input impedance = -j567".


Box 2 contains 19.2 degrees length at 4MHz of 200 ohm transmission line.
Based on VF=1, this line would be 3/4*10E2*19.2/360 = 4.0m long


On the smith chart, plot from infinte impedance circle 19.2 degrees
(transmission coefficient) and read -j2.84. Normalize to 1 = 200. The
impedance at the input of the line is -j(200*2.84) = -j567. Label this box
"input impedance = -j567".


Box 3 contains 27.2 degrees at 4MHz of 300 ohm transmission line. Based on
VF=1, this line would be 3/4*10E2*27.2/360 = 5.67m long.


On the smith chart, plot from infinte impedance circle 27.2 degrees
(transmission coefficient) and read -j1.89. Normalize to 1 = 300. The
impedance at the input of the line is -j(300*1.89) = -j567. Label this box
"input impedance = -j567".


So, do all boxres labeled "input impedance =-j567 ohm" transmission lines
behave the same when connected to the 600 ohm transmission line?


No.


For each of these, impedance at the discontinuity will be -j567. However,
each has different electrical lengths, thus the 600 ohm line connecting to
it will have to be cut to different electrical lengths, for all of the
degrees to add to 90 total.


You can only say that all -j567 of a given Zo will affect phase shifts in
connected 600 ohms lines in the same way.


So far, I find this very interesting. Not all -j567 impedors are equal when
it comes to transmission lines.


Wait a second.

You have three black boxes, all of which present an impedance of -j567
ohms at some frequency.

And you say that you can tell the difference between these boxes by
connecting a 600 ohm line to each one? If so, please detail exactly what
you would measure, and where, which would be different for the three
boxes. I maintain that there is no test you can devise at steady state
at one frequency (where they're all -j567 ohms) which would enable you
to tell them apart. I'll add a fourth box containing only a capacitor
and include that in the challenge.

If you agree with me that you can't tell them apart but that connecting
a 600 ohm line gives different numbers of "electrical degrees", then I'd
like to hear your definition of "electrical degrees" because it would
have to be something that's different for the different boxes yet you
can't tell the difference by any measurement or observation.

Roy Lewallen, W7EL


In this case, electrical degrees = physical degrees. VF = 1.

[email protected] December 12th 07 08:56 PM

Standing Wave Phase
 
On Dec 12, 7:26 am, Keith Dysart wrote:
On Dec 11, 11:24 pm, "AI4QJ" wrote:



"Keith Dysart" wrote in message


...


On Dec 10, 11:43 pm, "AI4QJ" wrote:
I may have misspoken. Once you get to -j567 at the discontinuity
(travelling
10 degrees along the 100 ohm line), now you interface with the 600 ohm
line.
At that point you have to normalize the -j567 ohms to -j(567/600)
= -j0.945
on the smith chart (you normalize to Zo for it to calculate properly).
This
abrupt switch increases the angle from 10 degrees to arctan (0.945)) or
43
degrees. I think the effect to look for is that the abrupt impedance
change
when Zo changes. A lumped component is not enough to make the model
correct.
Comments welcome


I follow the arithmetic, and it still has a certain attractiveness
but how can it make such a difference how the -j567 is produced.


What if you were offerred 3 black boxes, each labelled -j567?
Would it make much difference what was in them?
How does one compute the phase shift at the terminals?


I use the smith chart in my response.


If you have 3 black boxes each labeled "input impedance = -j567", they could
contain a number of different things but since I am using the smith chart,
they will contain 3 different lengths of open transmission lines.


Box 1 contains 10 degrees length at 4MHz of 100 ohm transmission line. Based
on VF=1, this line would be 3/4*E10E2*10/360 = 2.08m long.


On the smith chart, plot from circle 10 degrees (transmission coefficient)
and read -j5.67. Normalize to 1 = 100. The impedance at the input of the
line is -j567. Label this box "input impedance = -j567".


Box 2 contains 19.2 degrees length at 4MHz of 200 ohm transmission line.
Based on VF=1, this line would be 3/4*10E2*19.2/360 = 4.0m long


On the smith chart, plot from infinte impedance circle 19.2 degrees
(transmission coefficient) and read -j2.84. Normalize to 1 = 200. The
impedance at the input of the line is -j(200*2.84) = -j567. Label this box
"input impedance = -j567".


Box 3 contains 27.2 degrees at 4MHz of 300 ohm transmission line. Based on
VF=1, this line would be 3/4*10E2*27.2/360 = 5.67m long.


On the smith chart, plot from infinte impedance circle 27.2 degrees
(transmission coefficient) and read -j1.89. Normalize to 1 = 300. The
impedance at the input of the line is -j(300*1.89) = -j567. Label this box
"input impedance = -j567".


So, do all boxres labeled "input impedance =-j567 ohm" transmission lines
behave the same when connected to the 600 ohm transmission line?


No.


For each of these, impedance at the discontinuity will be -j567. However,
each has different electrical lengths, thus the 600 ohm line connecting to
it will have to be cut to different electrical lengths, for all of the
degrees to add to 90 total.


You can only say that all -j567 of a given Zo will affect phase shifts in
connected 600 ohms lines in the same way.


So far, I find this very interesting. Not all -j567 impedors are equal when
it comes to transmission lines.- Hide quoted text -


To find the length of the 600 ohm line, do I not just plot -j567/600
and work from there? It seems to me that it yields the same
answer regardless of the content of the black box.

...Keith


I see your point. To end up with -j567 on a 200 ohm line, you must use
19.2 degrees of length. 19.2 degrees of 200 ohm line brings you to -
j2.84 on the smith chart. To get -j567 on a 100 ohm line, you only
need to go 10 degrees, corresponding to -j5.67 on the smith chart.
Although we know that the 200 ohm line is longer, there is no
indication that the length of the 600 ohm line must or must not
change. I cannot know that unless I know the change in phase angle at
the new -j567 discontinuity with the 200 ohm line. I do not have
enough information on that unless I measure it, as was assumed to be
the case using the 100 ohm line. I was assuming that the phase change
at the discontinuity would not change but it is not immediately
obvious that it will or will not. Then, if it did not change and
stayed at 37 degrees, you would have had a new length of 600 ohm line
of 90-37-19.2= 33 degrees which at VF =1, l = 33/360*75 = 6.875m. I
do not have the information available to make that assumption. I would
have to resort to measurement, same as was done with the 600-100 ohm
combination.


[email protected] December 12th 07 09:09 PM

Standing Wave Phase
 
On Dec 12, 2:21 am, Roy Lewallen wrote:
AI4QJwrote:
"Keith Dysart" wrote in message
...
On Dec 10, 11:43 pm, "AI4QJ" wrote:
I may have misspoken. Once you get to -j567 at the discontinuity
(travelling
10 degrees along the 100 ohm line), now you interface with the 600 ohm
line.
At that point you have to normalize the -j567 ohms to -j(567/600)
= -j0.945
on the smith chart (you normalize to Zo for it to calculate properly).
This
abrupt switch increases the angle from 10 degrees to arctan (0.945)) or
43
degrees. I think the effect to look for is that the abrupt impedance
change
when Zo changes. A lumped component is not enough to make the model
correct.
Comments welcome
I follow the arithmetic, and it still has a certain attractiveness
but how can it make such a difference how the -j567 is produced.


What if you were offerred 3 black boxes, each labelled -j567?
Would it make much difference what was in them?
How does one compute the phase shift at the terminals?


I use the smith chart in my response.


If you have 3 black boxes each labeled "input impedance = -j567", they could
contain a number of different things but since I am using the smith chart,
they will contain 3 different lengths of open transmission lines.


Box 1 contains 10 degrees length at 4MHz of 100 ohm transmission line. Based
on VF=1, this line would be 3/4*E10E2*10/360 = 2.08m long.


On the smith chart, plot from circle 10 degrees (transmission coefficient)
and read -j5.67. Normalize to 1 = 100. The impedance at the input of the
line is -j567. Label this box "input impedance = -j567".


Box 2 contains 19.2 degrees length at 4MHz of 200 ohm transmission line.
Based on VF=1, this line would be 3/4*10E2*19.2/360 = 4.0m long


On the smith chart, plot from infinte impedance circle 19.2 degrees
(transmission coefficient) and read -j2.84. Normalize to 1 = 200. The
impedance at the input of the line is -j(200*2.84) = -j567. Label this box
"input impedance = -j567".


Box 3 contains 27.2 degrees at 4MHz of 300 ohm transmission line. Based on
VF=1, this line would be 3/4*10E2*27.2/360 = 5.67m long.


On the smith chart, plot from infinte impedance circle 27.2 degrees
(transmission coefficient) and read -j1.89. Normalize to 1 = 300. The
impedance at the input of the line is -j(300*1.89) = -j567. Label this box
"input impedance = -j567".


So, do all boxres labeled "input impedance =-j567 ohm" transmission lines
behave the same when connected to the 600 ohm transmission line?


No.


For each of these, impedance at the discontinuity will be -j567. However,
each has different electrical lengths, thus the 600 ohm line connecting to
it will have to be cut to different electrical lengths, for all of the
degrees to add to 90 total.


You can only say that all -j567 of a given Zo will affect phase shifts in
connected 600 ohms lines in the same way.


So far, I find this very interesting. Not all -j567 impedors are equal when
it comes to transmission lines.


Wait a second.

You have three black boxes, all of which present an impedance of -j567
ohms at some frequency.

And you say that you can tell the difference between these boxes by
connecting a 600 ohm line to each one? If so, please detail exactly what
you would measure, and where, which would be different for the three
boxes. I maintain that there is no test you can devise at steady state
at one frequency (where they're all -j567 ohms) which would enable you
to tell them apart. I'll add a fourth box containing only a capacitor
and include that in the challenge.

If you agree with me that you can't tell them apart but that connecting
a 600 ohm line gives different numbers of "electrical degrees", then I'd
like to hear your definition of "electrical degrees" because it would
have to be something that's different for the different boxes yet you
can't tell the difference by any measurement or observation.

Roy Lewallen, W7EL


I see your point. I assumed that the phase change specific to the
discontinuity was the same for all -j567 impedances. I do not have the
information to say it is true (or I lack the tools to prove it).

To end up with -j567 on a 200 ohm line, you must use 19.2 degrees of
length. 19.2 degrees of 200 ohm line brings you to -j2.84 on the smith
chart. Then, 200* -j2.84 = -j567. To get -j567 on a 100 ohm line, you
only need to go 10 degrees, corresponding to -j5.67 on the smith
chart. The 100* -j5.67 = -j567. Although we know that the 200 ohm line
is longer by 9.2 degrees, there is no indication that the length of
the 600 ohm line must or must not change. I cannot know that unless I
know the change in phase angle at the new -j567 discontinuity with the
200 ohm line. I do not have enough information on that without
additional measurements. I would need to measure it to to system
resonance (1/4WL = 90 degrees), as was the case using the 100 ohm
line. I was assuming that the phase change at the discontinuity would
not change but it is not immediately obvious that it will or will not.
But, assuming (rightly or wrongly) that the phase angle at the
discontinuity did not change and stayed at 37 degrees, you would have
had a new length of 600 ohm line of 90-37-19.2= 33 degrees which at
VF =1, l = 33/360*75 = 6.875m. I cannot make that assumption right
now. I would have to resort to measurement, same as was done with the
600-100 ohm combination.

In any case, this does not disprove the basic premise of the existence
of a phase change due to the impedance discontinuity. It does prove
that my minor point of elaboration may have had a false
assumption.Sorry for any confusion.


Cecil Moore[_2_] December 12th 07 09:12 PM

Standing Wave Phase
 
wrote:
Although we know that the 200 ohm line is longer, there is no
indication that the length of the 600 ohm line must or must not
change.


The phase shift at the impedance discontinuity depends
upon the *ratio of Z0High/Z0Low*. The following two
examples have the same phase shift at the impedance
discontinuity.

Z0High Z0Low

---43.4 deg 600 ohm line---+---10 deg 100 ohm line---open

---43.4 deg 300 ohm line---+---10 deg 50 ohm line---open

So how long does the 600 ohm line have to be in the following
example for the stub to exhibit 1/4WL of electrical length?

---??? deg 600 ohm line---+---10 deg 50 ohm line---open
--
73, Cecil
http://www.w5dxp.com

[email protected] December 12th 07 09:19 PM

Standing Wave Phase
 
On Dec 12, 11:00 am, Richard Clark wrote:
On Wed, 12 Dec 2007 07:21:21 -0600, Cecil Moore
wrote:

Double the frequency and see what happens.


Hi Dan,

The Lottery Commission is asking to re-examine your Ticket. Not to
worry, winners WILL be notified at a later date. All that is asked is
that you be patient as some have been waiting longer than you.

73's
Richard Clark, KB7QHC


Those white floating things are way, way off in the distance and
nowhere near to approaching us. The chairs for the band remain in
place, folded up. The angle of the deck is 0 degrees horizontal.

Roy Lewallen December 12th 07 09:55 PM

Standing Wave Phase
 
wrote:

I see your point. I assumed that the phase change specific to the
discontinuity was the same for all -j567 impedances. I do not have the
information to say it is true (or I lack the tools to prove it).

To end up with -j567 on a 200 ohm line, you must use 19.2 degrees of
length. 19.2 degrees of 200 ohm line brings you to -j2.84 on the smith
chart. Then, 200* -j2.84 = -j567. To get -j567 on a 100 ohm line, you
only need to go 10 degrees, corresponding to -j5.67 on the smith
chart. The 100* -j5.67 = -j567. Although we know that the 200 ohm line
is longer by 9.2 degrees, there is no indication that the length of
the 600 ohm line must or must not change. I cannot know that unless I
know the change in phase angle at the new -j567 discontinuity with the
200 ohm line. I do not have enough information on that without
additional measurements. I would need to measure it to to system
resonance (1/4WL = 90 degrees), as was the case using the 100 ohm
line. I was assuming that the phase change at the discontinuity would
not change but it is not immediately obvious that it will or will not.
But, assuming (rightly or wrongly) that the phase angle at the
discontinuity did not change and stayed at 37 degrees, you would have
had a new length of 600 ohm line of 90-37-19.2= 33 degrees which at
VF =1, l = 33/360*75 = 6.875m. I cannot make that assumption right
now. I would have to resort to measurement, same as was done with the
600-100 ohm combination.

In any case, this does not disprove the basic premise of the existence
of a phase change due to the impedance discontinuity. It does prove
that my minor point of elaboration may have had a false
assumption.Sorry for any confusion.


Sorry, I'm having trouble following that. But:

-- IF there's a phase change at the impedance discontinuity (which I
assume means the black box terminals), it's the same for all four (your
three and my one) black boxes. Whatever conclusions you might have drawn
about the relationship between the phase change and the contents of the
boxes, other than the impedance at the terminals, are wrong, and you
should investigate where you went astray in the process of reaching
those conclusions.
-- If you think you can distinguish the boxes by measurement (at the one
single frequency at which all their impedances are the same, in steady
state), show exactly how you'd do it and what the results would be. I
claim that you can't.
-- If the four boxes have different numbers of "electrical degrees" at
the same frequency, then "electrical degrees", as the term is used here,
is something you can't measure. That seems to be the case. And if you
can't measure "electrical degrees", how do you determine how many of
them are "missing"?

Of course, "electrical degrees" does have meaning. But like a number of
other terms, some newsgroup participants have made up alternate meanings
and given them properties which are nonsensical.

Roy Lewallen, W7EL

Cecil Moore[_2_] December 12th 07 10:52 PM

Standing Wave Phase
 
Roy Lewallen wrote:
-- IF there's a phase change at the impedance discontinuity (which I
assume means the black box terminals), it's the same for all four (your
three and my one) black boxes.


To see exactly how wrong that statement really is let's
take a look at two of the cases.

(1) with a -j567 ohm impedor (capacitor) connected inside
the black box to the existing 43.4 degrees of 600 ohm
line external to the black box.

(2) with 46.6 degrees of 600 ohm line connected to the
existing 43.4 degrees of 600 ohm line external to the
black box.

The reflection coefficient for (1) at the black box
terminals is 1.0 at -93 degrees, i.e. 100% reflection
at that point with an accompanying phase angle shift.

The reflection coefficient for (2) at the black box
terminals is 0 at 0 degrees, i.e. no reflections at
that point and no accompanying phase angle shift at
that point.

To assert that the phase change at the black box
terminals is the same in both of those cases is
ridiculous. In case (1) it is 93 degrees. In case (2)
it is zero degrees.
--
73, Cecil http://www.w5dxp.com

Keith Dysart[_2_] December 13th 07 12:23 AM

Standing Wave Phase
 
On Dec 12, 5:52 pm, Cecil Moore wrote:
Roy Lewallen wrote:
-- IF there's a phase change at the impedance discontinuity (which I
assume means the black box terminals), it's the same for all four (your
three and my one) black boxes.


To see exactly how wrong that statement really is let's
take a look at two of the cases.

(1) with a -j567 ohm impedor (capacitor) connected inside
the black box to the existing 43.4 degrees of 600 ohm
line external to the black box.

(2) with 46.6 degrees of 600 ohm line connected to the
existing 43.4 degrees of 600 ohm line external to the
black box.

The reflection coefficient for (1) at the black box
terminals is 1.0 at -93 degrees, i.e. 100% reflection
at that point with an accompanying phase angle shift.

The reflection coefficient for (2) at the black box
terminals is 0 at 0 degrees, i.e. no reflections at
that point and no accompanying phase angle shift at
that point.

To assert that the phase change at the black box
terminals is the same in both of those cases is
ridiculous. In case (1) it is 93 degrees. In case (2)
it is zero degrees.


So, when you are presented with 43.6 degrees of
600 ohm line connected to a black box (about
which you know nothing of the internals) which
provides an impedance -j567, do you answer the
question: What is the impedance at the input
of the 600 ohm line? Or do you refuse, because
you do not know what phase change is
occuring at the terminals?

....Keith

Cecil Moore[_2_] December 13th 07 02:39 AM

Standing Wave Phase
 
Keith Dysart wrote:
So, when you are presented with 43.6 degrees of
600 ohm line connected to a black box (about
which you know nothing of the internals) which
provides an impedance -j567, do you answer the
question: What is the impedance at the input
of the 600 ohm line? Or do you refuse, because
you do not know what phase change is
occuring at the terminals?


I'm not sure I understand the question. Measuring
the s22 parameter should be all we need to know.
--
73, Cecil http://www.w5dxp.com

Cecil Moore[_2_] December 13th 07 03:01 AM

Standing Wave Phase
 
AI4QJ wrote:
"Cecil Moore" wrote in message
. net...
wrote:
Although we know that the 200 ohm line is longer, there is no
indication that the length of the 600 ohm line must or must not
change.

The phase shift at the impedance discontinuity depends
upon the *ratio of Z0High/Z0Low*. The following two
examples have the same phase shift at the impedance
discontinuity.

Z0High Z0Low

---43.4 deg 600 ohm line---+---10 deg 100 ohm line---open

---43.4 deg 300 ohm line---+---10 deg 50 ohm line---open

So how long does the 600 ohm line have to be in the following
example for the stub to exhibit 1/4WL of electrical length?

---??? deg 600 ohm line---+---10 deg 50 ohm line---open


Based on what you say above, Zo high/Zo low = 6 resul;ts in 37 degrees.
Then for phase shift, (Zo high/Zo low)*37 deg = 6*D where D = phase shift.

If the above ratio is literally true, then in the above example, 12*37deg/6
= 74 degrees and length of the 600 ohm line = 90-74-10 = 6 degrees.

However, I would like to find a reference for the math showing the
characteristic impedance ratio relationship with phase shift. I am reluctant
to accepting formulas without seeing them derived at least once. :-)


Looks like you got the Z0 ratio upside down?

Actually I get 25.3 degrees for the 600 ohm line.

Arctan(Z0Low/Z0High)cot(10)) = 25.3 degrees
--
73, Cecil
http://www.w5dxp.com

Richard Clark December 13th 07 03:13 AM

Standing Wave Phase
 
On Wed, 12 Dec 2007 13:19:27 -0800 (PST), wrote:

On Dec 12, 11:00 am, Richard Clark wrote:
On Wed, 12 Dec 2007 07:21:21 -0600, Cecil Moore
wrote:

Double the frequency and see what happens.


Hi Dan,

The Lottery Commission is asking to re-examine your Ticket. Not to
worry, winners WILL be notified at a later date. All that is asked is
that you be patient as some have been waiting longer than you.

73's
Richard Clark, KB7QHC


Those white floating things are way, way off in the distance and
nowhere near to approaching us. The chairs for the band remain in
place, folded up. The angle of the deck is 0 degrees horizontal.


Keel's finally settled into the mud, I see.

73's
Richard Clark, KB7QHC

Keith Dysart[_2_] December 13th 07 09:51 AM

Standing Wave Phase
 
On Dec 12, 8:44 pm, "AI4QJ" wrote:
"Cecil Moore" wrote in message

. net...





wrote:
Although we know that the 200 ohm line is longer, there is no
indication that the length of the 600 ohm line must or must not
change.


The phase shift at the impedance discontinuity depends
upon the *ratio of Z0High/Z0Low*. The following two
examples have the same phase shift at the impedance
discontinuity.


Z0High Z0Low


---43.4 deg 600 ohm line---+---10 deg 100 ohm line---open


---43.4 deg 300 ohm line---+---10 deg 50 ohm line---open


So how long does the 600 ohm line have to be in the following
example for the stub to exhibit 1/4WL of electrical length?


---??? deg 600 ohm line---+---10 deg 50 ohm line---open


Based on what you say above, Zo high/Zo low = 6 resul;ts in 37 degrees.
Then for phase shift, (Zo high/Zo low)*37 deg = 6*D where D = phase shift.

If the above ratio is literally true, then in the above example, 12*37deg/6
= 74 degrees and length of the 600 ohm line = 90-74-10 = 6 degrees.

However, I would like to find a reference for the math showing the
characteristic impedance ratio relationship with phase shift. I am reluctant
to accepting formulas without seeing them derived at least once.


In another thread, "Calculating a (fictitious) phase shift;
was : Loading Colis", David Ryeburn has provided the
arithmetic for the general case which includes the
following expression:
-j*(Z_2)*cot(alpha + beta) = -j*(Z_1)*cot(alpha)

"alpha" is the length of the open line
"beta" is the "phase shift" at the joint
"Z_2" is the impedance of the open line
"Z_1" is the impedance of the driven line

It can be seen, as noted by Cecil, that beta
will be the same if the impedances of the two
lines are scaled proportionally.

But beta is dependant not only on the two
impedances, but also on the length of the
open line.

There are no simple relationships here.

It does not seem to be a concept that is
particularly useful for the solving of problems.

....Keith

Cecil Moore[_2_] December 13th 07 10:57 AM

Standing Wave Phase
 
It does not seem to be a concept that is
particularly useful for the solving of problems.


Looks like you haven't thought it through. If one
wants to create a shortened dual-Z0 stub with
equal lengths of each section of Z0High and Z0Low,
here is the corresponding chart for different
ratios of Z0High/Z0Low.

http://www.w5dxp.com/DualZ0.gif

As an example, one can create an electrical 1/4WL
stub that is 1/3 the normal physical length by
using 600 ohm line and 50 ohm line.
--
73, Cecil http://www.w5dxp.com

Keith Dysart[_2_] December 13th 07 01:30 PM

Standing Wave Phase
 
On Dec 13, 5:57 am, Cecil Moore wrote:
It does not seem to be a concept that is
particularly useful for the solving of problems.


Looks like you haven't thought it through. If one
wants to create a shortened dual-Z0 stub with
equal lengths of each section of Z0High and Z0Low,
here is the corresponding chart for different
ratios of Z0High/Z0Low.

http://www.w5dxp.com/DualZ0.gif

As an example, one can create an electrical 1/4WL
stub that is 1/3 the normal physical length by
using 600 ohm line and 50 ohm line.


There are many ways to create the impedances
for matching, each with different advantages. As
you point out, one of the benefits of using two
different impedance lines is a reduction in material,
though, you could go all the way to just using
a lumped capacitor and save even more.

This reality, however, does not demonstrate any
value for the *concept* of phase shift at a
discontinuity. For the concept to be useful it
should facilitate understanding or problem
solving. As far as I can tell, you always solve
the problem in the conventional way (change
the angle on the Smith chart, un-normalize
the impedance, re-normalize the impedance
to the new Z0, measure the angle to get to
the desired impedance) and then work out
the "phase shift" at the discontinuity. It sure
looks like additional work that adds no value
since the important and useful information
has already been derived before computing the
"phase shift".

As such, I declare it "not particularly useful".

....Keith

Gene Fuller December 13th 07 04:31 PM

Standing Wave Phase
 
Cecil Moore wrote:
It does not seem to be a concept that is
particularly useful for the solving of problems.


Looks like you haven't thought it through. If one
wants to create a shortened dual-Z0 stub with
equal lengths of each section of Z0High and Z0Low,
here is the corresponding chart for different
ratios of Z0High/Z0Low.

http://www.w5dxp.com/DualZ0.gif

As an example, one can create an electrical 1/4WL
stub that is 1/3 the normal physical length by
using 600 ohm line and 50 ohm line.


Cecil,

So how do you make that 12:1 connection, say 50 ohm coax to 600 ohm open
line? Do you s'pose the connection bits add any phase shift all by
themselves? Do you have a model for that extra phase shift?

8-)

73,
Gene
W4SZ

Cecil Moore[_2_] December 13th 07 05:00 PM

Standing Wave Phase in Loaded Mobile Antennas
 
Keith Dysart wrote:
This reality, however, does not demonstrate any
value for the *concept* of phase shift at a
discontinuity.


It may indeed have little value for stubs. But
for loaded mobile antennas the value is obvious.

The value is that it explains the phase shift
through a loading coil in a loaded mobile
antenna and the phase shift at the coil to
stinger junction. Using dual-Z0 transmission
line stubs we are ready to understand loaded
mobile antennas, the phase shift through the
loading coil, and the "missing degrees" at the
coil to stinger junction.

According to Dr. Corum, my 75m Texas Bugcatcher
coil has a Z0 of ~4000 and a VF of ~0.02.

The stinger has a Z0 in the ballpark of 400 ohms
and a VF close to 1.0

Knowing what we know about a dual-Z0 1/4WL stub,
we can now use that knowledge to analyze a base-
loaded mobile antenna with coil and stinger.

---Z0=4000 ohm coil---+---10 deg 400 ohm stinger

Now it's a piece of cake. How many degrees of
loading coil do we need to make the configuration
90 electrical degrees long?

Arctan((400/4000)*cot(10)) = ~30 degrees

What is the impedance at the coil to stinger
junction?

400*cot(10) = ~ -j2300 ohms

What is the phase shift at the coil to stinger
junction?

90 - 30 - 10 = ~50 degrees

I stumbled upon the dual-Z0 stub idea in trying to
understand the phase shifts and delays in a loaded
mobile antenna. The same general principles apply.
Using traveling-wave current to measure the delay
through my Texas Bugcatcher coil agreed within 15%
with these calculated values.

One side said the coil had to make up the missing 80
degrees of antenna that necessarily had to be there
with a 10 degree stinger. This side did not understand
the phase shift at the coil to stinger junction.

The other side said the coil, like a lumped inductor,
has ~zero phase shift through it. This side did not
understand the limitations of the lumped circuit
model.

The delay through a coil is what it measures and
calculates to be within a certain accuracy. It is not
80 degrees and it is not ~zero degrees.
--
73, Cecil http://www.w5dxp.com

John Smith December 13th 07 05:46 PM

Standing Wave Phase in Loaded Mobile Antennas
 
Cecil Moore wrote:

...

400*cot(10) = ~ -j2300 ohms
...


I am in the middle of a brain fog/block.

I am attempting to get an equation to obtain the cotangent of x (or 10
in the above.) I HAVE DONE THIS BEFORE-got something wrong here ...

(1/tan(10)) = 5.67128

and (400*(1/tan(10)) = 2268.51273

There is no "built in" cotan function on my ti-86, ti-83, etc.

Help me out Cecil, anyone?

Regards,
JS

Cecil Moore[_2_] December 13th 07 07:16 PM

Standing Wave Phase in Loaded Mobile Antennas
 
John Smith wrote:
There is no "built in" cotan function on my ti-86, ti-83, etc.


Poor guy - why can't you do cotangent functions in
your head? :-)

Help me out Cecil, anyone?


How about:

cot(x) = tan(90-x)

cot(10) = tan(80) = 5.67
--
73, Cecil http://www.w5dxp.com

David Ryeburn December 13th 07 09:52 PM

Standing Wave Phase
 
In article
,
Keith Dysart wrote:

In another thread, "Calculating a (fictitious) phase shift;
was : Loading Colis", David Ryeburn has provided the
arithmetic for the general case which includes the
following expression:
-j*(Z_2)*cot(alpha + beta) = -j*(Z_1)*cot(alpha)

"alpha" is the length of the open line
"beta" is the "phase shift" at the joint


Yes.

"Z_2" is the impedance of the open line
"Z_1" is the impedance of the driven line


Backwards. Z_1 is the characteristic impedance of the open-circuited line
(100 ohms, in some of the examples previously discussed). Z_2 is the
characteristic impedance of line from the junction point back to the source
(600 ohms, in those examples).

But beta is dependant not only on the two
impedances, but also on the length of the
open line.

There are no simple relationships here.

It does not seem to be a concept that is
particularly useful for the solving of problems.


I couldn't agree more. The angle alpha + beta is useful; the angle beta is
not. But I thought I would provide the formulas in an attempt to set things
straight.

In article
.
Keith Dysart wrote:

There are many ways to create the impedances
for matching, each with different advantages. As
you point out, one of the benefits of using two
different impedance lines is a reduction in material,
though, you could go all the way to just using
a lumped capacitor and save even more.


Agreed. I've always liked capacitors better than transmission line segments.
It takes a pretty crummy capacitor to have as low a Q as a transmission line
section is likely to have. Even inductors are often better than transmission
line segments. But W5DXP was trying to explain how a loaded mobile antenna
worked (using transmission line concepts).

However, loaded mobile antennas presumably radiate, at least a little, and
my analysis (and W5DXP's discussion of angle lengths of transmission lines
and "phase shift" at their junction) is for *LOSSLESS* transmission lines.
This makes me wonder.

David, ex-W8EZE

--
David Ryeburn

To send e-mail, use "ca" instead of "caz".

John Smith December 13th 07 09:58 PM

Standing Wave Phase in Loaded Mobile Antennas
 
Cecil Moore wrote:

...
Poor guy - why can't you do cotangent functions in
your head? :-)
...


Cecil:

The extremly difficult will take me a couple of minutes ...

The impossible takes just a bit more time. :-)

I AM NOT A GURU! yanno? LOL

Regards,
JS


All times are GMT +1. The time now is 02:17 PM.

Powered by vBulletin® Copyright ©2000 - 2025, Jelsoft Enterprises Ltd.
RadioBanter.com