![]() |
|
Derivation of Reflection Coefficient vs SWR
On Jan 27, 10:57 am, Roger Sparks wrote:
On Sat, 26 Jan 2008 19:24:22 -0800 (PST) Keith Dysart wrote: On Jan 26, 12:15 pm, Roger Sparks wrote: On Fri, 25 Jan 2008 19:13:31 -0800 (PST) Keith Dysart wrote: On Jan 24, 10:33 pm, Roger Sparks wrote: [snip] By examining this derivation, the reader can see that power and energy is reflected when a wave encounters a discontinuity. The reader can also see that more power is present on the transmission line than is delivered to the load. This is the conventional phraseology for describing the behaviour at the impedance discontinuity. Allow me to offer a specific example for which this phraseology is inappropriate. Consider a 50 V step function generator with an output impedance of 50 ohms driving a 50 ohm line that is 1 second long terminated in an open circuit. Turn on the generator. A 50 V step propagates down the line. The generator is putting 50 J/s into the line. One second later it reaches the open end and begins propagating backwards. After two seconds it reaches the generator. The voltage at the generator is now 100 V and no current is flowing from the generator into the line. In the 2 seconds, the generator put 100 joules into the line which is now stored in the line. The line is at a constant 100 V and the current is zero everywhere. Computing Pf and Pr will yield 50 W forward and 50 W reflected. And yet no current is flowing anywhere. The voltage on the line is completely static. And yet some will claim that 50 W is flowing forward and 50 W is flowing backwards. Does this seem like a reasonable claim for an open circuited transmission line with constant voltage along its length and no current anywhere? I do not find it so. ...Keith This is a reasonable observation for a static situation where energy is stored on a transmission line. If the example contained an ongoing consideration, like "Where does the power move to?", then it would be reasonable to consider that the wave continued to move, simply to avoid the complication of what EXACTLY happens when a wave starts and stops. So have you thought about "where does the power go?" Yes, only the model I use substitutes a battery for the signal generator that you are using. A battery is not the same since it has a very low output impedance. A battery in series with a 50 ohm resistor would offer a reasonable match to a 50 ohm transmission line. The returning wave can recharge the battery, but how does the current stop? Or does it ever stop? From a practical aspect, the current must stop, but I can not explain how except by resistance that absorbs the circulating power. That is the challenging part to understand when too much emphasis is placed on the existance of energy being transported with the "reflected power". When I was learning this stuff, I did many examples with matched generators (a battery with a 50 ohm resistor is a good example). With step functions, it is easy to compute the final state because you can just treat it as a DC circuit for analysis. We must keep the limitations of our models in mind. True, but over limiting is not good either. When the generator is matched to the line so that the reflected wave does not encounter an impedance discontinuity when it arrives back at the generator (and therefore is not reflected), where does the reflected power go? Does it enter the generator? Is it dissipated somewhere? Answers to these questions will quickly lead to doubts about the *reality* of "reflected power". ...Keith The reflected wave that does not encounter an impedance at the generator must be on an infinitely long line, and therefore the conditions must have changed between the time of launch and return. I don't follow the association between generator impedance and length of line. For a 50 ohm line, a matched generator has a 50 ohm output impedance. The returning wave does not encounter an impedance discontinuity so is not reflected. It disappears into the the generator. It makes more sense to think that the reflected voltage of (using your example) 50v meets 50v of forward voltage, and therefore finds an infinite resistance, coming to a stop. The current does stop (since it can not flow into the infinite resistance at the end of the line), and a 50 V step propagates back along the line. This 50 V reverse propagating step plus the 50 V already on the line produces a total of 100 V on the line. If the generator was constructed as a 100 V battery in series with a 50 ohm resistor, then when the step arrives back at the generator, there is 100 V on both sides of the source resistor (battery on one side, line on the other) and the current through the source resistor becomes zero. No further current flows into the line. If that happens, doesn't the same condition occur as soon as the reflected wave is first generated at the line end? The current really stops as soon as the end is reached, with the energy contained in the magnetic field converted to electric field energy visible as voltage. If this happened, the reflected wave could be better described as an electric "jump", similar to a hydraulic jump found in open channel flow of liquids, where kinetic energy is converted to potential energy. There do seem to be some similarities, though there is likely trouble if the analogy is carried to far. This idea of an electric "jump" requires not a reflection occuring without a discontinuity, but a moving wave front that absorbs the traveling wave, bringing it to a stop (in this case). The current has stoppped, but has the "wave"? Vf, Vr, If, Ir, Pf, Pr are still computable using the normal formulae. ....Keith |
Derivation of Reflection Coefficient vs SWR
On Sat, 2 Feb 2008 13:01:22 -0800 (PST)
Keith Dysart wrote: On Jan 27, 10:57 am, Roger Sparks wrote: On Sat, 26 Jan 2008 19:24:22 -0800 (PST) Keith Dysart wrote: On Jan 26, 12:15 pm, Roger Sparks wrote: On Fri, 25 Jan 2008 19:13:31 -0800 (PST) Keith Dysart wrote: On Jan 24, 10:33 pm, Roger Sparks wrote: [snip] By examining this derivation, the reader can see that power and energy is reflected when a wave encounters a discontinuity. The reader can also see that more power is present on the transmission line than is delivered to the load. This is the conventional phraseology for describing the behaviour at the impedance discontinuity. Allow me to offer a specific example for which this phraseology is inappropriate. Consider a 50 V step function generator with an output impedance of 50 ohms driving a 50 ohm line that is 1 second long terminated in an open circuit. Turn on the generator. A 50 V step propagates down the line. The generator is putting 50 J/s into the line. One second later it reaches the open end and begins propagating backwards. After two seconds it reaches the generator. The voltage at the generator is now 100 V and no current is flowing from the generator into the line. In the 2 seconds, the generator put 100 joules into the line which is now stored in the line. The line is at a constant 100 V and the current is zero everywhere. Computing Pf and Pr will yield 50 W forward and 50 W reflected. And yet no current is flowing anywhere. The voltage on the line is completely static. And yet some will claim that 50 W is flowing forward and 50 W is flowing backwards. Does this seem like a reasonable claim for an open circuited transmission line with constant voltage along its length and no current anywhere? I do not find it so. ...Keith This is a reasonable observation for a static situation where energy is stored on a transmission line. If the example contained an ongoing consideration, like "Where does the power move to?", then it would be reasonable to consider that the wave continued to move, simply to avoid the complication of what EXACTLY happens when a wave starts and stops. So have you thought about "where does the power go?" Yes, only the model I use substitutes a battery for the signal generator that you are using. A battery is not the same since it has a very low output impedance. A battery in series with a 50 ohm resistor would offer a reasonable match to a 50 ohm transmission line. The returning wave can recharge the battery, but how does the current stop? Or does it ever stop? From a practical aspect, the current must stop, but I can not explain how except by resistance that absorbs the circulating power. That is the challenging part to understand when too much emphasis is placed on the existance of energy being transported with the "reflected power". When I was learning this stuff, I did many examples with matched generators (a battery with a 50 ohm resistor is a good example). With step functions, it is easy to compute the final state because you can just treat it as a DC circuit for analysis. We must keep the limitations of our models in mind. True, but over limiting is not good either. When the generator is matched to the line so that the reflected wave does not encounter an impedance discontinuity when it arrives back at the generator (and therefore is not reflected), where does the reflected power go? Does it enter the generator? Is it dissipated somewhere? Answers to these questions will quickly lead to doubts about the *reality* of "reflected power". ...Keith The reflected wave that does not encounter an impedance at the generator must be on an infinitely long line, and therefore the conditions must have changed between the time of launch and return. I don't follow the association between generator impedance and length of line. For a 50 ohm line, a matched generator has a 50 ohm output impedance. The returning wave does not encounter an impedance discontinuity so is not reflected. It disappears into the the generator. OK, I think we are saying the same thing. The return wave DISAPPEARS. It makes more sense to think that the reflected voltage of (using your example) 50v meets 50v of forward voltage, and therefore finds an infinite resistance, coming to a stop. The current does stop (since it can not flow into the infinite resistance at the end of the line), and a 50 V step propagates back along the line. This 50 V reverse propagating step plus the 50 V already on the line produces a total of 100 V on the line. If the generator was constructed as a 100 V battery in series with a 50 ohm resistor, then when the step arrives back at the generator, there is 100 V on both sides of the source resistor (battery on one side, line on the other) and the current through the source resistor becomes zero. No further current flows into the line. If that happens, doesn't the same condition occur as soon as the reflected wave is first generated at the line end? The current really stops as soon as the end is reached, with the energy contained in the magnetic field converted to electric field energy visible as voltage. If this happened, the reflected wave could be better described as an electric "jump", similar to a hydraulic jump found in open channel flow of liquids, where kinetic energy is converted to potential energy. There do seem to be some similarities, though there is likely trouble if the analogy is carried to far. This idea of an electric "jump" requires not a reflection occuring without a discontinuity, but a moving wave front that absorbs the traveling wave, bringing it to a stop (in this case). The current has stoppped, but has the "wave"? Vf, Vr, If, Ir, Pf, Pr are still computable using the normal formulae. ...Keith Here is a link to a web site discussing reflections and more. http://www.ivorcatt.co.uk/em.htm He has some drawings that pertain to this discussion. He shows reflections and crossings, but no one-way transmission lines. -- 73, Roger, W7WKB |
Derivation of Reflection Coefficient vs SWR
"Roger Sparks" wrote in message ... On Sat, 2 Feb 2008 13:01:22 -0800 (PST) Keith Dysart wrote: On Jan 27, 10:57 am, Roger Sparks wrote: On Sat, 26 Jan 2008 19:24:22 -0800 (PST) Keith Dysart wrote: On Jan 26, 12:15 pm, Roger Sparks wrote: On Fri, 25 Jan 2008 19:13:31 -0800 (PST) Keith Dysart wrote: On Jan 24, 10:33 pm, Roger Sparks wrote: [snip] By examining this derivation, the reader can see that power and energy is reflected when a wave encounters a discontinuity. The reader can also see that more power is present on the transmission line than is delivered to the load. This is the conventional phraseology for describing the behaviour at the impedance discontinuity. Allow me to offer a specific example for which this phraseology is inappropriate. Consider a 50 V step function generator with an output impedance of 50 ohms driving a 50 ohm line that is 1 second long terminated in an open circuit. Turn on the generator. A 50 V step propagates down the line. The generator is putting 50 J/s into the line. One second later it reaches the open end and begins propagating backwards. After two seconds it reaches the generator. The voltage at the generator is now 100 V and no current is flowing from the generator into the line. In the 2 seconds, the generator put 100 joules into the line which is now stored in the line. The line is at a constant 100 V and the current is zero everywhere. Computing Pf and Pr will yield 50 W forward and 50 W reflected. And yet no current is flowing anywhere. The voltage on the line is completely static. And yet some will claim that 50 W is flowing forward and 50 W is flowing backwards. Does this seem like a reasonable claim for an open circuited transmission line with constant voltage along its length and no current anywhere? I do not find it so. ...Keith This is a reasonable observation for a static situation where energy is stored on a transmission line. If the example contained an ongoing consideration, like "Where does the power move to?", then it would be reasonable to consider that the wave continued to move, simply to avoid the complication of what EXACTLY happens when a wave starts and stops. So have you thought about "where does the power go?" Yes, only the model I use substitutes a battery for the signal generator that you are using. A battery is not the same since it has a very low output impedance. A battery in series with a 50 ohm resistor would offer a reasonable match to a 50 ohm transmission line. The returning wave can recharge the battery, but how does the current stop? Or does it ever stop? From a practical aspect, the current must stop, but I can not explain how except by resistance that absorbs the circulating power. That is the challenging part to understand when too much emphasis is placed on the existance of energy being transported with the "reflected power". When I was learning this stuff, I did many examples with matched generators (a battery with a 50 ohm resistor is a good example). With step functions, it is easy to compute the final state because you can just treat it as a DC circuit for analysis. We must keep the limitations of our models in mind. True, but over limiting is not good either. When the generator is matched to the line so that the reflected wave does not encounter an impedance discontinuity when it arrives back at the generator (and therefore is not reflected), where does the reflected power go? Does it enter the generator? Is it dissipated somewhere? Answers to these questions will quickly lead to doubts about the *reality* of "reflected power". ...Keith The reflected wave that does not encounter an impedance at the generator must be on an infinitely long line, and therefore the conditions must have changed between the time of launch and return. I don't follow the association between generator impedance and length of line. For a 50 ohm line, a matched generator has a 50 ohm output impedance. The returning wave does not encounter an impedance discontinuity so is not reflected. It disappears into the the generator. OK, I think we are saying the same thing. The return wave DISAPPEARS. It makes more sense to think that the reflected voltage of (using your example) 50v meets 50v of forward voltage, and therefore finds an infinite resistance, coming to a stop. The current does stop (since it can not flow into the infinite resistance at the end of the line), and a 50 V step propagates back along the line. This 50 V reverse propagating step plus the 50 V already on the line produces a total of 100 V on the line. If the generator was constructed as a 100 V battery in series with a 50 ohm resistor, then when the step arrives back at the generator, there is 100 V on both sides of the source resistor (battery on one side, line on the other) and the current through the source resistor becomes zero. No further current flows into the line. If that happens, doesn't the same condition occur as soon as the reflected wave is first generated at the line end? The current really stops as soon as the end is reached, with the energy contained in the magnetic field converted to electric field energy visible as voltage. If this happened, the reflected wave could be better described as an electric "jump", similar to a hydraulic jump found in open channel flow of liquids, where kinetic energy is converted to potential energy. There do seem to be some similarities, though there is likely trouble if the analogy is carried to far. This idea of an electric "jump" requires not a reflection occuring without a discontinuity, but a moving wave front that absorbs the traveling wave, bringing it to a stop (in this case). The current has stoppped, but has the "wave"? Vf, Vr, If, Ir, Pf, Pr are still computable using the normal formulae. ...Keith Here is a link to a web site discussing reflections and more. http://www.ivorcatt.co.uk/em.htm He has some drawings that pertain to this discussion. He shows reflections and crossings, but no one-way transmission lines. -- 73, Roger, W7WKB I just love this quote from that material "...Thus do these clapped-out radio men..." Though it's all above my head, I have indeed met some clapped out radio men. |
Derivation of Reflection Coefficient vs SWR
Roger Sparks wrote:
Here is a link to a web site discussing reflections and more. http://www.ivorcatt.co.uk/em.htm Interesting - especially about the inductance (loading coil) acting like a transmission line. -- 73, Cecil http://www.w5dxp.com |
Derivation of Reflection Coefficient vs SWR
On Jan 28, 11:30 am, Cecil Moore wrote:
Keith Dysart wrote: Unfortunately, this is quite wrong. And I continue to be surprised that you argue that there is a reflection where there is not an impedance discontinuity. Since an absence of reflections violates the conservation of energy principle, there is something wrong with your assertion and your earlier example was proved to contain a contradiction. Psource = Pfor - Pref = Pload Pfor = Psource + Pref = Pload + Pref Those equations are true only if reflected energy does not flow back into the source. I suspect that, contrary to your assertions, the actual real-world source presents an infinite impedance to reflected waves. Your suspicion is quite incorrect. Real-world generators which present well defined impedances to the reflected wave are common. And your assertion that a lack of reflections will result in a violation of the conservation of energy principle is also incorrect. The equations you present above hold just as well when there is no reflection at the source. It might do to analyze a simple example. To simplify analysis, this example does use ideal components: there is an ideal 50 ohm transmission line (R=G=0, uniform 50 ohm impedance along its length), two ideal resistors (zero tempco, no inductance or capacitance, just resistance), and an ideal voltage source (desired voltage is produced regardless of load impedance, though the external components mean this source does not need to provide or sink infinite current). If you don't think any understanding can be gained from examples with ideal components, please read no further. This simple example has a voltage source in series with a 50 ohm resistor, driving 45 degrees of 50 ohm line connected to a 150 ohm load. Rs Vg Vl +----/\/\/-----+----------------------+ | 50 ohm | | / Vs 45 degrees \ Rl 100 cos(wt) 50 ohm line / 150 ohm | \ load | | +--------------+----------------------+ gnd The voltage source in series with the 50 ohm resistor forms a generator. Vs(t) = 100 cos(wt) or, in phasor notation Vs = 100 /_ 0d where d is degrees or 2*pi/360 when converting to radians is appropriate. When the source is turned on, a wave travels down the line. At the generator terminal (Vg), the forward voltage is: Vf.g(t) = 50 cos(wt) Vf.g = 50 /_ 0d since the voltage divided evenly between the source 50 ohm resistor and 50 ohm impedance of the line. At the load, the voltage reflection coefficient is RCvl = (150-50)/(150+50) = 0.5 The forward voltage at the load is Vf.l(t) = 50 cos(wt - 45d) Vf.l = 50 /_ -45d The reflected voltage at the load is Vr.l(t) = 0.5 * 50 cos(wt - 45d) = 25 cos(wt - 45d) Vr.l = 25 /_ -45d The voltage at the load is Vl = Vf.l + Vr.l = 50 /_ -45d + 25 /_ -45d = 75 /_ -45d Vl(t) = 75 cos(wt - 45d) At the generator, the voltage reflection coefficient is RCvg = (50-50)/(50+50) = 0 so there is no reflection and the system has settled after one round trip. The voltage at the generator is, therefore, Vg = Vf.g + Vr.g = 50 /_ 0d + 25 /_ (-45d -45d) = 50 /_ 0d + 25 /_ -90d = 55.902 /_ -26.565d Vg(t) = 55.902 cos(wt - 26.565d) Currents can be similar computed... If.g(t) = 1 cos(wt) If.g = 1 /_ 0d RCil = -(150-50)/(150+50) = -0.5 If.l(t) = 1 cos(wt - 45d) If.l = 1 /_ -45d Ir.l(t) = -0.5 * 1 cos(wt - 45d) = -0.5 cos(wt - 45d) Ir.l = -0.5 /_ -45d Il = If.l + Ir.l = 1 /_ -45d - 0.5 /_ -45d = 0.5 /_ -45d Il(t) = 0.5 cos(wt - 45d) And just to check, from V = I*R R = V / I = Vl(t) / Il(t) = (75 cos(wt-45d)) / (0.5 cos(wt-45d)) = 150 as expected. RCig = -(50-50)/(50+50) = 0 Ig = If.g + Ir.g = 1 /_ 0d - 0.5 /_ (-45d -45d) = 1 /_ 0d -0.5 /_ -90d = 1.118 /_ 26.565d Ig(t) = 1.118 cos(wt + 26.565d) Now let us see if all the energy flows balance properly. The power applied to the load resistor is Pl(t) = Vl(t) * Il(t) = 75 cos(wt - 45d) * 0.5 cos(wt - 45d) Recalling the relation cos(a) * cos(b) = 0.5(cos(a+b)+cos(a-b)) Pl(t) = 75 * 0.5 * 0.5 (cos(2wt-90d)+cos(0)) = 18.75 cos(2wt-90d) + 18.75 cos(0) = 18.75 cos(2wt-90d) + 18.75 Since the average of cos is 0, the average power is Pl.avg = 18.75 To confirm, let us compute using Pavg = Vrms * Irms * cos(theta) Pl.avg = (75 * 0.707) * (0.5 * 0.707) * cos(-45d-(-45d)) = 18.75 * 1 = 18.75 Agreement. Now at the generator end Pg(t) = Vg(t) * Ig(t) = 55.902 cos(wt - 26.565d) * 1.118 cos(wt + 26.565d) = 55.902 * 1.118 * 0.5 (cos(2wt)+cos(-53.130)) = 31.249 cos(2wt) + 31.249 * 0.6 = 31.249 cos(2wt) + 18.75 Pg.avg = 18.75 Good news, the average power into the line is equal to the average power delivered to the load, as required to achieve conservation of energy. Now let us check Pf and Pr Pf.avg = Vfrms^2 / Zo = (50*.707)^2 / 50 = 25 Pr.avg = Vrrms^2 / Zo = (25*.707)^2 / 50 = 6.25 Pnet.avg = Pf.avg - Pr.avg = 25 - 6.25 = 18.75 Again, as expected, the average energy flow in the line is equal to the average power into the line and the average power out of the line. So, contrary to Cecil's assertion, an analysis based on 'no reflections at the source', has not resulted in any violation of conservation of energy. This is good. It is instructive to continue the cross-checking. Let us validate the input impedance of the line. Using a Smith chart, and going towards the source from a 150 ohm load on a 50 ohm line yields Zin.smith = 30 - j40 = 50 /_ -53.130 Dividing the voltage by the current at the input to the line... Zin = Vg / Ig = 55.902 /_ -26.565d / 1.118 /_ 26.565d = 50.002 /_ -53.130 = 30.001 -j 40.001 yields the same result as the Smith chart. Lastly let's compute the power provided by the source... Ps(t) = Vs(t) * Is(t) = 100 cos(wt) * 1.118 cos(wt+26.565) = 111.8 * 0.5 (cos(2wt+26.565) + cos(-26.565)) = 55.9 cos(2wt + 26.565) + 55.9 * 0.894 = 55.9 cos(2wt + 26.565) + 49.999 Ps.avg = 49.999 and that dissipated in the source resistor Prs(t) = Vrs(t) * Irs(t) = (Vs(t)-Vg(t)) * Ig(t) = (100 cos(wt) - 55.902 cos(wt - 26.565d)) * 1.118 cos(wt + 26.565d) = 55.902 cos(wt + 26.565d) * 1.118 cos(wt + 26.565d) = 55.902 * 1.118 * 0.5 (cos(2wt + 53.130) + cos(0)) = 31.249 cos(2wt + 53.130d) + 31.249 Prs.avg = 31.249 The power provided by the source is equal to the power dissipated in the source resistor and the power dissipated in the load resistor. 49.999 = 31.249 + 18.75 So all the energy is accounted for, as expected. When the source impedance is the same as the line impedance, there are no reflections at the source and all the energy is properly accounted. There is no violation of the conservation of energy principle. ....Keith PS. It is worthwhile to note that there are a large number (infinite) of source voltage and source resistor combinations that will produce exactly the same final conditions on the line. But if the source resistor is not 50 ohms, then there will be reflections at the source and it will take infinite time for the line to settle to its final state. |
Derivation of Reflection Coefficient vs SWR
Keith Dysart wrote:
Your suspicion is quite incorrect. Real-world generators which present well defined impedances to the reflected wave are common. Please provide an example of an amateur radio transmitter with a well-defined impedance seen by reflected waves. If you had done that 30 years ago, the argument would never have existed in the first place. And your assertion that a lack of reflections will result in a violation of the conservation of energy principle is also incorrect. One cannot have one's source power and eat it too. If the reflected energy is part of the forward energy, it cannot also flow into the source. The equations you present above hold just as well when there is no reflection at the source. How can there be no reflection at the source when the source is dissipating zero power? If you don't think any understanding can be gained from examples with ideal components, please read no further. If those ideal components are far removed from being realizable in the real-world, you have yourself a deal. Until you can provide an example of a real-world source approaching a zero real-world impedance, there is no reason to read any further. You might as well just say, "God causes everything." and be done with it. -- 73, Cecil http://www.w5dxp.com |
Derivation of Reflection Coefficient vs SWR
On Feb 4, 5:54*pm, Cecil Moore wrote:
Keith Dysart wrote: Your suspicion is quite incorrect. Real-world generators which present well defined impedances to the reflected wave are common. Please provide an example of an amateur radio transmitter with a well-defined impedance seen by reflected waves. If you had done that 30 years ago, the argument would never have existed in the first place. Non-sequitor. If the impedance is not well-defined, then it is impossible to draw any conclusions about reflections at the generator. So any claim of total reflection in such an environment would be invalid. And your assertion that a lack of reflections will result in a violation of the conservation of energy principle is also incorrect. One cannot have one's source power and eat it too. If the reflected energy is part of the forward energy, it cannot also flow into the source. I observe that you refuse to explore the example that demonstrates that this is not an issue. The equations you present above hold just as well when there is no reflection at the source. How can there be no reflection at the source when the source is dissipating zero power? In the example, the source is not dissipating zero power. You should consider examining the example. If you don't think any understanding can be gained from examples with ideal components, please read no further. If those ideal components are far removed from being realizable in the real-world, you have yourself a deal. Until you can provide an example of a real-world source approaching a zero real-world impedance, there is no reason to read any further. You might as well just say, "God causes everything." and be done with it. Any excuse to avoid the risk of learning that your beliefs are incorrect. Take a chance. Try to find the flaws in the analysis of this simplest of examples. If there are flaws, they should not take you long to locate. ...Keith |
Derivation of Reflection Coefficient vs SWR
Keith Dysart wrote:
I observe that you refuse to explore the example that demonstrates that this is not an issue. I didn't refuse to explore the example. You told me to "read no further" so I did just that. If you don't think any understanding can be gained from examples with ideal components, please read no further. Ideal components have led to such outrageous concepts as zero delays through 75m bugcatcher loading coils. Do you really believe in zero delays through those big honking 75m loading coils? -- 73, Cecil http://www.w5dxp.com |
Derivation of Reflection Coefficient vs SWR
On Feb 5, 12:05*am, Cecil Moore wrote:
Keith Dysart wrote: I observe that you refuse to explore the example that demonstrates that this is not an issue. I didn't refuse to explore the example. You told me to "read no further" so I did just that. There was an 'if' clause. YOU made the choice to avoid the opportunity for learning. I notice that your own examples are often constructed with ideal components, so this aversion to ideal components is not universal. Perhaps only when it can be conveniently used to avoid situations where your deeply held beliefs may be threatened? ...Keith |
Derivation of Reflection Coefficient vs SWR
Keith Dysart wrote:
This simple example has a voltage source in series with a 50 ohm resistor, driving 45 degrees of 50 ohm line connected to a 150 ohm load. Rs Vg Vl +----/\/\/-----+----------------------+ | 50 ohm | | / Vs 45 degrees \ Rl 100 cos(wt) 50 ohm line / 150 ohm | \ load | | +--------------+----------------------+ gnd The voltage source in series with the 50 ohm resistor forms a generator. Vs(t) = 100 cos(wt) So, contrary to Cecil's assertion, an analysis based on 'no reflections at the source', has not resulted in any violation of conservation of energy. This is good. Keith, this special case is covered in my Worldradio energy analysis article at: http://www.w5dxp.com/energy.htm I agree with your special case analysis. The reason that it is a special case is that at the generator terminals: (Vf)^2 + (Vr)^2 = (Vf+Vr)^2 i.e. you have chosen the one special case where the superposition of powers yields a valid result. Quoting my article with some special characters replaced by ASCII characters: "If A = 90 deg, then cos(A) = 0, and there is no destructive/constructive interference between V1 and V2. There is also no destructive/constructive interference between V3 and V4. Any potential destructive/constructive interference between any two voltages is eliminated because A = 90 deg, i.e. the voltages are superposed orthogonal to each other (almost as if they were not coherent)." At the generator terminals, you have chosen the one phase angle between Vf and Vr that will result in zero interference. Whether by accident or on purpose is unclear. The phase angle between Vf and Vr at the generator terminals is 90 degrees resulting in zero interference. Your analysis is completely correct for this special case. Now try it for any length of feedline between 0 deg and 180 deg besides 45 deg and 135 deg. 90 degrees would be very easy to calculate. -- 73, Cecil http://www.w5dxp.com |
Derivation of Reflection Coefficient vs SWR
Keith Dysart wrote:
Cecil Moore wrote: I didn't refuse to explore the example. You told me to "read no further" so I did just that. There was an 'if' clause. YOU made the choice to avoid the opportunity for learning. It was an obvious joke, Keith. I just analyzed your analysis and pointed out that your choice was a special case that made it OK to superpose powers. Shame on you. -- 73, Cecil http://www.w5dxp.com |
Derivation of Reflection Coefficient vs SWR
Keith Dysart wrote:
The power provided by the source is equal to the power dissipated in the source resistor and the power dissipated in the load resistor. 49.999 = 31.249 + 18.75 So all the energy is accounted for, as expected. I'm surprised you don't see your own contradiction. If, as you say, the reflected wave is not reflected by the source, then the reflected wave flows through the source resistor to ground and is dissipated. If the reflected wave is dissipated in the source resistor, it cannot join the forward wave. The forward wave is 25 joules/sec. The source is supplying 18.75 joules/sec. If the reflected wave is dissipated in the source, where is the other 6.25 joules/sec coming from? Is it mere coincidence that the reflected wave is 6.25 joules/sec???? Hint: You cannot eat your reflected wave and have it too. If the forward power is greater than the source power, the reflected wave is joining the forward wave, i.e. being reflected by the source. Here is an example of the reflected wave flowing through the circulator resistor and being dissipated. Source---1---2----45 deg 50 ohm feedline---150 ohm load \ / | 50 ohms But in this example Psource = Pforward in order to satisfy the conservation of energy principle which your example does not. -- 73, Cecil http://www.w5dxp.com |
Derivation of Reflection Coefficient vs SWR
On Mon, 4 Feb 2008 12:32:39 -0800 (PST)
Keith Dysart wrote: On Jan 28, 11:30 am, Cecil Moore wrote: Keith Dysart wrote: Unfortunately, this is quite wrong. And I continue to be surprised that you argue that there is a reflection where there is not an impedance discontinuity. Since an absence of reflections violates the conservation of energy principle, there is something wrong with your assertion and your earlier example was proved to contain a contradiction. Psource = Pfor - Pref = Pload Pfor = Psource + Pref = Pload + Pref Those equations are true only if reflected energy does not flow back into the source. I suspect that, contrary to your assertions, the actual real-world source presents an infinite impedance to reflected waves. Your suspicion is quite incorrect. Real-world generators which present well defined impedances to the reflected wave are common. And your assertion that a lack of reflections will result in a violation of the conservation of energy principle is also incorrect. The equations you present above hold just as well when there is no reflection at the source. It might do to analyze a simple example. To simplify analysis, this example does use ideal components: there is an ideal 50 ohm transmission line (R=G=0, uniform 50 ohm impedance along its length), two ideal resistors (zero tempco, no inductance or capacitance, just resistance), and an ideal voltage source (desired voltage is produced regardless of load impedance, though the external components mean this source does not need to provide or sink infinite current). If you don't think any understanding can be gained from examples with ideal components, please read no further. This simple example has a voltage source in series with a 50 ohm resistor, driving 45 degrees of 50 ohm line connected to a 150 ohm load. Rs Vg Vl +----/\/\/-----+----------------------+ | 50 ohm | | / Vs 45 degrees \ Rl 100 cos(wt) 50 ohm line / 150 ohm | \ load | | +--------------+----------------------+ gnd The voltage source in series with the 50 ohm resistor forms a generator. Vs(t) = 100 cos(wt) or, in phasor notation Vs = 100 /_ 0d where d is degrees or 2*pi/360 when converting to radians is appropriate. When the source is turned on, a wave travels down the line. At the generator terminal (Vg), the forward voltage is: Vf.g(t) = 50 cos(wt) Vf.g = 50 /_ 0d since the voltage divided evenly between the source 50 ohm resistor and 50 ohm impedance of the line. At the load, the voltage reflection coefficient is RCvl = (150-50)/(150+50) = 0.5 The forward voltage at the load is Vf.l(t) = 50 cos(wt - 45d) Vf.l = 50 /_ -45d The reflected voltage at the load is Vr.l(t) = 0.5 * 50 cos(wt - 45d) = 25 cos(wt - 45d) Vr.l = 25 /_ -45d The voltage at the load is Vl = Vf.l + Vr.l = 50 /_ -45d + 25 /_ -45d = 75 /_ -45d Vl(t) = 75 cos(wt - 45d) At the generator, the voltage reflection coefficient is RCvg = (50-50)/(50+50) = 0 so there is no reflection and the system has settled after one round trip. The voltage at the generator is, therefore, Vg = Vf.g + Vr.g = 50 /_ 0d + 25 /_ (-45d -45d) = 50 /_ 0d + 25 /_ -90d = 55.902 /_ -26.565d Vg(t) = 55.902 cos(wt - 26.565d) Whoa! You started with 50 volts applied to the forward line, then froze the wave by finding the time phase of the wave. Mathematically, you want to find the voltage at the generator which is the sum of the terms Vf.g and Vr.g. The sum of those terms is 50 + 0 = 50, not 55.902 /_ -26.565d. Currents can be similar computed... If.g(t) = 1 cos(wt) If.g = 1 /_ 0d RCil = -(150-50)/(150+50) = -0.5 If.l(t) = 1 cos(wt - 45d) If.l = 1 /_ -45d Ir.l(t) = -0.5 * 1 cos(wt - 45d) = -0.5 cos(wt - 45d) Ir.l = -0.5 /_ -45d Il = If.l + Ir.l = 1 /_ -45d - 0.5 /_ -45d = 0.5 /_ -45d Il(t) = 0.5 cos(wt - 45d) And just to check, from V = I*R R = V / I = Vl(t) / Il(t) = (75 cos(wt-45d)) / (0.5 cos(wt-45d)) = 150 as expected. RCig = -(50-50)/(50+50) = 0 Ig = If.g + Ir.g = 1 /_ 0d - 0.5 /_ (-45d -45d) = 1 /_ 0d -0.5 /_ -90d = 1.118 /_ 26.565d Ig(t) = 1.118 cos(wt + 26.565d) The same error here. Ig = 1 /_ 0d - 0.5 /_ -90d = 1 - 0 = 1 Now let us see if all the energy flows balance properly. The power applied to the load resistor is Pl(t) = Vl(t) * Il(t) = 75 cos(wt - 45d) * 0.5 cos(wt - 45d) Recalling the relation cos(a) * cos(b) = 0.5(cos(a+b)+cos(a-b)) Pl(t) = 75 * 0.5 * 0.5 (cos(2wt-90d)+cos(0)) = 18.75 cos(2wt-90d) + 18.75 cos(0) = 18.75 cos(2wt-90d) + 18.75 Since the average of cos is 0, the average power is Pl.avg = 18.75 To confirm, let us compute using Pavg = Vrms * Irms * cos(theta) Pl.avg = (75 * 0.707) * (0.5 * 0.707) * cos(-45d-(-45d)) = 18.75 * 1 = 18.75 Agreement. Now at the generator end Pg(t) = Vg(t) * Ig(t) = 55.902 cos(wt - 26.565d) * 1.118 cos(wt + 26.565d) = 55.902 * 1.118 * 0.5 (cos(2wt)+cos(-53.130)) = 31.249 cos(2wt) + 31.249 * 0.6 = 31.249 cos(2wt) + 18.75 Pg.avg = 18.75 No. Based on the way I read your CORRECTED sums, the power at the generator Pg should be 50 * 1 = 50. Good news, the average power into the line is equal to the average power delivered to the load, as required to achieve conservation of energy. Now let us check Pf and Pr Pf.avg = Vfrms^2 / Zo = (50*.707)^2 / 50 = 25 Pr.avg = Vrrms^2 / Zo = (25*.707)^2 / 50 = 6.25 Pnet.avg = Pf.avg - Pr.avg = 25 - 6.25 = 18.75 Again, as expected, the average energy flow in the line is equal to the average power into the line and the average power out of the line. So, contrary to Cecil's assertion, an analysis based on 'no reflections at the source', has not resulted in any violation of conservation of energy. This is good. It is instructive to continue the cross-checking. Let us validate the input impedance of the line. Using a Smith chart, and going towards the source from a 150 ohm load on a 50 ohm line yields Zin.smith = 30 - j40 = 50 /_ -53.130 Dividing the voltage by the current at the input to the line... Zin = Vg / Ig = 55.902 /_ -26.565d / 1.118 /_ 26.565d = 50.002 /_ -53.130 = 30.001 -j 40.001 yields the same result as the Smith chart. Lastly let's compute the power provided by the source... Ps(t) = Vs(t) * Is(t) = 100 cos(wt) * 1.118 cos(wt+26.565) = 111.8 * 0.5 (cos(2wt+26.565) + cos(-26.565)) = 55.9 cos(2wt + 26.565) + 55.9 * 0.894 = 55.9 cos(2wt + 26.565) + 49.999 Ps.avg = 49.999 and that dissipated in the source resistor Prs(t) = Vrs(t) * Irs(t) = (Vs(t)-Vg(t)) * Ig(t) = (100 cos(wt) - 55.902 cos(wt - 26.565d)) * 1.118 cos(wt + 26.565d) = 55.902 cos(wt + 26.565d) * 1.118 cos(wt + 26.565d) = 55.902 * 1.118 * 0.5 (cos(2wt + 53.130) + cos(0)) = 31.249 cos(2wt + 53.130d) + 31.249 Prs.avg = 31.249 The power provided by the source is equal to the power dissipated in the source resistor and the power dissipated in the load resistor. 49.999 = 31.249 + 18.75 So all the energy is accounted for, as expected. When the source impedance is the same as the line impedance, there are no reflections at the source and all the energy is properly accounted. There is no violation of the conservation of energy principle. ...Keith PS. It is worthwhile to note that there are a large number (infinite) of source voltage and source resistor combinations that will produce exactly the same final conditions on the line. But if the source resistor is not 50 ohms, then there will be reflections at the source and it will take infinite time for the line to settle to its final state. With the circuit and conditions presented, the reflected voltage and current return out of phase in time with the source voltage and current. A standing wave condition of 3:1 would always exist throughout the system. -- 73, Roger, W7WKB |
Derivation of Reflection Coefficient vs SWR
On Feb 5, 5:59*am, Cecil Moore wrote:
Keith Dysart wrote: This simple example has a voltage source in series with a 50 ohm resistor, driving 45 degrees of 50 ohm line connected to a 150 ohm load. * * * * * *Rs * * * Vg * * * * * * * * * * Vl * * *+----/\/\/-----+----------------------+ * * *| * *50 ohm * * * * * * * * * * * * * | * * *| * * * * * * * * * * * * * * * * * * / * * Vs * * * * * * * * 45 degrees * * * * *\ * Rl *100 cos(wt) * * * * * 50 ohm line * * * * / 150 ohm * * *| * * * * * * * * * * * * * * * * * * \ *load * * *| * * * * * * * * * * * * * * * * * * | * * *+--------------+----------------------+ * * gnd The voltage source in series with the 50 ohm resistor forms a generator. Vs(t) = 100 cos(wt) So, contrary to Cecil's assertion, an analysis based on 'no reflections at the source', has not resulted in any violation of conservation of energy. This is good. Keith, this special case is covered in my Worldradio energy analysis article at: http://www.w5dxp.com/energy.htm I agree with your special case analysis. The reason that it is a special case is that at the generator terminals: (Vf)^2 + (Vr)^2 = (Vf+Vr)^2 i.e. you have chosen the one special case where the superposition of powers yields a valid result. Quoting my article with some special characters replaced by ASCII characters: "If A = 90 deg, then cos(A) = 0, and there is no destructive/constructive interference between V1 and V2. There is also no destructive/constructive interference between V3 and V4. Any potential destructive/constructive interference between any two voltages is eliminated because A = 90 deg, i.e. the voltages are superposed orthogonal to each other (almost as if they were not coherent)." At the generator terminals, you have chosen the one phase angle between Vf and Vr that will result in zero interference. Whether by accident or on purpose is unclear. The phase angle between Vf and Vr at the generator terminals is 90 degrees resulting in zero interference. Your analysis is completely correct for this special case. Now try it for any length of feedline between 0 deg and 180 deg besides 45 deg and 135 deg. 90 degrees would be very easy to calculate. I choose 45 degrees because it was not 90, the standard value used which leaves all sorts of misleading artifacts when doing analysis. I noticed that a few artifacts also exist at 45 but I had hoped they would not mislead. I see I was wrong. Below, I have redone the analysis with a 35 degree line. The analysis is based on no reflection occurring at the generator, and the energy flows still balance as expected. The analysis for a 35 degree line follow. -------- This simple example has a voltage source in series with a 50 ohm resistor, driving 35 degrees of 50 ohm line connected to a 150 ohm load. Rs Vg Vl +----/\/\/-----+----------------------+ | 50 ohm | | / Vs 35 degrees \ Rl 100 cos(wt) 50 ohm line / 150 ohm | \ load | | +--------------+----------------------+ gnd The voltage source in series with the 50 ohm resistor forms a generator. Vs(t) = 100 cos(wt) or, in phasor notation Vs = 100 /_ 0d where d is degrees or 2*pi/360 when converting to radians is appropriate. When the source is turned on, a wave travels down the line. At the generator terminal (Vg), the forward voltage is: Vf.g(t) = 50 cos(wt) Vf.g = 50 /_ 0d since the voltage divided evenly between the source 50 ohm resistor and 50 ohm impedance of the line. At the load, the voltage reflection coefficient is RCvl = (150-50)/(150+50) = 0.5 The forward voltage at the load is Vf.l(t) = 50 cos(wt - 35d) Vf.l = 50 /_ 35d The reflected voltage at the load is Vr.l(t) = 0.5 * 50 cos(wt - 35d) = 25 cos(wt - 35d) Vr.l = 25 /_ -35d The voltage at the load is Vl = Vf.l + Vr.l = 50 /_ -35d + 25 /_ -35d = 75 /_ -35d Vl(t) = 75 cos(wt - 35d) At the generator, the voltage reflection coefficient is RCvg = (50-50)/(50+50) = 0 so there is no reflection and the system has settled after one round trip. The voltage at the generator is, therefore, Vg = Vf.g + Vr.g = 50 /_ 0d + 25 /_ (-35d -35d) = 50 /_ 0d + 25 /_ -70d = 63.087640 /_ -21.862219d Vg(t) = 63.087640 cos(wt - 21.86221d) Currents can be similar computed... If.g(t) = 1 cos(wt) If.g = 1 /_ 0d RCil = -(150-50)/(150+50) = -0.5 If.l(t) = 1 cos(wt - 35d) If.l = 1 /_ -35d Ir.l(t) = -0.5 * 1 cos(wt - 35d) = -0.5 cos(wt - 35d) Ir.l = -0.5 /_ -35d Il = If.l + Ir.l = 1 /_ -35d - 0.5 /_ -35d = 0.5 /_ -35d Il(t) = 0.5 cos(wt - 35d) And just to check, from V = I*R R = V / I = Vl(t) / Il(t) = (75 cos(wt-35d)) / (0.5 cos(wt-35d)) = 150 as expected. RCig = -(50-50)/(50+50) = 0 Ig = If.g + Ir.g = 1 /_ 0d - 0.5 /_ (-35d -35d) = 1 /_ 0d - 0.5 /_ -70d = 0.952880 /_ 29.543247d Ig(t) = 0.952880 cos(wt + 29.54324d) Now let us see if all the energy flows balance properly. The power applied to the load resistor is Pl(t) = Vl(t) * Il(t) = 75 cos(wt - 35d) * 0.5 cos(wt - 35d) Recalling the relation cos(a) * cos(b) = 0.5(cos(a+b)+cos(a-b)) Pl(t) = 75 * 0.5 * 0.5 (cos(2wt-70d)+cos(0)) = 18.75 cos(2wt-70d) + 18.75 cos(0) = 18.75 cos(2wt-70d) + 18.75 Since the average of cos is 0, the average power is Pl.avg = 18.75 To confirm, let us compute using Pavg = Vrms * Irms * cos(theta) Pl.avg = (75 * 0.707) * (0.5 * 0.707) * cos(-35d-(-35d)) = 18.75 * 1 = 18.75 Agreement. Now at the generator end Pg(t) = Vg(t) * Ig(t) = 63.087640 cos(wt - 21.862212d) * 0.952880 cos(wt + 29.543247d) = 63.087640 * 0.952880 * 0.5 (cos(2wt+7.681035)+cos(-51.405466)) = 30.057475 cos(2wt) + 30.057475 * 0.623805 = 30.057475 cos(2wt) + 18.750004 Pg.avg = 18.75 Good news, the average power into the line is equal to the average power delivered to the load, as required to achieve conservation of energy. Now let us check Pf and Pr Pf.avg = Vfrms^2 / Zo = (50*.707)^2 / 50 = 25 Pr.avg = Vrrms^2 / Zo = (25*.707)^2 / 50 = 6.25 Pnet.avg = Pf.avg - Pr.avg = 25 - 6.25 = 18.75 Again, as expected, the average energy flow in the line is equal to the average power into the line and the average power out of the line. So, contrary to Cecil's assertion, an analysis based on 'no reflections at the source', has not resulted in any violation of conservation of energy. This is good. It is instructive to continue the cross-checking. Let us validate the input impedance of the line. Using a Smith chart (http://education.tm.agilent.com/index.cgi?CONTENT_ID=5), and going towards the source from a 150 ohm load on a 50 ohm line yields Zin.smith = 41.28 - j51.73 = 66.18 /_ -51.41 Dividing the voltage by the current at the input to the line... Zin = Vg / Ig = 63.087640 /_ -21.862219d / 0.952880 /_ 29.543247d = 66.207329 /_ -51.405466 = 41.300466 -j51.746324 yields the same result as the Smith chart. Lastly let's compute the power provided by the source... Ps(t) = Vs(t) * Is(t) = 100 cos(wt) * 0.952880 cos(wt+29.543247d) = 95.288000 * 0.5 (cos(2wt+29.543247d) + cos(-29.543247d)) = 47.644000 cos(2wt + 29.543247) + 47.644000 * 0.869984 = 47.644000 cos(2wt + 29.543247) + 41.449507 Ps.avg = 41.449507 and that dissipated in the source resistor Prs(t) = Vrs(t) * Irs(t) = (Vs(t)-Vg(t)) * Ig(t) = (100 cos(wt) - 63.087640 cos(wt - 21.862219d)) * 0.95288 cos(wt + 29.543247d) = 47.643989 cos(wt + 29.543247d) * 0.952880 cos(wt + 29.543247d) = 47.643989 * 0.952880 * 0.5 (cos(2wt + 59.086480d) + cos(0)) = 22.699502 cos(2wt + 59.086480d) + 22.699502 Prs.avg = 22.699502 The power provided by the source is equal to the power dissipated in the source resistor and the power dissipated in the load resistor. 41.44950 = 22.699502 + 18.75 So all the energy is accounted for, as expected. When the source impedance is the same as the line impedance, there are no reflections at the source and all the energy is properly accounted. There is no violation of the conservation of energy principle. ...Keith PS. It is worthwhile to note that there are a large number (infinite) of source voltage and source resistor combinations that will produce exactly the same final conditions on the line. But if the source resistor is not 50 ohms, then there will be reflections at the source and it will take infinite time for the line to settle to its final state. |
Derivation of Reflection Coefficient vs SWR
On Feb 5, 8:53*am, Roger Sparks wrote:
On Mon, 4 Feb 2008 12:32:39 -0800 (PST) Keith Dysart wrote: [snip] The voltage at the generator is, therefore, Vg = Vf.g + Vr.g * *= 50 /_ 0d + 25 /_ (-45d -45d) * *= 50 /_ 0d + 25 /_ -90d * *= 55.902 /_ -26.565d Vg(t) = 55.902 cos(wt - 26.565d) Whoa! *You started with 50 volts applied to the forward line, then froze the wave by finding the time phase of the wave. *Mathematically, you want to find the voltage at the generator which is the sum of the terms Vf.g and Vr.g. *The sum of those terms is 50 + 0 = 50, not *55.902 /_ -26.565d.. Vr.g is the reflection of Vf from the load so it is a delayed version of Vr.l, the delay being another 45 degrees. The reflected voltage at the load is 25 /_ -45d Another 45 degrees makes it 25 /_ -90d by the time it gets back to the generator terminal. So the total voltage at the generator is Vg = Vf.g + Vr.g = 50 /_ 0d + 25 /_ (-45d -45d) = 50 /_ 0d + 25 /_ -90d = 55.902 /_ -26.565d Vg(t) = 55.902 cos(wt - 26.565d) [snip] Similarly for Ig and Ig(t) and Pg.avg and Pg(t). [snip] With the circuit and conditions presented, the reflected voltage and current return out of phase in time with the source voltage and current. *A standing wave condition of 3:1 would always exist throughout the system. Agreed, though it might be slightly more correct to say that there is a 3:1 VSWR on the transmission line. ...Keith |
Derivation of Reflection Coefficient vs SWR
Keith Dysart wrote:
So, contrary to Cecil's assertion, an analysis based on 'no reflections at the source', has not resulted in any violation of conservation of energy. This is good. Again your analysis violates the conservation of energy principle. The only way to balance your energy equation is for your source to supply 25 joules/sec. IF THE REFLECTED WAVE IS NOT REFLECTED FROM THE SOURCE, IT FLOWS THROUGH THE SOURCE RESISTOR AND IS DISSIPATED IN THE SOURCE RESISTOR. THAT REFLECTED WAVE ENERGY IS THEREFORE NOT AVAILABLE TO THE FORWARD WAVE. You cannot eat your reflected wave and have it too. The standard equation is: Psource = Pfor - Pref = Pload But you have taken away the reflected energy and dissipated it in the source resistor. So your new equation becomes: Psource = Pfor + ???????? 18.75w = 25w + ________ You say the source power is 18.75 joules/sec and the forward power is 25 joules/sec. If none of the reflected energy is available to the forward wave, where did the extra 6.25 joules/sec come from? Is it sheer coincidence that the reflected wave is associated with 6.25 joules/sec that are now missing from the above equation? Here is an example of the reflected wave flowing through a circulator resistor and being dissipated. Source---1---2----45 deg 50 ohm feedline---150 ohm load 25w \ / 18.75w | 50 ohms 6.25w But in this example Psource = Pfor in order to satisfy the conservation of energy principle which your example does not. -- 73, Cecil http://www.w5dxp.com |
Derivation of Reflection Coefficient vs SWR
On Feb 5, 7:40*am, Cecil Moore wrote:
Keith Dysart wrote: The power provided by the source is equal to the power dissipated in the source resistor and the power dissipated in the load resistor. 49.999 = 31.249 + 18.75 So all the energy is accounted for, as expected. I'm surprised you don't see your own contradiction. If, as you say, the reflected wave is not reflected by the source, then the reflected wave flows through the source resistor to ground and is dissipated. If the reflected wave is dissipated in the source resistor, it cannot join the forward wave. The forward wave is 25 joules/sec. The source is supplying 18.75 joules/sec. If the reflected wave is dissipated in the source, where is the other 6.25 joules/sec coming from? Is it mere coincidence that the reflected wave is 6.25 joules/sec???? Hint: You cannot eat your reflected wave and have it too. If the forward power is greater than the source power, the reflected wave is joining the forward wave, i.e. being reflected by the source. I wondered if this bit of numerology would lead to confusion, and apparently it has. Consider what happens when the source is first turned on. Immediately Pf.avg = 25 W Sometime later the forward wave reaches the load and a reflected wave is returned Pr.avg = 6.25 W Later, this wave arrives back at the generator. How does this reflected wave of 6.25 W affect the already present forward wave of 25 W when it arrives back at the generator. It affects it not one iota. The forward power remains the same, the forward voltage remains the same and the forward current remains the same. This is the meaning of no reflection. The one thing that changes is the net average power which decreases to 18.75 W. I would suggest that you start with the circuit I proposed and analyze it with the technique of your choice. What is the final Vf, Vr, Pf.avg, Pr.avg, Pg.avg and Pl.avg? Are your answers different than mine? If so, we can explore which approach is in error. What happens at the generator when the first reflection arrives back at the generator? Does Vf and Pf.avg change? Or remain the same? When Pf.avg remains the same, how can it be claimed that the reflected wave is re-reflected? ...Keith |
Derivation of Reflection Coefficient vs SWR
On Tue, 5 Feb 2008 07:36:05 -0800 (PST)
Keith Dysart wrote: On Feb 5, 8:53*am, Roger Sparks wrote: On Mon, 4 Feb 2008 12:32:39 -0800 (PST) Keith Dysart wrote: [snip] The voltage at the generator is, therefore, Vg = Vf.g + Vr.g * *= 50 /_ 0d + 25 /_ (-45d -45d) * *= 50 /_ 0d + 25 /_ -90d * *= 55.902 /_ -26.565d Vg(t) = 55.902 cos(wt - 26.565d) Whoa! *You started with 50 volts applied to the forward line, then froze the wave by finding the time phase of the wave. *Mathematically, you want to find the voltage at the generator which is the sum of the terms Vf.g and Vr.g. *The sum of those terms is 50 + 0 = 50, not *55.902 /_ -26.565d. Vr.g is the reflection of Vf from the load so it is a delayed version of Vr.l, the delay being another 45 degrees. The reflected voltage at the load is 25 /_ -45d Another 45 degrees makes it 25 /_ -90d by the time it gets back to the generator terminal. So the total voltage at the generator is Vg = Vf.g + Vr.g = 50 /_ 0d + 25 /_ (-45d -45d) = 50 /_ 0d + 25 /_ -90d = 55.902 /_ -26.565d Vg(t) = 55.902 cos(wt - 26.565d) OK, 55.902 /_ -26.565d is another way of expressing 50. I should have realized that identity. Sorry to have troubled you. [snip] Similarly for Ig and Ig(t) and Pg.avg and Pg(t). [snip] With the circuit and conditions presented, the reflected voltage and current return out of phase in time with the source voltage and current. *A standing wave condition of 3:1 would always exist throughout the system. Agreed, though it might be slightly more correct to say that there is a 3:1 VSWR on the transmission line. ...Keith -- 73, Roger, W7WKB |
Derivation of Reflection Coefficient vs SWR
Keith Dysart wrote:
How does this reflected wave of 6.25 W affect the already present forward wave of 25 W when it arrives back at the generator. It affects it not one iota. The forward power remains the same, the forward voltage remains the same and the forward current remains the same. This is the meaning of no reflection. Maybe a more drastic example will help. Rs Vg Vl +----/\/\/-----+----------------------+ | 50 ohm | | / Vs 90 degrees \ Rl 100 cos(wt) 50 ohm line / 1 ohm | \ load | | +--------------+----------------------+ gnd Current through the source: Is = 0.0392 cos(wt). The source is supplying 1.96 watts. That is all the power available to the entire system. You say the forward power is 25 watts and that none of the reflected power is reflected at the source. How can there be 25 watts of forward power when the source is supplying only 1.96 watts and none of the reflected energy is joining the forward wave? -- 73, Cecil http://www.w5dxp.com |
Derivation of Reflection Coefficient vs SWR
On Feb 5, 10:44*am, Cecil Moore wrote:
Keith Dysart wrote: So, contrary to Cecil's assertion, an analysis based on 'no reflections at the source', has not resulted in any violation of conservation of energy. This is good. Again your analysis violates the conservation of energy principle. The only way to balance your energy equation is for your source to supply 25 joules/sec. IF THE REFLECTED WAVE IS NOT REFLECTED FROM THE SOURCE, IT FLOWS THROUGH THE SOURCE RESISTOR AND IS DISSIPATED IN THE SOURCE RESISTOR. THAT REFLECTED WAVE ENERGY IS THEREFORE NOT AVAILABLE TO THE FORWARD WAVE. Not sure that shouting helps. I do not find any unbalances with the energy. See below. You cannot eat your reflected wave and have it too. The standard equation is: Psource = Pfor - Pref = Pload Yes. Indeed. And just changing to use my terminology... Pgenerator = Pfor - Pref = Pload For the example at hand... Pgenerator = 18.75 Pfor - Pref = 18.75 Pload = 18.75 And the source provides 50 W of which 31.25 is dissipated in the source resistor and 18.75 is delivered to the line (Pgenerator, above). All seems well with world and no energy is left unaccounted. But you have taken away the reflected energy and dissipated it in the source resistor. So your new equation becomes: Psource = Pfor + ???????? 18.75w *= 25w *+ ________ As your original equation above Psource = Pfor - Pref 18.75 = 25 - 6.25 I do not see any issues. When the source was first turned on, 25 J/s flowed from the generator into the line. Pfor = 25 W After the reflected wave makes it back to the generator, 25 - 6.25 - 18.75 J/s are flowing in the line. Pfor - Pref = 18.75 W And the generator output has also reduced from 25 W to 18.75 W, so all is still in balance. I am having difficulty determining where you think there is a violation of the conservation of energy principle. ...Keith PS Do not be fooled by the numerology where 25 + 6.25 gives 31.25. For the 35 degree line, the corresponding numbers are Ps = 41.449507 Prs = 22.699502 Pg = 18.75 Pf = 25 Pr = 6.25 Pl = 18.75 Pg = Pf - Pr = Pl Ps = Prs + Pg All as expected. No missing energy. |
Derivation of Reflection Coefficient vs SWR
On Feb 5, 2:41*pm, Cecil Moore wrote:
Keith Dysart wrote: How does this reflected wave of 6.25 W affect the already present forward wave of 25 W when it arrives back at the generator. It affects it not one iota. The forward power remains the same, the forward voltage remains the same and the forward current remains the same. This is the meaning of no reflection. Maybe a more drastic example will help. * * * * * * Rs * * * Vg * * * * * * * * * * Vl * * * *+----/\/\/-----+----------------------+ * * * *| * *50 ohm * * * * * * * * * * * * * | * * * *| * * * * * * * * * * * * * * * * * * / * * * Vs * * * * * * * * 90 degrees * * * * *\ * Rl * *100 cos(wt) * * * * * 50 ohm line * * * * / *1 ohm * * * *| * * * * * * * * * * * * * * * * * * \ *load * * * *| * * * * * * * * * * * * * * * * * * | * * * *+--------------+----------------------+ * * * gnd Current through the source: Is = 0.0392 cos(wt). The source is supplying 1.96 watts. That is all the power available to the entire system. You say the forward power is 25 watts and that none of the reflected power is reflected at the source. How can there be 25 watts of forward power when the source is supplying only 1.96 watts and none of the reflected energy is joining the forward wave? The answer would be clear to you if you were to complete the analysis. Please compute: Pfor Pref Vfor Vref at the point Vg, both before and after the reflected wave makes it back to the point Vg. When you find (as you will), that Pfor and Vfor do not change when the reflected wave returns, it should be difficult to assert that the reflected wave is re-reflected at Vg. If the reflected wave was re-reflected at Vg, there would necessarily be a change to Vfor and Pfor. ...Keith |
Derivation of Reflection Coefficient vs SWR
Keith Dysart wrote:
Cecil Moore wrote: How can there be 25 watts of forward power when the source is supplying only 1.96 watts and none of the reflected energy is joining the forward wave? The answer would be clear to you if you were to complete the analysis. Please don't ignore the question. How does a 1.96 watt source support a forward power of 25 watts without reflected energy joining the forward energy? -- 73, Cecil http://www.w5dxp.com |
Derivation of Reflection Coefficient vs SWR
Keith Dysart wrote:
Cecil Moore wrote: Rs Vg Pfor--25w Vl +----/\/\/-----+----------------------+ | 50 ohm ~23w--Pref | | 0.04w / 1.92w Vs 90 degrees \ Rl 100 cos(wt) 1.96w 50 ohm line / 1 ohm | \ load | | +--------------+----------------------+ gnd When you find (as you will), that Pfor and Vfor do not change when the reflected wave returns, it should be difficult to assert that the reflected wave is re-reflected at Vg. Not difficult at all. I've added the powers to the diagram above. The reflected power is ~23 watts. The power dissipated in the source resistor is ~0.04 watts. The reflected power is obviously *NOT* being dissipated in the source resistor so where is it going instead? The answer is destructive interference at the source resistor is redistributing the reflected energy back toward the load as an equal magnitude of constructive interference. I call that a reflection. The redistribution of energy due to interference is a well known and well understood phenomenon in optical physics but has been virtually ignored in the field of RF engineering. It is not a conventional reflection. It is wave cancellation in action. It is obeying the following equation: Ptot = P1 + P2 - 2*SQRT(P1*P2) where -2*SQRT(P1*P2) is the destructive interference term. If the reflected wave was re-reflected at Vg, there would necessarily be a change to Vfor and Pfor. Nope, not true. The phase angle between the voltages determines which direction the energy flows. If the above example is changed to 1/2WL instead of 1/4WL, the forward and reflected voltages and powers remain the same but the interference at the source resistor changes from destructive to constructive and the source resistor heats up. -- 73, Cecil http://www.w5dxp.com |
Derivation of Reflection Coefficient vs SWR
Cecil Moore wrote:
Keith Dysart wrote: Cecil Moore wrote: Rs Vg Pfor--25w Vl +----/\/\/-----+----------------------+ | 50 ohm ~23w--Pref | | 0.04w / 1.92w Vs 90 degrees \ Rl 100 cos(wt) 1.96w 50 ohm line / 1 ohm | \ load | | +--------------+----------------------+ gnd When you find (as you will), that Pfor and Vfor do not change when the reflected wave returns, it should be difficult to assert that the reflected wave is re-reflected at Vg. Not difficult at all. I've added the powers to the diagram above. The reflected power is ~23 watts. The power dissipated in the source resistor is ~0.04 watts. The reflected power is obviously *NOT* being dissipated in the source resistor so where is it going instead? The answer is destructive interference at the source resistor is redistributing the reflected energy back toward the load as an equal magnitude of constructive interference. I call that a reflection. The redistribution of energy due to interference is a well known and well understood phenomenon in optical physics but has been virtually ignored in the field of RF engineering. It is not a conventional reflection. It is wave cancellation in action. It is obeying the following equation: Ptot = P1 + P2 - 2*SQRT(P1*P2) where -2*SQRT(P1*P2) is the destructive interference term. Is this the total applied power or the remaining power (Prem)(which is really the reflected power), where Prem = Z0(If - Ir)^2 = Z0((If^2) +(Ir^2) - 2(If*Ir)) I think these (yours and mine) are both the same equation except that I changed the terms so that we could use it on a transmission line. Z0 is transmission line impedance, If is forward current, Ir is reflected current Just to clarify, 2*SQRT(P1*P2) = 2*SQRT((Z*I1^2)*(Z*I2^2) = 2*Z(I1*I2) The equation should apply at all locations on the transmission line. If the reflected wave was re-reflected at Vg, there would necessarily be a change to Vfor and Pfor. Nope, not true. The phase angle between the voltages determines which direction the energy flows. If the above example is changed to 1/2WL instead of 1/4WL, the forward and reflected voltages and powers remain the same but the interference at the source resistor changes from destructive to constructive and the source resistor heats up. 73, Roger, W7WKB |
Derivation of Reflection Coefficient vs SWR
Roger Sparks wrote:
The equation should apply at all locations on the transmission line. What you say is true but there is a caveat. Remember that I have previously said that interference can exist without wave cancellation. As long as Z0 remains constant up and down a transmission line, there is no forward and reflected wave interaction. They pass each other like "ships in the night". The resistor is a physical object. When the forward and reflected waves superpose at the *resistor*, there is an obvious interaction, i.e., a permanent interference. One only has to observe the power dissipated in the resistor to ascertain that it is not the same as the forward power plus the reflected power unless the E-fields of the two waves are 90 degrees apart, a condition for which zero interference exists. What is interesting is a procedure for determining the current through Rs using only powers. We have to be pretty accurate with the powers to do that. We know the forward power is 25w. The power reflection coefficient at the load is [(50-1)/(50+1)]^2 = 0.92311. That makes the reflected power from the load equal to 23.077 watts. When the forward wave and reflected wave superpose at the 50 ohm source resistor, they are 180 degrees out of phase which makes the interference term minus and therefore destructive. 25w + 23.077w - 2*SQRT(25w*23.077w) = 0.03845w That's the dissipation in the 50 ohm source resistor. So the RMS current is SQRT(0.03845w/50ohm)= 0.02773a Ig(t) = 1.414(0.02773)cos(wt) = 0.039216 cos(wt) And that is, indeed, the current through the 50 ohm source resistor, Rs, using only an energy analysis. All energy, except 0.03845w, is "redistributed", i.e. reflected back toward the load. This is all explained in my energy analysis article at: http://www.w5dxp.com/energy.htm -- 73, Cecil http://www.w5dxp.com |
Derivation of Reflection Coefficient vs SWR
"Cecil Moore" wrote in message
. net... Roger Sparks wrote: The equation should apply at all locations on the transmission line. What you say is true but there is a caveat. Remember that I have previously said that interference can exist without wave cancellation. As long as Z0 remains constant up and down a transmission line, there is no forward and reflected wave interaction. They pass each other like "ships in the night". The resistor is a physical object. When the forward and reflected waves superpose at the *resistor*, there is an obvious interaction, i.e., a permanent interference. One only has to observe the power dissipated in the resistor to ascertain that it is not the same as the forward power plus the reflected power unless the E-fields of the two waves are 90 degrees apart, a condition for which zero interference exists. What is interesting is a procedure for determining the current through Rs using only powers. We have to be pretty accurate with the powers to do that. We know the forward power is 25w. The power reflection coefficient at the load is [(50-1)/(50+1)]^2 = 0.92311. That makes the reflected power from the load equal to 23.077 watts. When the forward wave and reflected wave superpose at the 50 ohm source resistor, they are 180 degrees out of phase which makes the interference term minus and therefore destructive. 25w + 23.077w - 2*SQRT(25w*23.077w) = 0.03845w That's the dissipation in the 50 ohm source resistor. So the RMS current is SQRT(0.03845w/50ohm)= 0.02773a Ig(t) = 1.414(0.02773)cos(wt) = 0.039216 cos(wt) And that is, indeed, the current through the 50 ohm source resistor, Rs, using only an energy analysis. All energy, except 0.03845w, is "redistributed", i.e. reflected back toward the load. This is all explained in my energy analysis article at: http://www.w5dxp.com/energy.htm -- 73, Cecil http://www.w5dxp.com I disagree. If the current through the 50 ohm source resistor is 0.039216, then the power in the 50 ohm source resistor cannot be 0.03845w. Namely because 0.039216 * 0.039216 * 50 = 0.076895w (eye-squared-are, matey). Either your power is wrong or your current is wrong. My own calculations show that your current is correct. Therefore, your energy analysis appears to be in error. John |
Derivation of Reflection Coefficient vs SWR
John KD5YI wrote:
I disagree. If the current through the 50 ohm source resistor is 0.039216, then the power in the 50 ohm source resistor cannot be 0.03845w. Namely because 0.039216 * 0.039216 * 50 = 0.076895w (eye-squared-are, matey). Either your power is wrong or your current is wrong. My own calculations show that your current is correct. Therefore, your energy analysis appears to be in error. You seem to have forgotten that since 0.039216 is the maximum value of current you need to divide the 0.076895w by two. 0.076895w/2 = 0.03845 watts If we used the RMS value of the current, i.e. 0.039216/1.414 equals 0.027734a, then 50(0.027734)^2 = 0.03845 watts and all is well. -- 73, Cecil http://www.w5dxp.com |
Derivation of Reflection Coefficient vs SWR
On Feb 6, 8:02*am, Cecil Moore wrote:
Keith Dysart wrote: Cecil Moore wrote: * * * * * * Rs * * * Vg * Pfor--25w * * * * Vl * * * *+----/\/\/-----+----------------------+ * * * *| * *50 ohm * * * ~23w--Pref * * * * | * * * *| * *0.04w * * * * * * * * * * * * * */ *1.92w * * * Vs * * * * * * * * 90 degrees * * * * *\ * Rl * *100 cos(wt) 1.96w * * 50 ohm line * * * * / *1 ohm * * * *| * * * * * * * * * * * * * * * * * * \ *load * * * *| * * * * * * * * * * * * * * * * * * | * * * *+--------------+----------------------+ * * * gnd When you find (as you will), that Pfor and Vfor do not change when the reflected wave returns, it should be difficult to assert that the reflected wave is re-reflected at Vg. Not difficult at all. I've added the powers to the diagram above. The reflected power is ~23 watts. The power dissipated in the source resistor is ~0.04 watts. The reflected power is obviously *NOT* being dissipated in the source resistor so where is it going instead? The answer is destructive interference at the source resistor is redistributing the reflected energy back toward the load as an equal magnitude of constructive interference. I call that a reflection. When we analyze this circuit we find that there is no voltage re-reflection when the wave gets back to the generator. This is clear because Vf does not change, which it would have to do if any of Vr was re-reflected. And yet it appears that you are claiming that power is reflected at the generator. How can power be reflected if voltage is not? You may find the Excel spreadsheet on this page http://keith.dysart.googlepages.com/...oad,reflection interesting. It computes the various results for the circuit we have been discussing. Input Vs, Rs, Rl and line length and it will compute the various voltages, currents and powers. After entering the circuit parameters, click "First". The circuit conditions at the end of the first round trip will be computed. Click "Next" to have any re-reflection included into the forward conditions for the next round trip. When Rs is 50 ohms (i.e. it matches the line impedance), the circuit conditions settle to their final state immediately, as would be expected when there is no reflection at the generator. Change Rs to a value other than 50 and it takes many clicks of "Next" before the conditions settle. At each click, Vf changes as some of Vr is re-reflected and added to Vf. ...Keith |
Derivation of Reflection Coefficient vs SWR
"Cecil Moore" wrote in message ... John KD5YI wrote: I disagree. If the current through the 50 ohm source resistor is 0.039216, then the power in the 50 ohm source resistor cannot be 0.03845w. Namely because 0.039216 * 0.039216 * 50 = 0.076895w (eye-squared-are, matey). Either your power is wrong or your current is wrong. My own calculations show that your current is correct. Therefore, your energy analysis appears to be in error. You seem to have forgotten that since 0.039216 is the maximum value of current you need to divide the 0.076895w by two. Yes, I forgot to use the RMS value of the source. John |
Derivation of Reflection Coefficient vs SWR
Keith Dysart wrote:
When we analyze this circuit we find that there is no voltage re-reflection when the wave gets back to the generator. This is clear because Vf does not change, which it would have to do if any of Vr was re-reflected. Nope, Vf doesn't have to change for there to be a reflection. Looking at what happens to the power dissipation in the source resistor, Rs, when the reflected wave arrives, we see that the energy being supplied by the source drops by 99.85%. Most of the energy in the forward wave is supplied by the reflected wave, starting at the time the reflected wave arrives and causes destructive interference. And yet it appears that you are claiming that power is reflected at the generator. How can power be reflected if voltage is not? To be technically correct, reflected energy is redistributed back toward the load during the process of destructive interference. The conditions before the reflected wave arrives and after the reflected wave arrives are extremely different. Before the reflected wave arrives, the source resistor, Rs, is dissipating 25 watts. After the reflected wave arrives, the source resistor, Rs, is dissipating 0.03845 watts. Clearly, something drastic has happened and that is: 99.85% of the forward energy originally supplied by the source has been replaced with reflected energy being redistributed back toward the load. Because of destructive interference, reflected energy *never* flows through the source resistor, Rs, and is instead redistributed back toward the load. Nothing else is possible since the source is supplying only 1.9608 watts during steady-state. 92.3% of the forward power is not being supplied by the source during steady-state. The energy incident upon a point must equal the energy exiting the point. The energy incident upon the generator terminals is 1.92234 joules/sec from the source and 23.0777 joules/sec from the reflected wave. The energy exiting that point is 25 joules/sec. The reflected wave energy obviously reverses direction and joins the forward wave and that is what we call a "reflection". -- 73, Cecil http://www.w5dxp.com |
Derivation of Reflection Coefficient vs SWR
On Feb 8, 9:15*am, Cecil Moore wrote:
Keith Dysart wrote: When we analyze this circuit we find that there is no voltage re-reflection when the wave gets back to the generator. This is clear because Vf does not change, which it would have to do if any of Vr was re-reflected. Nope, Vf doesn't have to change for there to be a reflection. Looking at what happens to the power dissipation in the source resistor, Rs, when the reflected wave arrives, we see that the energy being supplied by the source drops by 99.85%. Most of the energy in the forward wave is supplied by the reflected wave, starting at the time the reflected wave arrives and causes destructive interference. And yet it appears that you are claiming that power is reflected at the generator. How can power be reflected if voltage is not? To be technically correct, reflected energy is redistributed back toward the load during the process of destructive interference. The conditions before the reflected wave arrives and after the reflected wave arrives are extremely different. Before the reflected wave arrives, the source resistor, Rs, is dissipating 25 watts. After the reflected wave arrives, the source resistor, Rs, is dissipating 0.03845 watts. Clearly, something drastic has happened and that is: 99.85% of the forward energy originally supplied by the source has been replaced with reflected energy being redistributed back toward the load. Because of destructive interference, reflected energy *never* flows through the source resistor, Rs, and is instead redistributed back toward the load. Nothing else is possible since the source is supplying only 1.9608 watts during steady-state. 92.3% of the forward power is not being supplied by the source during steady-state. The energy incident upon a point must equal the energy exiting the point. The energy incident upon the generator terminals is 1.92234 joules/sec from the source and 23.0777 joules/sec from the reflected wave. The energy exiting that point is 25 joules/sec. The reflected wave energy obviously reverses direction and joins the forward wave and that is what we call a "reflection". Are you sure? I thought a reflection was something that occurred at an impedance discontinuity and the magnitude of the voltage reflection was defined by Vr = Vincident * ReflectionCoefficient = Vincident * (Z2-Z1)/(Z2+Z1) and that the reflected voltage then added to any wave already travelling in that direction. But you are claiming that power can be reflected when voltage is not. I have never encountered this claim before. Are you sure? ...Keith |
Derivation of Reflection Coefficient vs SWR
Keith Dysart wrote:
Are you sure? I thought a reflection was something that occurred at an impedance discontinuity and the magnitude of the voltage reflection was defined by Vr = Vincident * ReflectionCoefficient = Vincident * (Z2-Z1)/(Z2+Z1) That's true for normal reflections which involve only one wave. Wave cancellation is a different kind of energy reflection involving two waves. The energy flow is canceled in one direction and therefore flows in the other direction. In optics, it is known as a redistribution of energy in directions that allow constructive interference. In a transmission line, there are only two possible directions so any redistribution of energy due to destructive interference can be considered to be a reflection in the opposite direction, the only direction available to constructive interference. and that the reflected voltage then added to any wave already travelling in that direction. True for a single wave reflection. For two interacting waves, the voltage in one of the waves can simply replace the voltage in the other wave. In our example, the reflected voltage simply replaces the source voltage component. But you are claiming that power can be reflected when voltage is not. I have never encountered this claim before. When the reflected wave arrives, it cancels most of the existing forward wave from the source. The reflected voltage exactly equals the canceled source voltage in our example because the source resistance is the same as the Z0 of the line. Are you sure? It is obvious that reflected energy never flows in the source resistor so it must go in the only other direction possible. Yes, I am sure. The conservation of energy principle will allow nothing else. -- 73, Cecil http://www.w5dxp.com |
Derivation of Reflection Coefficient vs SWR
Keith Dysart wrote:
Are you sure? Rs Vg Pfor--25w Vl +----/\/\/-----+----------------------+ | 50 ohm 23.08w--Pref | | 48.08w / 1.92w Vs 45 degrees \ Rl 100 cos(wt) 50 ohm line / 1 ohm 50w \ load | | +--------------+----------------------+ gnd As a matter of interest, let's return to the 45 degree line, the one to which I objected previously. The forward power and reflected power are the same as in the previous example but now the dissipation in Rs is equal to the sum of the forward power and reflected power. (It would be nice if all cases were as straight forward as this special case.) This is indeed the one special case where everything you have been saying is true. There is no redistribution of energy because there is no interference. There is no interference because at Vg, Vfor and Vref are 90 degrees out of phase. These concepts are covered in my magazine article at: http://www.w5dxp.com/energy.htm -- 73, Cecil http://www.w5dxp.com |
All times are GMT +1. The time now is 03:31 PM. |
|
Powered by vBulletin® Copyright ©2000 - 2025, Jelsoft Enterprises Ltd.
RadioBanter.com