Home |
Search |
Today's Posts |
|
#1
![]() |
|||
|
|||
![]()
Owen Duffy wrote:
An extension of that thinking is in the proposition that I have seen that a Bird 43 cannot give valid readings unless there is at least a quarter wave of 50 ohm line on each side of itself. In this case, the magnitude of significantly affected line seems to be 25%, someone else's is 2%, can they both be correct? I think if you will recheck that posting you will find the assertion was that a Bird 43 cannot give valid readings by sampling at a point. The line must be at least 1/4WL, and preferably 1/2WL, so that voltage maximums and minimums will exist and can be measured. And that 2% of a wavelength is from my faulty memory. I'll try to Google and find the exact quotation. -- 73, Cecil http://www.qsl.net/w5dxp |
#2
![]() |
|||
|
|||
![]() "Cecil Moore" wrote in message t... Owen Duffy wrote: An extension of that thinking is in the proposition that I have seen that a Bird 43 cannot give valid readings unless there is at least a quarter wave of 50 ohm line on each side of itself. In this case, the magnitude of significantly affected line seems to be 25%, someone else's is 2%, can they both be correct? I think if you will recheck that posting you will find the assertion was that a Bird 43 cannot give valid readings by sampling at a point. The line must be at least 1/4WL, and preferably 1/2WL, so that voltage maximums and minimums will exist and can be measured. And that 2% of a wavelength is from my faulty memory. I'll try to Google and find the exact quotation. -- 73, Cecil http://www.qsl.net/w5dxp i want to see a quote from a manufacturer's or good laboratory manual for that 1/4 or 1/2 wave thing on the bird also. |
#3
![]() |
|||
|
|||
![]()
Dave wrote:
"Cecil Moore" wrote in message et... I think if you will recheck that posting you will find the assertion was that a Bird 43 cannot give valid readings by sampling at a point. The line must be at least 1/4WL, and preferably 1/2WL, so that voltage maximums and minimums will exist and can be measured. i want to see a quote from a manufacturer's or good laboratory manual for that 1/4 or 1/2 wave thing on the bird also. Cecil was quoting someone else there, and is completely innocent :-) Here's how the Bird 43 measures VSWR. It contains a pair of needle-fine voltage probes, powered by small explosive charges. When coax is connected at either side, it fires those probes out into the coax until it finds a voltage maximum and a voltage minimum. Then it computes the Voltage Standing Wave Ratio and a recoil mechanism reels the probes back in. It's so slick, it all happens before you even know it. Warning: when handling a Bird 43, keep all sensitive parts more than 1/2WL from those sockets! An alternative possibility is that the Bird 43 does give valid readings by sampling at the point where it physically is. -- 73 from Ian G/GM3SEK 'In Practice' columnist for RadCom (RSGB) http://www.ifwtech.co.uk/g3sek |
#4
![]() |
|||
|
|||
![]()
On Sat, 8 Oct 2005 14:20:46 -0000, "Dave" wrote:
i want to see a quote from a manufacturer's or good laboratory manual for that 1/4 or 1/2 wave thing on the bird also. Hi Dave, Don't hold your breath waiting for that Baloney sandwich to be made. 73's Richard Clark, KB7QHC |
#5
![]() |
|||
|
|||
![]()
On Sat, 08 Oct 2005 14:13:02 GMT, Cecil Moore wrote:
Owen Duffy wrote: An extension of that thinking is in the proposition that I have seen that a Bird 43 cannot give valid readings unless there is at least a quarter wave of 50 ohm line on each side of itself. In this case, the magnitude of significantly affected line seems to be 25%, someone else's is 2%, can they both be correct? I think if you will recheck that posting you will find the assertion Cecil, it is someone else who has on a number of occasions suggested the quarter wave thing in email correspondence, and here in postings. My suggestion is that the sampler inside a Bird 43 coupler section is sufficiently far inside the 50 ohm coupler line to provide measurements within the instrument's stated accuracy of what is happening within the 50 ohm coupler, irrespective of whether, for instance, a 75 ohm line is attached to the coupler on the load side. The measurements of what is happening within the Bird 43 coupler could then be used to model what is happening on the adjacent line, having regard for any Zo changes, loss, length etc. Owen -- |
#6
![]() |
|||
|
|||
![]()
Owen Duffy wrote:
Cecil, it is someone else who has on a number of occasions suggested the quarter wave thing in email correspondence, and here in postings? Yep, it's not me, it's Reg. I have defended the Bird wattmeter design. Reg sez one needs at least 1/4WL and preferably 1/2WL in order to accurately ascertain the "real" SWR. -- 73, Cecil http://www.qsl.net/w5dxp |
#7
![]() |
|||
|
|||
![]()
Cecil Moore wrote:
Owen Duffy wrote: Cecil, do you have some quantitative explanation / support for this? Nope, but there were no disagreeing postings. I am not asking whether or not field conditions (and V/I on the conductors) immediate to the discontinuity are not Zo of either of the lines, just where has the 2% of a wavelength come from? As I remember it came from the spacing between conductors Vs wavelength. The spacing between conductors is about 0.1 inches for RG-58. How many times that value would you think it would take for a transmission line to force its Z0 upon the signals? At 10 MHz, 2% of a wavelength (24 inches) is about 250 times the spacing between conductors. Maybe the electromagnetics people have a useful way to visualize it... Deep inside the coax, the electric field lines between the inner and outer of the coax are exactly at right-angles to the main axis. Where that is exactly true, you have a pure TE10 mode so it's also valid to assume that V/I is exactly equal to Zo. Very close to the end of the coax, the electric field lines from the center conductor start to reach out and connect with whatever is out there beyond the end of the shield. Then you no longer have pure TE10 and can no longer assume that V/I=Zo. Coming at it from the other direction, the question would be: how far into the coax must you go before the field lines become accurately at right-angles? We can be sure that the field lines won't suddenly snap from being divergent to being accurately at right-angles, so what we're really asking is: how far before the field lines are near-enough at right angles to make V/I=Zo a good engineering approximation? Intuitively, the diverging field lines only seem likely to occur within a few diameters of the end of the shield. Field lines always connect with highly conducting surfaces at right-angles, and they won't like to be sharply bent to run along the axis of the coax. In other words, the effect would seem to be mainly a function of shield diameter D. Again intuitively, I can't see where wavelength would come into it, unless D itself is a significant fraction of the wavelength (which is normally never true, and even microwave engineers try to avoid it). Following this picture of diverging field lines, there should also be a secondary effect depending on how the inner and shield of the coax are connected to the circuit outside. All of this suggests that it's impossible to give a single answer that would be valid for all cases (unless you choose a number that's so big, it can't fail to be correct... like "120 radials" :-) However, none of this speculation is of any practical consequence. All practical experience indicates that if a line is so short that V/I is not quite equal to Zo, the impedance transformation along that line will be so small that the effect of any Zo error is lost in the noise. -- 73 from Ian G/GM3SEK 'In Practice' columnist for RadCom (RSGB) http://www.ifwtech.co.uk/g3sek |
#8
![]() |
|||
|
|||
![]()
In all transmission lines, including coax, there are various shapes of
transverse electric and magnetic fields that can exist for the particular transmission line geometry. For each shape, the "propagation constant" can be calculated. Many transmission lines (at lower frequencies) have only one shape with propagates with low attenuation. The other shapes can exist, but their "propagation constant" is such that they decrease exponentially with distance. The propagation constant for each shape can be calculated, and is often a function of frequency. When there is a discontinuity in a line, other shapes than the usual one must exist at the point of the discontinuity. (for example, in order to ensure that the transverse electric field is zero the surface of a conducting shape that is part of the line discontinuity). Thus, these other shapes exist (at a certain amplitude) at the point of discontinuity. The amplitude of the other shapes decreases exponentially at distances away from the discontinuity. The rate of the fall-off will depend on the particular shape, according to its propagation constant. Thus, the distance needed to be back to regular old TEM propagation in a coax will depend on the particular discontinuity, and the propagation constants of the "higher order modes" or different field shapes, of a coax line. I have seen examples worked out for waveguide propagation and a step change in waveguide width. There are probably worked examples of coax discontinuities in the literature, also. These non-propagating shapes are usually called " evanescent modes", and this would be a good search term to use to investigate this further. Cliff Curry "Ian White G/GM3SEK" wrote in message ... Cecil Moore wrote: Owen Duffy wrote: Cecil, do you have some quantitative explanation / support for this? Nope, but there were no disagreeing postings. I am not asking whether or not field conditions (and V/I on the conductors) immediate to the discontinuity are not Zo of either of the lines, just where has the 2% of a wavelength come from? As I remember it came from the spacing between conductors Vs wavelength. The spacing between conductors is about 0.1 inches for RG-58. How many times that value would you think it would take for a transmission line to force its Z0 upon the signals? At 10 MHz, 2% of a wavelength (24 inches) is about 250 times the spacing between conductors. Maybe the electromagnetics people have a useful way to visualize it... Deep inside the coax, the electric field lines between the inner and outer of the coax are exactly at right-angles to the main axis. Where that is exactly true, you have a pure TE10 mode so it's also valid to assume that V/I is exactly equal to Zo. Very close to the end of the coax, the electric field lines from the center conductor start to reach out and connect with whatever is out there beyond the end of the shield. Then you no longer have pure TE10 and can no longer assume that V/I=Zo. Coming at it from the other direction, the question would be: how far into the coax must you go before the field lines become accurately at right-angles? We can be sure that the field lines won't suddenly snap from being divergent to being accurately at right-angles, so what we're really asking is: how far before the field lines are near-enough at right angles to make V/I=Zo a good engineering approximation? Intuitively, the diverging field lines only seem likely to occur within a few diameters of the end of the shield. Field lines always connect with highly conducting surfaces at right-angles, and they won't like to be sharply bent to run along the axis of the coax. In other words, the effect would seem to be mainly a function of shield diameter D. Again intuitively, I can't see where wavelength would come into it, unless D itself is a significant fraction of the wavelength (which is normally never true, and even microwave engineers try to avoid it). Following this picture of diverging field lines, there should also be a secondary effect depending on how the inner and shield of the coax are connected to the circuit outside. All of this suggests that it's impossible to give a single answer that would be valid for all cases (unless you choose a number that's so big, it can't fail to be correct... like "120 radials" :-) However, none of this speculation is of any practical consequence. All practical experience indicates that if a line is so short that V/I is not quite equal to Zo, the impedance transformation along that line will be so small that the effect of any Zo error is lost in the noise. -- 73 from Ian G/GM3SEK 'In Practice' columnist for RadCom (RSGB) http://www.ifwtech.co.uk/g3sek |
#9
![]() |
|||
|
|||
![]()
Cliff Curry wrote:
In all transmission lines, including coax, there are various shapes of transverse electric and magnetic fields that can exist for the particular transmission line geometry. For each shape, the "propagation constant" can be calculated. Many transmission lines (at lower frequencies) have only one shape with propagates with low attenuation. The other shapes can exist, but their "propagation constant" is such that they decrease exponentially with distance. The propagation constant for each shape can be calculated, and is often a function of frequency. When there is a discontinuity in a line, other shapes than the usual one must exist at the point of the discontinuity. (for example, in order to ensure that the transverse electric field is zero the surface of a conducting shape that is part of the line discontinuity). Thus, these other shapes exist (at a certain amplitude) at the point of discontinuity. The amplitude of the other shapes decreases exponentially at distances away from the discontinuity. The rate of the fall-off will depend on the particular shape, according to its propagation constant. Thus, the distance needed to be back to regular old TEM propagation in a coax will depend on the particular discontinuity, and the propagation constants of the "higher order modes" or different field shapes, of a coax line. I have seen examples worked out for waveguide propagation and a step change in waveguide width. There are probably worked examples of coax discontinuities in the literature, also. These non-propagating shapes are usually called " evanescent modes", and this would be a good search term to use to investigate this further. All agreed. Along with the math that Cecil has retrieved and quoted again, everything points towards the distance in question being a function of coax diameter only; and not wavelength. -- 73 from Ian G/GM3SEK 'In Practice' columnist for RadCom (RSGB) http://www.ifwtech.co.uk/g3sek |
#10
![]() |
|||
|
|||
![]()
Ian White G/GM3SEK wrote:
All agreed. Along with the math that Cecil has retrieved and quoted again, everything points towards the distance in question being a function of coax diameter only; and not wavelength. Please forgive my previous senior moment. It was ~2% of a wavelength at 10 MHz for RG-213. It appears that one foot of coax on each side of a Bird wattmeter is enough to establish Z0 at 50 ohms which forces Vfor/Ifor=Vref/Iref=50, the necessary Bird boundary conditions. -- 73, Cecil http://www.qsl.net/w5dxp |
Reply |
|
Thread Tools | Search this Thread |
Display Modes | |
|
|
![]() |
||||
Thread | Forum | |||
S/N ratio question - have I got this right? | Antenna | |||
The "TRICK" to TV 'type' Coax Cable [Shielded] SWL Loop Antennas {RHF} | Antenna | |||
The "TRICK" to TV 'type' Coax Cable [Shielded] SWL Loop Antennas {RHF} | Shortwave | |||
speaker impedance transformation | Homebrew | |||
calculate front/back ratio of Yagi antenna? | Antenna |