In message , Frank Dinger
writes
I have a number of transformers and would like to experiement using then

at
a higher frequency....let say 500 hz and / or higher.....

Would they still work?...I am assuming so...

Would they run cooler?....

Could anyone foresee any negative effects?....

=========================
Running transformers on a higher freq is fine provided the core can manage
the higher freq.

During the valve era ,aeronautical radio equipment ran on 400 Hz resulting
in smaller and hence lower weight transformers.

However running power supply transformers at an AC frequency lower than the
one they are designed for might cause the laminated core to overheat.

In practice : 50 Hz transformers meant for use in Europe and elsewhere can
be readily used in the US and Canada.
However transformers designed for 60 Hz having 'marginal cores' could
overheat when used on a 50 Hz supply.
So equipment with 'wallwarts' purchased in the US ,(apart from being
suitable for 117 V only ) I never use on a 50 Hz supply system.

Nowadays with much equipment having a switch mode power supply , the
frequency / voltage problem no longer exists.

Frank GM0CSZ / KN6WH



Yes, you can sometimes have serious trouble on 50Hz when the equipment
was designed in a 60Hz area. The problem is simply not enough inductance
in the transformer for the lower frequency (even though the difference
is small).

I recall two examples from my work (in the cable TV industry):
1. Hundreds of 50 to 600MHz outdoor repeater amplifiers, line powered
(via the coax) at 60VAC. Took far too much current, and all the
transformers had to be replaced.
2. Piece of rack equipment. 115V input, multiple output windings. We
simply provided a 240-115V step down when we installed it. No problems.
One day, new unit, fuse pops after a few seconds. Mains transformer same
part number, but different supplier, also slightly fewer laminations.
Current went up from 0.2A to 3A. Not an easy fix.

There can also be a problem with switch mode power supplies, but the
problem is not the frequency. It is the higher inrush current when you
switch on. Again, cable TV equipment, had 0.25A mains fuse. Regularly
popped fuse on switch-on. Took a slow-blow 1A to stop it, although the
steady-state current was only 80mA.

I'm not pro-American, but I often think that the world might have been a
simpler place if we had all used 115VAC, 60Hz, 525-line TV etc....

Ian.

--

  #2   Report Post  
Old January 17th 04, 12:36 AM
Avery Fineman
 
Posts: n/a
Default

In article le.rogers.com,
"larry" writes:

Way back, when I was 7 or 8 years old, (I am 55 now), my dad got me an
electric train set....During that Christmas we were at my Grandparents place
and they were on 25 hz power....At home we were on 60 hz power...

We had to be at home for me to try out my new train set.

What has that got to do with this question?...

This....

I have a number of transformers and would like to experiement using then at
a higher frequency....let say 500 hz and / or higher.....

Would they still work?...I am assuming so...


Should not be a problem. Designed for 25 Hz operation, they have
a lot more iron in the core than those for 50/60 Hz. That means
they are HEAVY. [it's a mechanical mounting problem only]

Would they run cooler?....


Not any more than audio amplifier power output transformers at
the same wattage.

Could anyone foresee any negative effects?....


Other than physical mounting places having to be much more
sturdy, no problems at all.

Aerospace electronics went to 400 Hz (and higher "wild" supply
frequencies) some time ago to save WEIGHT. For the same
power handling capability, the core size could be smaller for a
given core flux desnity in comparison to 60 Hz.

You WILL get heating and inordinate core losses and loss of
efficiency of power transfer in trying to use a 400 Hz transformer
at 60 Hz.

You will NOT have any of those problems on getting a lower-
frequency transformer to work at a higher frequency.

For common transformer iron laminations, the upper end of
frequency response...where all the effects others were talking about,
would be above, perhaps, 5 KHz to 10 KHz. Those other effects
would only begin to show up at that limit frequency, getting worse
at higher frequencies.

In the old vacuum tube "Hi-Fi" music amplifers, output transformers
needed a BIG core cross section to reach down to 30 Hz. The
upper end of response was determined primarily by the distributed
capacitance of the winding with the most turns, secondarily by the
iron alloy of the core. Mutual inductance effects didn't much come
into play - regardless of what some instructors talked about in
classes to illustrate "points" about mutual inductance. :-)

Len Anderson
retired (from regular hours) electronic engineer person
Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Wanted: Power Supply for TR-4C KA9S-3_Jeff Boatanchors 0 December 8th 04 09:31 PM
Wanted: Power Supply for TR-4C KA9S-3_Jeff Equipment 0 December 8th 04 09:31 PM
More free: Power transformers Tom Bruhns Boatanchors 0 June 24th 04 06:19 AM
Derivation of the Reflection Coefficient? Dr. Slick Antenna 104 September 6th 03 02:27 AM


All times are GMT +1. The time now is 08:35 AM.

Powered by vBulletin® Copyright ©2000 - 2025, Jelsoft Enterprises Ltd.
Copyright ©2004-2025 RadioBanter.
The comments are property of their posters.
 

About Us

"It's about Radio"

 

Copyright © 2017