![]() |
The Rest of the Story
Roger Sparks wrote:
How can we justify calling the +/- 2*SQRT[Pf.g(t)*Pr.g(t) term the "interference term"? Page 388, "Optics", by Eugene Hecht, 4th edition: "The interference term becomes I12 = 2*SQRT(I1*I2)cos(A)" where 'I' is the Irradiance (power density)[NOT Current] Later Hecht says +2*SQRT(I1*I2) is the total constructive interference term and -2*SQRT(I1*I2) is the total destructive interference term. Chapter 9 is titled "Interference" - recommended reading. Am I correct in assuming that this equation describes the instantaneous power delivered to Rs? Yes, if Tom, K7ITM, is correct about the equation working for instantaneous power densities, not just for average power densities as I had first assumed. Let's say the instantaneous forward voltage dropped across the source resistor is +50 volts and the instantaneous reflected voltage across the source resistor is -30 volts. The source resistor is 50 ohms. Pf.rs(t) = (+50v)^2/50 = 50w Pr.rs(t) = (-30v)^2/50 = 18w Prs(t) = Pf.rs(t) + Pr.rs(t) - interference Prs(t) = 50w + 18w - 2*SQRT(50*18) = 8 watts If Tom is correct, that should be the actual dissipation in the source resistor at that time which includes 60 watts of destructive interference that will be dissipated 90 degrees later when 2*SQRT(50*18) = +60 watts. -- 73, Cecil http://www.w5dxp.com |
The Rest of the Story
Keith Dysart wrote:
So yes, the phrase "conservation of power" is appropriately descriptive and follows from conservation of energy. You have a contradiction built into your concepts. You have argued that the instantaneous power dissipated in the source resistor is not equal to the instantaneous forward power component plus the instantaneous reflected power because power must be conserved at each instant of time. That is simply not true. I'm telling that energy must be conserved at each instant of time but power does not have to be conserved at each instant of time. Energy can obviously be stored in a battery or network reactance for dissipation later in time. Do you require that the power used to charge a battery be instantaneously dissipated in the battery? Of course not! That's true for a dummy load but NOT for a battery. There is no reason to require dissipation of power at each instant of time to balance. Since energy can be stored, there is no such thing as conservation of instantaneous power, only of instantaneous energy. Where is "cos(theta)" in this? And what "theta" is to be used? How many times do I have to explain this? For instantaneous values of voltage, if the sign of the two interfering voltages are the same, theta is zero degrees and the cosine of theta is +1.0. If the sign of the two interfering voltages are opposite, theta is 180 degrees and the cosine of theta is -1.0. Is it the same theta that was used to conclude that this was a "no interference" example? See "A Simple Voltage Source - No Interference" at http://www.w5dxp.com/intfr.htm That theta is the phase angle of the phasor. If you would switch over to phasor notation for your values of instantaneous voltages, it might make things clearer for you. You have been dealing only with real part of the phasors which limits theta to either zero or 180 degrees. So the plus/minus in the equation aboves means that for part of the cycle we should add and part of the cycle we should subtract. This equation is ambiguous and is therefore incomplete since it does not tell us when we should add and when we should subtract. I have told you about five times now. If the sign of the two interfering voltages are the same, the interference term has a positive sign (constructive). If the sign of the two interfering voltages are opposite, the interference term has a negative sign (destructive). Instead of me having to keep posting this over and over how about you keep reading it over and over until you understand it? Could you provide a mathematically precise description of when we should do each? See above. If we deal with phasors, theta is the phase angle between the two interfering voltages. If we deal only with real values, theta is limited to either zero (cosine = +1.0) or 180 degrees (cosine = -1.0). Where is this destructive interference energy stored while waiting to be dissipated constructively later? In our 45 degree shorted stub example, it is stored in the equivalent inductive reactance of the stub. For each instant in which destructive interference energy is stored, there is an instant in time 90 degrees later when that same energy is dissipated as constructive interference power in the source resistor. That's why 100% of the average reflected power is dissipated in the source resistor for these special cases of zero average interference. -- 73, Cecil http://www.w5dxp.com |
The Rest of the Story
Keith Dysart wrote:
Cecil Moore wrote: We are not discussing matched systems. If the total RMS voltage differs from the RMS forward voltage, then Vr is NOT zero. True for this example. But it is generally unwise to pick names or descriptions that will have to change when the component values are changed. Picking nits won't change the laws of physics. -- 73, Cecil http://www.w5dxp.com |
The Rest of the Story
On Sun, 23 Mar 2008 09:03:31 -0500
Cecil Moore wrote: Roger Sparks wrote: How can we justify calling the +/- 2*SQRT[Pf.g(t)*Pr.g(t) term the "interference term"? Page 388, "Optics", by Eugene Hecht, 4th edition: "The interference term becomes I12 = 2*SQRT(I1*I2)cos(A)" where 'I' is the Irradiance (power density)[NOT Current] Later Hecht says +2*SQRT(I1*I2) is the total constructive interference term and -2*SQRT(I1*I2) is the total destructive interference term. Chapter 9 is titled "Interference" - recommended reading. Am I correct in assuming that this equation describes the instantaneous power delivered to Rs? Yes, if Tom, K7ITM, is correct about the equation working for instantaneous power densities, not just for average power densities as I had first assumed. Let's say the instantaneous forward voltage dropped across the source resistor is +50 volts and the instantaneous reflected voltage across the source resistor is -30 volts. The source resistor is 50 ohms. Pf.rs(t) = (+50v)^2/50 = 50w Pr.rs(t) = (-30v)^2/50 = 18w Prs(t) = Pf.rs(t) + Pr.rs(t) - interference Prs(t) = 50w + 18w - 2*SQRT(50*18) = 8 watts If Tom is correct, that should be the actual dissipation in the source resistor at that time which includes 60 watts of destructive interference that will be dissipated 90 degrees later when 2*SQRT(50*18) = +60 watts. -- 73, Cecil http://www.w5dxp.com Thanks for your thoughtful reply. TanH(30/50) = 30.96 degrees. This takes us back to the 12.5 ohm load example. Is it possible that in your example here, the reflected voltage acts in series with Rs but arrives 90 degrees out of phase with the forward voltage? If so, then Vrs = sqrt(50^2 + 30^2) (the reflected voltage should ADD to the source voltage) = sqrt(3400) = 58.31v The power to Rs would be Prs = (V^2)/50 = 3400/50 = 68w We previously found that 32w was used at the 12.5 ohm load, so 32 + 68 = 100w. The entire output from the source is accounted for. If this is the case, we have here an example of constructive interference, and complete accounting for the power. You might wonder why I would consider this alternative. If the destructive interference included a 90 degree delay, how would I know whether the 30v was the delayed voltage or exactly in phase with the source? It must be delayed by 90 degrees because the forward voltage is always 90 degrees ahead of the reflected wave (in 45 degree line length example). Your example certainly works as written, but it also introduces a dilemma. Where is the power stored for 90 degrees? To answer that question, I see two possiblities: The source voltage causes a reflection so the 60w is stored as an additional reflected wave on the transmission line. Or second, the 60w is stored in the source. -- 73, Roger, W7WKB |
The Rest of the Story
On Sun, 23 Mar 2008 05:10:26 -0700, Roger Sparks
wrote: Zo =3D 1/(C*Vel) where C is the capacitance of the line per unit distance and Vel is the vel= ocity of the wave. This second solution for Zo demonstrates the power storage capabilities of = the transmission line over time. What is old is new again. Hasn't this "formula" been put in the ground once before? For one, what is velocity but something that has to be computed first only to find us refilling all the terms back into this shortcut? For two, "power storage capabilities... over time?" Apparently the stake missed the heart of this one. = A0 =A 0 = A0 = A 0 Vs = A 0 =A 0 = A0 = A0 =A 0 = A0 = A 0 73's Richard Clark, KB7QHC |
The Rest of the Story
Roger Sparks wrote:
(the reflected voltage should ADD to the source voltage) If you graph the two voltages you will find that half the time the reflected voltage adds to the source voltage and half the time the reflected voltage subtracts from the source voltage. Both are true half the time. You can point out either case on the graph. That's why the average interference term is zero for this special case and therefore why 100% of the average reflected power is dissipated in the source resistor for this special case. You might wonder why I would consider this alternative. If the destructive interference included a 90 degree delay, how would I know whether the 30v was the delayed voltage or exactly in phase with the source? By looking at the graphs? Where is the power stored for 90 degrees? In the equivalent reactance of the transmission line. That's what reactances do in AC circuits. They store energy and deliver it back to the system some time later. -- 73, Cecil http://www.w5dxp.com |
The Rest of the Story
On Mar 23, 10:31 am, Cecil Moore wrote:
Keith Dysart wrote: So yes, the phrase "conservation of power" is appropriately descriptive and follows from conservation of energy. You have a contradiction built into your concepts. You have argued that the instantaneous power dissipated in the source resistor is not equal to the instantaneous forward power component plus the instantaneous reflected power because power must be conserved at each instant of time. That is simply not true. Bzzzzzzzzzzztt. I'm telling that energy must be conserved at each instant of time but power does not have to be conserved at each instant of time. Bzzzzzzzzzzztt. Energy can obviously be stored in a battery or network reactance for dissipation later in time. Indeed. And forgetting to include such flows in the summation would be a serious error. For example, from the example, Ps(t) = Prs(t) + Pg(t) includes Pg(t) which accounts for the energy stored in the line and later returned. There are no missing flows in this equation. And Ps(t) also accounts for energy absorbed in the voltage source. Only the source resistor has a unidirectional energy flow. Do you require that the power used to charge a battery be instantaneously dissipated in the battery? The energy flow into the battery is exactly and always accounted for by the energy flow that heats the battery and the energy flow consumed in the reversable chemical reaction. The instantaneous flows always sum appropriately to satisfy conservation of energy. Of course, if one forgets a flow, then the sum will not balance. Of course not! That's true for a dummy load but NOT for a battery. There is no reason to require dissipation of power at each instant of time to balance. Since energy can be stored, there is no such thing as conservation of instantaneous power, Of course there is, but you must include the flows into the elements that store energy as I have done. only of instantaneous energy. Where is "cos(theta)" in this? And what "theta" is to be used? How many times do I have to explain this? For instantaneous values of voltage, if the sign of the two interfering voltages are the same, theta is zero degrees and the cosine of theta is +1.0. If the sign of the two interfering voltages are opposite, theta is 180 degrees and the cosine of theta is -1.0. A strange of way of looking at it. It seems easier just to say that there is no theta. And add the voltages. But no matter, I have figured out where your extra term comes from. Let us a consider a simple circuit with two voltage sources (V.s1 and V.s2) in series, connected to a resistor R. Using superposition we have V.s1 = R * Ir.s1 and V.s2 = R * Ir.s2 So Vr.tot = V.s1 + V.s2 and Ir.tot = I.s1 + I.s2 This is superposition, and all is well. The power dissipated in the resistor is Pr = (Vr.tot)**2 / R but we could also derive Pr in terms of V.s1 and V.s2 Pr = (V.s1 + V.s2) (V.s1 + V.s2) / R = ((V.s1)**2 + (V.s2)**2 + (2 * V.s1 * V.s2) ) / R = (V.s1)**2 / R + (V.s2)**2 / R + (2 * V.s1 * V.s2) / R Now some people attempt to compute a power for each of the contributing voltages across the resistor and obtain Pr.s1 = (V.s1)**2 / R Pr.s2 = (V.s1)**2 / R When these are added one obtains Pr.false = (V.s1)**2 / R + (V.s2)**2 / R which, by comparison with Pr above can easily be seen not to be the power dissipated in the resistor. Pr.false is missing the term ((2 * V.s1 * V.s2) / R) from Pr. It is for this reason that it is said that one can not superpose powers. Simply stated, when powers are dervived from the constituent voltages that are superposed, it is not valid to add the powers together to derive the total power. Of course for the most part, powers being added are not powers derived from the constituent voltages of a total voltage, so in most cases it is quite valid to add powers and expect them to sum to the total power. But what do you do if a circuit is superposing two voltages and you are presented with information about the circuit in terms of powers. Well then you can add the powers and include a correction term. Assume Pr = Pr.false + Pr.correction = Pr.s1 + Pr.s2 + Pr.correction But can we find a Pr.correction? It has to correct for the term missing from Pr.false but present in Pr, i.e. ((2 * V.s1 * V.s2) / R). Restated in terms of power, ((2 * V.s1 * V.s2) / R) becomes 2 * sqrt(P.s1 * P.s2) But sqrt has two solutions so we have to write Pr = Pr.s1 + Pr.s2 +/- 2 * sqrt(P.s1 * P.s2) which should look very familiar. As you have correctly pointed out, the sign of Pr.correction is negative when the signs of the constituent voltages are different and positive when they are the same. The reason for this can easily be seen from the derivation of Pr.correction. This Pr.correction term has nothing to do with interference, it is the correction required when it is desired to add two powers computed from the superposing constituent voltages of an actual total voltage across an element and derive the energy flow into the element. Note that there is no hint that Pr.correction needs to be stored when it is negative nor come from somewhere when it is positive. It is, after all, just a correction that needs to be applied when one wants to compute the total power given two powers derived from the constituent voltages of superposition. Since one needs to know the constituent voltages to determine the sign of Pr.correction, why not just use superposition to compute the total voltage and then derive the power? It would be much simpler. With no need for Pr.correction, interference, storage and release of interference 'energy', ... (Of course, over in optics land it is difficult to measure the voltage, so suffering the pain of using powers is probably appropriate). This analysis also makes clear the nature of powers computed from the constituent voltages of superposition. These powers do not represent real energy flows. As discussed far above, real energy flows can be summed to test for conservation of energy. When energy flows do not sum appropriately, then either an energy flow is missing, or one is attempting to sum powers which are not real, for example, having been computed from the constituent voltages of superposition (e.g. Pfor and Pref in a transmission line). ....Keith |
The Rest of the Story
On Sun, 23 Mar 2008 19:57:24 GMT
Cecil Moore wrote: Roger Sparks wrote: (the reflected voltage should ADD to the source voltage) If you graph the two voltages you will find that half the time the reflected voltage adds to the source voltage and half the time the reflected voltage subtracts from the source voltage. Both are true half the time. You can point out either case on the graph. That's why the average interference term is zero for this special case and therefore why 100% of the average reflected power is dissipated in the source resistor for this special case. You might wonder why I would consider this alternative. If the destructive interference included a 90 degree delay, how would I know whether the 30v was the delayed voltage or exactly in phase with the source? By looking at the graphs? Where is the power stored for 90 degrees? In the equivalent reactance of the transmission line. That's what reactances do in AC circuits. They store energy and deliver it back to the system some time later. -- 73, Cecil http://www.w5dxp.com I did not use a graph, but created a spreadsheet that calculated Vrs for the short circuit, 45 degree long line. It shows the 90 degree transfer of power that you described. I posted the spreadsheet in PDF format at http://www.fairpoint.net/~rsparks/Reflect_short.pdf. To me, this shows that my traveling wave analysis on an instant basis is not correct because the energy can not be located precisely on a degree-by-degree scale. Yes, it is correct on the average over 360 degrees, but not instantaneously. We are missing something. Central to traveling waves is the assumption that the wave is not compressable. The energy is assumed to flow in a consistantly predictable mannor that is linear and described by a sine wave. That assumption is violated when energy is delayed for reasons other than distance of travel, which is demonstrated in this example. I am not ready to suggest a cure for my traveling wave analysis. I only see that it does not work to my expectations. Thanks for providing the examples and comments. -- 73, Roger, W7WKB |
The Rest of the Story
Keith Dysart wrote:
The energy flow into the battery is exactly and always accounted for by the energy flow that heats the battery and the energy flow consumed in the reversable chemical reaction. Point is, energy can be stored and released at a later time. You earlier said that reactances do not store energy for release at a later time yet that is exactly what reactances do. A strange of way of looking at it. It seems easier just to say that there is no theta. And add the voltages. Saying there is no theta is a shortcut that can get one into trouble as it did with you. Since there is no such thing as negative energy, there is also no such thing as negative power. Note there are no negative power signs in the power density equation where 'theta' is the phase angle between the two interfering voltages: Ptot = P1 + P2 + 2*SQRT(P1*P2)cos(theta) The last term is known as the "interference term", page 388 of "Optics" by Hecht, 4th edition. When 90 theta 180, the sign of the last term is negative indicating destructive interference. When 0 = theta 90, the sign of the last term is positive indicating constructive interference. When theta = 90, there is zero interference which is what Part 1 of my web articles is based upon. This Pr.correction term has nothing to do with interference, ... Your argument is not with me but rather is with Eugene Hecht who defined that term as the "interference term" in "Optics". Have you even read his chapter on interference? If not, I would suggest that you do so. Two other enlightening chapters are on "Superposition" and "Coherency". Note that there is no hint that Pr.correction needs to be stored when it is negative nor come from somewhere when it is positive. You're correct, there's no hint. It is spelled out in detail in "Optics". The possibilities are listed below. Your above statement is a conceptual violation of the conservation of energy principle. In the absence of any other energy source or energy sink, localized destructive interference must exactly match the localized constructive interference magnitude in order to avoid a violation of the conservation of energy principle. This is why a Z0-match works. Since one needs to know the constituent voltages to determine the sign of Pr.correction, why not just use superposition to compute the total voltage and then derive the power? That is what has extended this discussion to arguments over the past quarter century. That 30,000 foot method says nothing about where the ExH energy in the reflected wave goes. The irradiance (power density) equation with its defined "interference term" tells us exactly where all the energy goes and answers the question: What happens to the ExH energy in the reflected wave? Here are the basic principles: When destructive interference occurs, there is "extra" energy left over from that isolated event. That energy must go somewhere. Here are the possibilities in a typical lossless RF transmitting system. 1. The source can throttle back on its energy output to compensate for the destructive interference energy. 2. Reactive components can store the destructive interference energy and return it to the network at a later time. 3. In the absence of (1) and (2) above, an RF energy wave is launched in a direction that allows the "extra" energy to leave the destructive event area. The last possibility is why we can observe reflected energy being redistributed back toward the load in the complete absence of single-wave reflections. When constructive interference occurs, there is "missing" energy needed to be supplied into that isolated event. That energy must come from somewhere. Here are the possibilities in a typical lossless RF transmitting system. 1. The source can simply supply the energy needed by the constructive interference event. 2. Reactive components can return stored energy to the network. 3. In the absence of (1) and (2) above, constructive interference energy *must* be supplied in real time by destructive interference between two other waves. ************************************************** ******* * The last possibility is how a Z0-match redistributes * * all of the reflected energy back toward the load when * * the physical reflection coefficient is not 1.0. * ************************************************** ******* The two-step process of redistributing 100% of the ExH reflected wave energy back toward the load is covered in my other energy analysis article on my web page at: http://www.w5dxp.com/energy.htm This analysis also makes clear the nature of powers computed from the constituent voltages of superposition. These powers do not represent real energy flows. As discussed far above, real energy flows can be summed to test for conservation of energy. Translation: Don't bother trying to ascertain where the ExH component wave energy goes. Since the conservation of energy principle cannot be violated in reality, it is OK to violate it conceptually. Now where have I heard that argument before? :-) "I personally don't have a compulsion to understand where this power 'goes'." Do you really think that the ExH energy in a reflection from a mirror does not represent real energy flow? -- 73, Cecil http://www.w5dxp.com |
The Rest of the Story
Roger Sparks wrote:
To me, this shows that my traveling wave analysis on an instant basis is not correct because the energy can not be located precisely on a degree-by-degree scale. Yes, it is correct on the average over 360 degrees, but not instantaneously. We are missing something. What you are missing is the localized interference patterns within the individual cycles. The interference changes from destructive to constructive every 90 degrees. For every negative (destructive) interference term, there is an equal magnitude positive (constructive) interference term 90 degrees later. These, of course, average out to zero. Exactly the same thing happens when a coil or capacitor is present in a circuit. When the instantaneous voltage of a source is zero and thus delivering zero instantaneous power, a circuit capacitor is delivering energy back into the circuit that can be dissipated by a resistor. Central to traveling waves is the assumption that the wave is not compressable. The energy is assumed to flow in a consistantly predictable mannor that is linear and described by a sine wave. That assumption is violated when energy is delayed for reasons other than distance of travel, which is demonstrated in this example. Power is certainly compressible. One can stuff 100 amphere- hours into a battery in 2 hours and take 20 hours to remove it. Why can't 60 watts of instantaneous power be stuffed into a reactance and be removed 90 degrees later? I am not ready to suggest a cure for my traveling wave analysis. I only see that it does not work to my expectations. Your expectations seem to be based on a conservation of power principle which doesn't exist. There is no violation of linearity if the energy dissipation is delayed by 90 degrees or by ten billion years. I don't recall any published material where anyone tried to explain where the instantaneous energy goes while at the same time denying the possibility of interference. -- 73, Cecil http://www.w5dxp.com |
All times are GMT +1. The time now is 09:50 PM. |
Powered by vBulletin® Copyright ©2000 - 2025, Jelsoft Enterprises Ltd.
RadioBanter.com