RadioBanter

RadioBanter (https://www.radiobanter.com/)
-   Antenna (https://www.radiobanter.com/antenna/)
-   -   Additional Line Losses Due to SWR (https://www.radiobanter.com/antenna/2639-additional-line-losses-due-swr.html)

Jim Kelley December 3rd 04 06:43 PM



Bart Rowlett wrote:

Jim Kelley wrote:


I think the source of part of the confusion here is that some people
apparently interpret the 'forward power' reading on their meter to
mean the power into their transmission line.



It's not.


I sincerely hope you don't think I was implying that YOU were confused
by such a thing, Bart. ;-)

73, Jim AC6XG


Cecil Moore December 3rd 04 06:53 PM

Robert Lay W9DMK wrote:

On Thu, 02 Dec 2004 09:47:54 -0600, Cecil Moore
wrote:


Consider an earlier example made up of lossless lines:

100W XMTR---50 ohm---+---one second long 291.5 ohm---50 ohm load

The voltage reflection coefficient at the load is 0.707. The power
reflection at the load is 0.5, i.e. half the power is reflected.

After steady-state has been reached, the XMTR has output 300 more
joules than the load has accepted. A smaller real-world experiment
will easily verify that it is a fact that all energy sourced that
has not reached the load must necessarily be confined to circulating
energy or losses in the transmission line.

Question: In the above example, where are those 300 joules of energy
located and what is happening to them?

We know that 300 joules is wave energy and RF waves always move
at the speed of light, i.e. they cannot stand still. So please
determine how much energy is moving and in which of only two
possible directions.



Dear Cecil,

Here's my guesses -
The 300 joules of energy decays at a particular rate - i.e., in a
certain interval of time, 63.2% of it will have been converted to and
become dissipated as heat. During that same time interval,Ti, there
will be an equal amount of energy introduced to replenish the amount
lost. In other words, there will be a continuum of energy transferring
into the transmission line to exactly make up for that lost in any
given period of time.


Yep, the point is that the *net* energy in the transmission line will
remain at 300 joules during steady-state. The transmission line is one
second long and the source is sourcing 100 joules/sec. That means that
200 joules of "extra" energy is being stored in the transmission line.
The forward power is 200 joules/sec, 100 joules/sec higher than the
source power. The reflected power is 100 joules/sec. There is exactly
where the 200 joules of energy are stored - half in the forward wave
and half in the reflected wave whose superposition results in the
standing wave.

Eventually, someone will disconnect the source generator at time T2.
However, the load will continue to receive energy for a length of
time, Ti, at which point roughly 63.2% of 300 joules of energy will
have been dissipated in the load. If we wait long enough, 99.9% of the
300 joules will have been dissipated, but it will take forever for the
last little bit to disappear.

It kind of makes you think in terms of "life everlasting", doesn't it?


It probably gets close enough to zero for government work.

Did you see my question on another posting? If one hooks up a 1/4WL
stub to a signal generator, what is the dB loss in the stub? It might
have something to do with your original posting.
--
73, Cecil http://www.qsl.net/w5dxp

Reg Edwards December 3rd 04 07:00 PM

Instead of messing about calculating the additional loss due to SWR and then
adding it to the matched loss, I've just had a wonderful idea.

Why not calculate the actual line loss directly and solve all your problems
at one fell swoop.
---
Reg.



Richard Clark December 3rd 04 07:13 PM

On Fri, 3 Dec 2004 19:00:14 +0000 (UTC), "Reg Edwards"
wrote:

Glass half empty theory:
Instead of messing about calculating the additional loss due to SWR and then
adding it to the matched loss, I've just had a wonderful idea.

Glass half full theory:
Why not calculate the actual line loss directly and solve all your problems
at one fell swoop.



Cecil Moore December 3rd 04 07:19 PM

Jim Kelley wrote:
It's accurate to say that power is something which itself doesn't
propagate in any fashion, at any wavelength.


I know that's the physicists view, but some engineering views
are slightly different because of a differing definition of
"power". Let's say we have a one second EM pulse containing one
joule of energy traveling along a transmission line with three
joules/sec measuring points. For one second periods in succession,
we will measure one watt at the measuring points. In each case,
the one watt is the same one watt, displaced in time, being
transferred to the load. That one watt appears at the first
measuring point, then at the second measuring point, then at
the third measuring point, and finally heats up the load. It
certainly appears to be associated with the pulse moving from
the source to the load.

That's the way a lot of engineers deal with power, including
all the power company engineers that I know, and that's the way
the IEEE Dictionary deals with power.

Your "tree falling in the forest making no sound" concept
may not be the best approach for the real world.
--
73, Cecil http://www.qsl.net/w5dxp

Cecil Moore December 3rd 04 07:52 PM

Reg Edwards wrote:
Instead of messing about calculating the additional loss due to SWR and then
adding it to the matched loss, I've just had a wonderful idea.

Why not calculate the actual line loss directly and solve all your problems
at one fell swoop.


What is the formula for the total dB loss?
--
73, Cecil http://www.qsl.net/w5dxp

Gene Fuller December 3rd 04 08:58 PM

Cecil,

I am glad to see you have come around to the correct view that the
"extra" energy is stored in a standing wave.

Now if only we could convince you that mathematically, physically, and
in "reality" there is not the slightest bit of difference between
individual wave components and their superposition result then there
would be real progress.

Oh, by the way, is there some reason you highlight *net* energy? Is
there any other kind? Energy is a scalar, so numerically it can be only
positive or negative, with no phase angle or other vector properties.
Unless part of the energy in your transmission line is negative the net
energy would be the same as the gross energy. (Not including sales tax
and shipping charges.)

I am well acquainted with the concept of negative energy when describing
atomic structure, for example, but I have not heard of negative energy
in transmission lines. Can you explain the distinction you appear to make?

73,
Gene
W4SZ



Cecil Moore wrote:


Yep, the point is that the *net* energy in the transmission line will
remain at 300 joules during steady-state. The transmission line is one
second long and the source is sourcing 100 joules/sec. That means that
200 joules of "extra" energy is being stored in the transmission line.
The forward power is 200 joules/sec, 100 joules/sec higher than the
source power. The reflected power is 100 joules/sec. There is exactly
where the 200 joules of energy are stored - half in the forward wave
and half in the reflected wave whose superposition results in the
standing wave.


Jim Kelley December 3rd 04 10:09 PM

Jim Kelley wrote:

It's accurate to say that power is something which itself doesn't
propagate in any fashion, at any wavelength.


Will someone please try to explain to Cecil that engineering is an
application of fundamental physical properties, and that the disciplines
of physics and engineering are not at odds with one another?

thanks,

AC6XG


Cecil Moore December 3rd 04 10:13 PM

Gene Fuller wrote:
Cecil,

I am glad to see you have come around to the correct view that the
"extra" energy is stored in a standing wave.


Never have I ever budged from the view that the "extra" energy
is stored in the standing wave components, i.e. in the forward
wave and the reflected wave. What I object to is your merging
of the forward wave and reflected wave as if they were some sort
of homoginized energy. You can prove your beliefs by providing
an example of a standing wave not composed of the superposition
of a forward wave and a reflected wave. I have offered that challenge
before and nobody has stepped up to the plate. Perhaps, you will
be the first. I await with abated breath.

Now if only we could convince you that mathematically, physically, and
in "reality" there is not the slightest bit of difference between
individual wave components and their superposition result then there
would be real progress.


What you are arguing is that there is no difference between a husband
and a wife. They are just two components of a family who merge into
a single entity so either or both may be male or female. Sorry, Gene,
that's not my view of the world. IMHO, it is the *components* that are
important. IMO, you liberals are trying to destroy science and society
all at the same time.

Oh, by the way, is there some reason you highlight *net* energy? Is
there any other kind?


Of course, there is another kind of energy besides net energy. Is there
any difference between a wife and a husband? They are both parents, so
you liberals would argue that there is no difference between them. I
simply don't agree with you.

I am well acquainted with the concept of negative energy when describing
atomic structure, for example, but I have not heard of negative energy
in transmission lines. Can you explain the distinction you appear to make?


It's a convention, Gene. I'm surprised you have never heard of it. ExH
traveling in one direction is positive. ExH traveling in the opposite
direction is negative. The Z0 of a transmission line forces the E-field
to H-field ratio to be Z0, i.e. forces the forward voltage to forward
current ratio to be Z0 - and the same for reflected current. One of my
references shows a Poynting Vector for the forward power and a separate
Poynting Vector for the reflected power, i.e. husbands and wives are not
interchangable!
--
73, Cecil http://www.qsl.net/w5dxp

Cecil Moore December 3rd 04 10:39 PM

Jim Kelley wrote:
Will someone please try to explain to Cecil that engineering is an
application of fundamental physical properties, and that the disciplines
of physics and engineering are not at odds with one another?


On the contrary, many of the pure-physics-oriented posters to
this newsgroup have alleged that the IEEE Definitions are Bull$hit
and are to be ignored. Check Google if you don't believe it.

The IEEE Definitions are what engineers abide by. Of course,
the disciplines of physics and engineering are certainly at
odds with one another. For instance, engineers have an altogether
different view of what "work" is, compared to the physicists.
Physicists say no work is done if the starting line and the finish
line are the same for a marathon. Engineers will say: "Then why am
I so friggin' tired?"

The POWER engineers at a POWER generating station operated by
a POWER company simply don't buy into your pure physics BS.
They assume that POWER (joules/sec) leaving a generating station
will, after subtracting losses, make money for the company.
--
73, Cecil http://www.qsl.net/w5dxp

Richard Clark December 3rd 04 11:48 PM

On Fri, 03 Dec 2004 16:13:44 -0600, Cecil Moore
wrote:
ExH traveling in one direction is positive.

Radiation
ExH traveling in the opposite direction is negative.

Rearadiation

You got transmitters in Texas that suck?

Cecil Moore December 3rd 04 11:57 PM

Richard Clark wrote:

Cecil Moore wrote:
ExH traveling in one direction is positive.


Radiation

ExH traveling in the opposite direction is negative.


Rearadiation

You got transmitters in Texas that suck?


Suggest that you take time to understand the difference between an
unterminated Rhombic and a terminated Rhombic and get back to us.

Hint: The forward wave radiates in the forward direction. The reflected
wave radiates in the reverse direction. The termination eliminates the
reflected wave thus eliminating the reverse radiation. I'm surprised
that you don't know that.
--
73, Cecil http://www.qsl.net/w5dxp


Cecil Moore December 4th 04 12:00 AM

Richard Clark wrote:
If that is too hard, how many candela total intensity did we begin
with?


You first, Richard. What is the difference between a duck?

Jim Kelley December 4th 04 12:09 AM



Richard Clark wrote:
On Fri, 03 Dec 2004 16:13:44 -0600, Cecil Moore
wrote:

ExH traveling in one direction is positive.


Radiation

ExH traveling in the opposite direction is negative.


Rearadiation

You got transmitters in Texas that suck?


Maybe so. Texas certainly does seem to have its own unique set of
physical laws. ;-)

"Physicists say no work is done if the starting line and the finish
line are the same for a marathon."

:-)
No physicist I know would ever say something like that. Only a gross
misapplication of Newtonian mechanics and/or thermodynamics could lead
someone to such a belief. For example, such a person might think that a
ball thrown up into the air has had zero work performed on it after it
returns to the hand which threw it. The fact is, it requires as much
work to return it to the earth as it does to throw it into the air.
(There are some interesting physics demonstrations on how this doubling
of work can be used to interesting advantage.) But since in mechanics
there is no such thing as negative work, total work is accumulative.
Potential and kinetic energies are of course restored to initial
conditions, but the conversion from one to the other does not ordinarily
occur without some form of external 'help'. The misunderstanding is at
least consistent with some similar misunderstandings that have been
expressed with regard to the physics of power and energy.

ac6xg


Richard Clark December 4th 04 12:11 AM

On Fri, 03 Dec 2004 17:57:32 -0600, Cecil Moore
wrote:
You got transmitters in Texas that suck?

Suggest that you take time to understand

That's whining liberal talk - Up or Down, is it yes boy?

Richard Clark December 4th 04 12:17 AM

On Fri, 03 Dec 2004 18:00:59 -0600, Cecil Moore
wrote:
Richard Clark wrote:
If that is too hard, how many candela total intensity did we begin
with?

You first, Richard. What is the difference between a duck?

Your question, put in optical terms, and you can't answer it, that is
the difference, duck. :-)

Wes Stewart December 4th 04 12:58 AM

On Fri, 03 Dec 2004 16:13:44 -0600, Cecil Moore
wrote:
[snip]

|I await with abated breath.

If only it was true [g]

Reg Edwards December 4th 04 01:16 AM


"Cecil Moore" wrote
Reg Edwards wrote:
Instead of messing about calculating the additional loss due to SWR and

then
adding it to the matched loss, I've just had a wonderful idea.

Why not calculate the actual line loss directly and solve all your

problems
at one fell swoop.


What is the formula for the total dB loss?
--

=================================

I wonder why I ever bothered to introduce Chipman to this newsgroup.

Try him.

----
Reg.



Richard Clark December 4th 04 02:09 AM

On Fri, 03 Dec 2004 17:54:33 -0800, Jim Kelley
wrote:

I can if the light source is a sodium discharge lamp. :-) What sort of
light source are you assuming?


Hi Jim,

I bet you can!

Edison/Mazda style tungsten filament light bulb. Available at K-Mart
or Walton's or any of a million retail outlets, even in Texas. If not
in Texas, then heat a brandin' arn to incandescence (bet he can't tell
us what temperature for 555nM tho').

Please, folks, Optics is for the professionals. Don't try this at
home! ;-)

73's
Richard Clark, KB7QHC

[email protected] December 4th 04 03:00 AM


"Reg Edwards" wrote in message
...

"Cecil Moore" wrote
Reg Edwards wrote:

SNIP
I wonder why I ever bothered to introduce Chipman to this newsgroup.

Try him.

----
Reg.


Reg,
This thread is purely a platform for snide remarks or for the pursuit of
appearing clever
to readers. It is not for technical education but instead it is a duking out
of smarmy comments
so as to produce a suedo pecking order for onlookers to assuage who has the
most accumen
with respect antenna education. It also helps in ascertaining the personal
ethics of one
compared to others. Thus the introduction of Chipman would serve no real
purpose other than to
deflect the daggers or missiles thrown between individuals. I am amazed that
Cecil is willing to
stand there whether he is right or wrong when many (not all ) contributors
have no interest in
keeping to the subject other than to provide utterances that cannot be
understood apparently
or to throw a stone and then hide.
Cecil, you just have nothing to gain by conversing with those
whose only intent is to taunt you and not to provide true closure of posting
discussion.
Respond to those who have something to offer and let the others drown in
their own saliva
when left alone.
Cheers and beers
Art



Roy Lewallen December 4th 04 04:48 AM

Cecil Moore wrote:

. . .
The IEEE Definitions are what engineers abide by. . .


If you believe that, you haven't had much contact with real, working
engineers.

In my experience, the IEEE definitions are often way out of step with
common usage by working engineers. Nearly none in my acquaintance look
to it as an authoritative source. A useful guideline, perhaps, at most.
I can easily see three causes for the deficiency:

1. The IEEE Dictionary covers an extremely wide variety of rapidly
evolving specialties, including power, digital, fields, control systems,
fiber optics, electronics, EMC, and on and on. It would be extremely
difficult to cover all these disparate specialties accurately and in
depth without a huge amount of input from working engineers in each
specialty.
2. As far as I can tell, the Dictionary is put together by volunteers,
which limits the time and effort which can applied to it.
3. The active membership of the IEEE largely comprises academics rather
than working engineers. Academics are a poor source of information about
common usage by working engineers. And, working engineers don't tend to
"abide by" the dictates of academics, in my experience.

I don't have a recent copy of the IEEE Dictionary, but think and hope
it's improved over the years. But I'm certain it hasn't come anywhere
close to the point at which it's something "engineers" "abide by".

Roy Lewallen, W7EL

Robert Lay W9DMK December 4th 04 05:24 AM

On Sat, 27 Nov 2004 21:43:14 GMT, (Robert Lay
W9DMK) wrote:

On Fri, 26 Nov 2004 10:57:25 -0700, Wes Stewart
wrote:


Yes. But the ITT Reference Data For Radio Engineers uses this paper
as a reference.

If you have Mathcad, a sheet that implements some of the equations was
included as a reference in my Balanced Transmission line paper.

http://users.triconet.org/wesandlinda/LineCalc.mcd


Dear Wes,

I was happy to find that the MacAlpine paper is the first part of
Chapter 22 of the ITT Handbook, as the latter is much more readable.

I did not pick up on the MathCad files, because I do not have MathCd -
however, the material from MacAlpine and Ricardi have answered most of
my concerns.


|I hope that MacAlpine agrees with what Dave and Richard are telling
|me, because their responses seem to be correct and are exactly what I
|was afraid of - that I've been sucked into another example of the
|strange terminology used to describe "losses".
|
|I have always thought of "loss" as a conversion to another form of
|energy (typically heat energy) which is lost from the system.
|Apparently, the kind of "loss" being described in the example that I
|gave is not a loss at all.


I was premature in those two paragraphs, above. I can see now that the
Additional Losses Due to SWR really are dissipative and are unrelated
to the "Mismatch Losses" and "Transducer Losses" defined on page 22-12
of the ITT Handbook, 5th Ed.


Yes it is. A simple-minded way of looking at it is if the SWR is
greater than unity then increased current is flowing in the line. The
line has resistive loss, so the I^2*R loss increases. The current
isn't constant (there is a current standing ratio, ISWR, just like a
VSWR) so there are peaks and valleys in the current and as you have
figured out, the longer the line and the higher its nominal loss, the
lower the ISWR is at the line input.


My interpretation of your "Yes it is." is that you mean that the
Additional Losses Due to SWR are truly heat losses and are due to the
ohmic losses in the hot spots of the line. Then we agree on that
point. Your paragraph above is much more succinct than the papers by
MacAlpine and Ricardi, but it certainly tells the story.

So the loss per unit length is non-linear and varies with distance
from the mismatch, but it is a real dissipative loss.


I don't know that I would have used the term "non-linear", but I would
certainly agree that it varies along the line in accordance with the
current loops.

For those interested in the loss in the shorted or open stub case,
maybe this will be of interest:
http://users.triconet.org/wesandlind...ching_Loss.pdf


I took that pdf and added it to the collection. There were several
things about that paper that filled-in gaps of detail in MacAlpine.
However, neither paper gives us much hope for a simple model of these
losses. Nonetheless, it makes hash out of the material in The ARRL
Antenna Book. In all fairness, the Antenna Book cannot cover all
aspects of these topics in detail. Unfortunately, the material in the
Antenna Book is, in my opinion, very misleading in several specific
areas, as follows:
- The Antenna Book gives only one expression for Total Line
Loss (combining ML loss and the Additional Loss Due to SWR). If we
accept Macalpine's model, there are different relationships for the
range of SWR from 0 to 6 and for the range from 6 upwards.
- Antenna Book does not explain that the hot spots are very
localized and that the additional losses can be quite dependant upon
the length of the line in wavelengths. For example, the losses in a
segment of line less than 1/3 wavelength might be insignificant in
comparison with a segment of line greater than 1/3 wavelength simply
because the shorter segment may not contain a hot spot. In other
words, one cannot apply the Antenna Book equations, blindly, because
of several factors that are not even mentioned, and for short line
segments it is quite possible that there would be no signicant losses
due to SWR.
- The most misleading information in The Antenna Book is on
pages 24-11 and 24-12 where it is shown that a 100 foot RG-213
feedline will suffer 25 dB of Additional Loss Due to SWR at 1.83 MHz
because of the very short antenna. I believe that when the equations
from the ITT Handbook are used instead, that the actual losses will be
far, far less.

Just today, I made a careful measurement on an RG-8/U line of 5.33
meters length at 30 MHz and terminated with a 4700 + j 0 load. The
Matched Line Loss of that line at 30 MHz is 0.9 dB per 100 feet, and
its Velocity Factor is between 0.75 and 0.80 The input impedance was
actually measured at 2.45 -j15 ohms for an SWR at the input of 22.25.
The SWR at the load end was 94. Those two SWR's establish a total loss
on the line of 0.15 dB. If one were to blindly apply the formula in
The Antenna Book on page 24-9, the result obtained would be 4.323 dB.


I have finally resolved this problem. The last paragraph, immediately
above, represents the problem that I have been unable to reconcile
until now.

Surprisingly, it was not until today that I finally made a computation
of the input power to the line for the configuration above.
Specifically, I was able to compute the voltage and current at the
input to the line that would produce a 100 volt reference voltage
across the 4700 ohm line. That is the obvious thing that had to be
done in order to establish a reference power for purposes of computing
losses. That calculation resulted in an applied voltage at the line
input of 29.2 volts at angle -171.5 degrees and a current of 1.917
amps at -90.78 degrees. Computing power into the line as E*Icos(theta)
= 9.024 watts. The power delivered to the load is 100 volts squared
divided by 4700 ohms, which is 2.127 watts.

Therefore the efficiency is 23.6% and the losses in the line are 6.275
dB. In all fairness, I did have to change one assumption in the data
above. I had to revise my attenuation value of 0.9 dB per 100 ft.
upwards to a value of 1.72 dB per 100 ft. in order to get my measured
impedance at the line input to be consistent with that line impedance,
length, load value and velocity factor.

Up until today, I could not see the losses being that high. In fact,
everything that I used to compute losses based on the measurements
above told me that the losses were on the order of 0.3 dB or less,
depending on which foolish method I was using. The method that really
sucked me in was the method based on two SWR readings - one at the
load and one at the input. That method, gives either 0.15 dB or 0.3
dB, depending upon whether you believe the scale at the bottom of the
Smith Chart or whether you believe the nomograms on pages 22-7 or 22-8
of the ITT Reference Data for Radio Engineers, 5th Edition.

So, once I tackled it head on and just did the brute force, obvious
calculation, I got a loss figure that exactly corresponds to the
losses predicted in The ARRL Antenna Book, 17th Edition, page 24-9.

So, I hope everyone had fun and learned something in the process. I
know I did.

73,

Bob, W9DMK, Dahlgren, VA
http://www.qsl.net/w9dmk

Ian White, G3SEK December 4th 04 09:52 AM

Cecil Moore wrote:
Of course,
the disciplines of physics and engineering are certainly at
odds with one another.


That is nothing but an excuse for your own sloppy thinking.

When it comes down to fundamentals, physics and engineering must always
agree exactly - because they are both working with the same physical
reality. That is a bedrock principle, known and shared by all competent
physicists and all competent engineers.

There's a reason why they call these subjects "disciplines", you know.
Reality sets hard rules that you have to follow - or else you'll get it
wrong.

The only differences between physics and engineering are the
acknowledged and clearly understood approximations that each side has to
apply in order to follow its own particular interests. Physics is most
interested in knowing things, while engineering is most interested in
doing things - but neither to the exclusion of the other.

If your ideas cannot make the physics and engineering approaches agree,
it means that your ideas are wrong. That is a simple and completely
reliable test.

And it's strictly *your* problem.


--
73 from Ian G3SEK 'In Practice' columnist for RadCom (RSGB)
http://www.ifwtech.co.uk/g3sek

Cecil A. Moore December 4th 04 12:46 PM

Roy Lewallen wrote:
Cecil Moore wrote:
The IEEE Definitions are what engineers abide by. . .


If you believe that, you haven't had much contact with real, working
engineers.


What dictionary do "real, working engineers" use? A language
without a dictionary is a disaster waiting to happen.
--
73, Cecil http://www.qsl.net/w5dxp

Cecil A. Moore December 4th 04 01:27 PM

Ian White, G3SEK wrote:
If your ideas cannot make the physics and engineering approaches agree,
it means that your ideas are wrong.


If you believe physicists and engineers agree on everything, you are
living in never-never land. It's difficult to find two physicists
who agree on everything - or two engineers. Witness the arguments
on this newsgroup.

Ian, there are 13 definitions of "efficiency" in the IEEE Dictionary,
each associated with a different engineering discipline. And that's
not counting the definitions of "efficiency" that exist in the
world of pure physics. Anyone who thinks a word has one and only
one definition that everyone agrees upon and encompasses all subjects
and all fields is clearly out of touch with reality.

For instance, I point to the definition of "power" in the IEEE
dictionary. Some posters on this newsgroup disagree with that definition
and that's from people who had the same textbook as I did in college.
Since that's the case, then of course, some of the ideas of engineering
and physics will disagree. "Power" for a power engineer working at a
power generating plant measuring megajoules/sec in a transmission line
simply does not have the same definition as "power" for a physics professor.
--
73, Cecil http://www.qsl.net/w5dxp

Ian White, G3SEK December 4th 04 04:53 PM

Cecil A. Moore wrote:
"Power" for a power engineer working at a
power generating plant measuring megajoules/sec in a transmission line
simply does not have the same definition as "power" for a physics professor.


"Power" is just a single word, so it certainly does have to carry
several different shades of usage.

My point is that the competent engineer and the competent physics
professor understand that their different usages are still completely
consistent at a fundamental level.

I don't believe you understand the discipline that that need for
consistency imposes.



--
73 from Ian G3SEK 'In Practice' columnist for RadCom (RSGB)
http://www.ifwtech.co.uk/g3sek

H. Adam Stevens, NQ5H December 4th 04 05:25 PM


"Ian White, G3SEK" wrote in message
...
Cecil A. Moore wrote:
"Power" for a power engineer working at a
power generating plant measuring megajoules/sec in a transmission line
simply does not have the same definition as "power" for a physics
professor.


"Power" is just a single word, so it certainly does have to carry several
different shades of usage.

My point is that the competent engineer and the competent physics
professor understand that their different usages are still completely
consistent at a fundamental level.

I don't believe you understand the discipline that that need for
consistency imposes.

Cecil's back at it, I see.



--
73 from Ian G3SEK 'In Practice' columnist for RadCom (RSGB)
http://www.ifwtech.co.uk/g3sek




Richard Clark December 4th 04 06:40 PM

On Sat, 04 Dec 2004 05:24:33 GMT, (Robert Lay
W9DMK) wrote:

Just today, I made a careful measurement on an RG-8/U line of 5.33
meters length at 30 MHz and terminated with a 4700 + j 0 load. The
Matched Line Loss of that line at 30 MHz is 0.9 dB per 100 feet, and
its Velocity Factor is between 0.75 and 0.80 The input impedance was
actually measured at 2.45 -j15 ohms for an SWR at the input of 22.25.
The SWR at the load end was 94. Those two SWR's establish a total loss
on the line of 0.15 dB. If one were to blindly apply the formula in
The Antenna Book on page 24-9, the result obtained would be 4.323 dB.

Surprisingly, it was not until today that I finally made a computation
of the input power to the line for the configuration above.
Specifically, I was able to compute the voltage and current at the
input to the line that would produce a 100 volt reference voltage
across the 4700 ohm line. That is the obvious thing that had to be
done in order to establish a reference power for purposes of computing
losses. That calculation resulted in an applied voltage at the line
input of 29.2 volts at angle -171.5 degrees and a current of 1.917
amps at -90.78 degrees. Computing power into the line as E*Icos(theta)
= 9.024 watts. The power delivered to the load is 100 volts squared
divided by 4700 ohms, which is 2.127 watts.

Therefore the efficiency is 23.6% and the losses in the line are 6.275
dB. In all fairness, I did have to change one assumption in the data
above. I had to revise my attenuation value of 0.9 dB per 100 ft.
upwards to a value of 1.72 dB per 100 ft. in order to get my measured
impedance at the line input to be consistent with that line impedance,
length, load value and velocity factor.


Hi Bob,

I notice that true to form, all the response in this thread were not
to your bench results. I trust you will appreciate hard
correspondence rather than the fluff.

The one thing (actually there are several) I noted was your having to
double the presumed line loss to make the numbers come out. Given
this injection (or removal) of 100% (or %50) of error, it stands to
reason that your bench, method or instruments need a attention.

The details as I've sifted from the postings:
Cable type = Columbia's number 1198 - not 9913.
Open circuit stub length = 5.334 meters
Frequency = 10.6 MHz,
Input Z = 0.57 + j 0.3 ohms.

The above details appear to have shifted in mid-stream to:
Cable type = RG-8/U line
stub length = 5.334 meters
Frequency = 30.0 MHz,
Open end termination = 4700 + j 0
Input Z = 2.45 -j15

I will skip the determinations of loss and SWR as being problematic as
you indicate and simply go with your observations noted above, and
summarized he
Open end Vtermination = 100V @ 0°
Open end Itermination = 0.0213A @ 0°
Fed end Vinput = 29.2V @ -171.5°
Fed end Iinput = 1.917A @ -90.78°

I was puzzled to see what was initially a resonant stub now measured
with an extremely high Reactance until I re-scanned the material to
note the tripling of frequency.

What caught my eye was this load and certainly your leap of faith that
it was wholly resistive, especially at HF for its size. This would be
extremely unlikely even in a standards lab.

To make a measurement, the rule of thumb is to have instrumentation
whose precision and accuracy exceeds the goal of measuring an unknown
by 5 to 10 times. For really difficult tests (and RF is classic in
that regard) 3 times is often the best you can achieve.

Let's look at that 4700 Ohm resistance. It demands that any
instrumentation support a paralleling load of no less than 23.5K Ohms
to 47K Ohms, or worst case, 14K Ohms. Let's simply ask about the
family lineage of that 4700 Ohm resistance. It sounds suspiciously
like a common (hopefully) carbon composition resistor.

If so, such beasties are rare if it is of the commercial variety, to
not exhibit reactances due to spiral cut value trimming, or an
end-to-end capacitance. Let's just say that you obtained a remarkable
resistor, but it cannot escape this common parasitic capacitance which
for the garden variety resistor amounts to 1.5pF.

At 30 MHz, this 1.5pF capacitance represents a reactance of 3.5K Ohm.
This rather sweeps aside your specification for the load and replaces
it with 4700 -j3537 Ohms. This is a big time source of error and does
not even come close to the 3X requirement for the lowest accuracy.
Worse yet, you haven't even added the bridging impedance of your
measuring device which is certain to be on par, if not worse (you
haven't identified your instrumentation).

Hope you are still looking forward to more fun. ;-)

73's
Richard Clark, KB7QHC

Richard Clark December 4th 04 09:51 PM

On Sat, 04 Dec 2004 18:40:20 GMT, Richard Clark
wrote:

At 30 MHz, this 1.5pF capacitance represents a reactance of 3.5K Ohm.
This rather sweeps aside your specification for the load and replaces
it with 4700 -j3537 Ohms.


Actually 1700 -j2258 Ohms

As you can see, this is the reason why open stubs are avoided.
"Knowing" the parasitic capacitance is problematic. The fringing
effect at the end is difficult to manage whereas a short is much
simpler to define and implement.

73's
Richard Clark, KB7QHC

Reg Edwards December 5th 04 12:36 AM


(PS : You can't deal with reflections without involving Distance,

Velocity,
Place and Time.)


======================================

Just an addition -

You can't deal with Reflections without involving Distance, Velocity,
ECHO's, Place, and, above all, TIME.

Attempted steady-state analyses reduce to non-sense without involving TIME.

But it is a simple matter to relate power levels, one to another, dB-wise or
otherwise, at different PLACES and TIME.

All you guru's, old wives and experts on forward and reflected powers, real
or imaginary, should bear this basic, elementary stuff in mind.

Whatever happened to your primay education?

Power, work and energy are intimately related to TIME.

The self-educated kids living in South American underground Rio sewers,
subjected to culling by armed police, reduced to making a precarious living
be selling laced cigarettes, can do better.

But don't worry about it. Just continue taking your viagra. As for me,
tonight I'm on white, dry, Bordeaux, best consumed within six months of
purchase. And the French know what they are talking about.
----
Reg.



Robert Lay W9DMK December 5th 04 02:53 AM

On Sat, 04 Dec 2004 21:51:09 GMT, Richard Clark
wrote:

On Sat, 04 Dec 2004 18:40:20 GMT, Richard Clark
wrote:

At 30 MHz, this 1.5pF capacitance represents a reactance of 3.5K Ohm.
This rather sweeps aside your specification for the load and replaces
it with 4700 -j3537 Ohms.


Actually 1700 -j2258 Ohms

As you can see, this is the reason why open stubs are avoided.
"Knowing" the parasitic capacitance is problematic. The fringing
effect at the end is difficult to manage whereas a short is much
simpler to define and implement.

73's
Richard Clark, KB7QHC


Dear Richard,
Each and every one of your concerns is deeply appreciated. I had
seriously about measuring that 4700 ohm resistor by itself for just
the reasons that you mention. The reason that I did not is quite
simple. The Resistance dial on the General Radio Model 1606B RF Bridge
only goes to 1000 ohms. C'est la Vie!

I could have chosen a much lower resistance to start with, but then I
would not have had the desired high SWR, which is critical to the
experiment. You might well ask why I made the switch from a 1/4 wave
open ended stub (at 10.6 Mhz) to the 30 MHz test using the same piece
of line. That was to get a high SWR and still have reasonable
confidence in the value without actually measuring it. Perhaps I
should use a capacitor instead. That's still a possibility. I am
thinking of doing it over with a measured 1 k resistor, and just
accepting the SWR of only 20:1. I don't think I have any low ohm
resistors that would give me something around 1 to 3 ohms and still be
low inductance - not from my parts box. Actually, I doubt seriously
that the capacitance effects are as bad as you are suggesting, but I
won't argue that without some additional measurements.

My reason for not going with a short circuit was even simpler. I
wanted a concrete value for a non-zero load power.

Regarding the artificial adjustment of the attenuation loss from
around 0.9 up to about 1.72 did not bother me at the time that I did
it, but I can see why it bothers an independant observer. I will have
to do something about that, and perhaps doing it over with a 1 K
resistor is the answer to all of that - so, here goes, and I will get
back to you in a few hours.

BTW - this is becoming more and more academic, since I think the real
mystery has been resolved, but there's nothing like getting it wrapped
up with a proper ribbon.

Bob, W9DMK, Dahlgren, VA
http://www.qsl.net/w9dmk

Richard Clark December 5th 04 07:24 AM

On Sun, 05 Dec 2004 02:53:35 GMT, (Robert Lay
W9DMK) wrote:

Each and every one of your concerns is deeply appreciated. I had
seriously about measuring that 4700 ohm resistor by itself for just
the reasons that you mention. The reason that I did not is quite
simple. The Resistance dial on the General Radio Model 1606B RF Bridge
only goes to 1000 ohms. C'est la Vie!


Say la-la!

Hi Bob,

Good, you have a great piece of equipment, but the implicit question
remains, what do you use to measure the voltage? That is going to be
a serious load across even a 4700 +j0 resistor. Even X10 Scope probes
would be a poor method.

I could have chosen a much lower resistance to start with, but then I
would not have had the desired high SWR, which is critical to the
experiment. You might well ask why I made the switch from a 1/4 wave
open ended stub (at 10.6 Mhz) to the 30 MHz test using the same piece
of line. That was to get a high SWR and still have reasonable
confidence in the value without actually measuring it. Perhaps I
should use a capacitor instead. That's still a possibility.


Hardly worth the thought actually. The 1.5pF stray capacitance would
be a coup-de-grace for the resistor, do you think you could find less
capacitance (with or without the resistor) when there is probably
already that much in fringe capacitance?

I am
thinking of doing it over with a measured 1 k resistor, and just
accepting the SWR of only 20:1. I don't think I have any low ohm
resistors that would give me something around 1 to 3 ohms and still be
low inductance - not from my parts box. Actually, I doubt seriously
that the capacitance effects are as bad as you are suggesting,


They are, life is cruel.

but I
won't argue that without some additional measurements.


It's better than sitting on the park bench with a box of chocolates
and spouting the philosophy of optical interference. For that you get
my Kudos.

My reason for not going with a short circuit was even simpler. I
wanted a concrete value for a non-zero load power.

Regarding the artificial adjustment of the attenuation loss from
around 0.9 up to about 1.72 did not bother me at the time that I did
it, but I can see why it bothers an independant observer. I will have
to do something about that, and perhaps doing it over with a 1 K
resistor is the answer to all of that - so, here goes, and I will get
back to you in a few hours.


Well, one way is to take your measurements and stick with the original
attenuation loss and transform from the input to this 4700 Ohm load.
Does the data suggest this load is closer to my hip shot guess? You
have a reactance built into your results that is unaccounted for, but
comes with this parasitic inclusion I offer.

BTW - this is becoming more and more academic, since I think the real
mystery has been resolved, but there's nothing like getting it wrapped
up with a proper ribbon.


It's all academic, Bob. When you have to take more than one exam
(with questions that go beyond parallel parking) to pursue a hobby
it's part of the turf. Owning a GR-1606 caps it.

73's
Richard Clark, KB7QHC

Bart Rowlett December 5th 04 04:57 PM

Cecil Moore wrote:
Reg Edwards wrote:

Instead of messing about calculating the additional loss due to SWR
and then
adding it to the matched loss, I've just had a wonderful idea.

Why not calculate the actual line loss directly and solve all your
problems
at one fell swoop.


What is the formula for the total dB loss?


I don't know of one, but here's a procedure which will get you the answer:

1) Determine the transmission line characteristics R, G, L & C at the
frequency of interest.

2) Determine the transmission line termination impedance (or admittance)
at the frequency of interest.

3) For convenience, define the excitation at the input to the
transmission line. e.g. defined voltage, current, or generator with
defined source impedance.

4) Solve the transmission line equation for both the voltage and
current, as a function of time and position, subject to the imposed
boundary conditions. Use any method you wish, though the usual approach
is the so called method of reflections where the complete solution is
taken as the summation of damped forward and reverse traveling waves.
Calculation of Zo and Gamma require knowledge of R,G,L & C.

The solution can be expressed algebraically in terms of hyperbolic
functions and will be found in any good transmission line reference.

Now known are v(x,t) and i(x,t).

5) Separately calculate the dissipative losses due to series resistance
and shunt conductance (or dielectric power factor) as follows:

a) The loss due to series resistance at any instant in time for some
section of transmission line, is i(x,t)^2 * R * dx, integrated over the
subject transmission line section.

b) The loss due to shunt conductance at any instant in time for some
section of transmission line, is v(x,t)^2 * G * dx, integrated over the
subject transmission line section.

c) The total dissipative power loss is the the sum of the time averaged
series and shunt loss components, integrated over the entire
transmission line length.

Consider:

The SWR (reflection coefficient at the termination) alone is not
sufficient to determine the loss in general. This is an important
concept to understand.

For illustration, assume the limiting case where the shunt conductance
can be disregarded. This is a useful approximation for many
transmission line installations used at HF where the SWR is reasonably
low (50). In such practical cases the losses will be dominated by
series resistance.

Consider a short (45 electrical degrees) transmission line terminated
in a pure resistance which is much less than Ro. The standing wave
pattern will be such that the current will be maximum, and the voltage
minimum, at the termination. The losses can be calculated using the
procedure given above.

Now consider the same transmission line terminated in a pure resistance
larger than Ro such that the SWR is the same as previously. The current
will now be minimum at the termination and the total dissipative loss
will be considerably less than when the termination resistance is low,
even though the SWR is identical.

Transmission line losses depend on both the actual load impedance and
the transmission line parameters. Knowing matched attenuation
(dB/length) and load SWR is not sufficient to calculate losses exactly.
Any formulas using only SWR and matched transmission line loss are
approximations and must be used carefully!

Feeding electrically short antennas with 50 ohm coax as is commonly
attempted by amateurs on 80 & 160m can result in transmission line
losses much larger than predicted using the simple approximations given
in the amateur literature.

bart
wb6hqk






Reg Edwards December 5th 04 05:30 PM


You are all floundering about like fish out of water.

The ONLY way to predict the performance of a small resistor at UHF is to
treat it as a transmission line - starting with the simple dimensions of
length and diameter.

L, C and R, and short-circuit input resistance versus frequency
automatically drop into your laps with adequate ball-park accuracy.

As so-called engineers, if you can't measure it, such obvious arithmetical
techniques should already have been included in your elementary analytical
educations.

Spice (of which I have heard about only by reputation on newsgroups) is
useless unless one already knows what it's all about beforehand.

My criticism is not personal - only of the western world's educational
systems and insistent dependence on weapons of mass-destruction.
----
Reg.



Bart Rowlett December 5th 04 06:07 PM

Cecil Moore wrote:
Reg Edwards wrote:

Cecil, when there are several different power levels at different
places in
a circuit, it is entirely up to you how you reference one to another
in dB.


Now Reg, that just cannot be true.


It is true.

Otherwise, there would exist no
conventions.


Multiple conventions exist in all the technical disciplines. A well
versed practioneer is familiar with the various conventions commonly in
use and will choose the one most appropriate to the problem at hand.
General terms such as 'gain' and 'loss' always require the context be
carefully established before the term can be used with any precision.
For example, dissipative loss in a transmission line is different from
transducer loss, but both are often expressed in decibels. One relates
to an actual ratio of two physically meaningful power levels, and the
other is notional.

It's a simple question: When you tell me that the losses
in a transmission line with reflections are 2 dB, exactly what power
are you referencing those losses against?


Reasonable question. Without knowing the context the statement is
essentially meaningless.

Reflected volts - yes!
Reflected current - yes!
Reflected power - NO!


Reflected volts and reflected current existing without any associated
joules/sec????


Reg didn't say any such thing. The wave equation is usually expressed
in terms related to the two complementary field quantities associated
with energy storage. In the case of TEM transmission lines, the two
variables are voltage, and current. The method of reflections (images)
used to facilitate solution of the wave equation, utilizes the concept
of voltage and current reflection coefficient respectively. These
concepts are used to find the v(x,t) and i(x,t) without any reference to
to power or energy. Once v(x,t) and i(x,t) are known, the power, v(x,t)
* i(x,t) can easily be calculated at any point x and time t. The
energy storage density can be calculated as i(x,t)^2 * L/2 + v(x,t)^2 *
C/2. As you might expect, the v(x,t)*i(x,t) is the derivative of the
energy storage density.

I've heard of waves without any trace of energy before,
Reg, but I certainly didn't expect to hear miracle metaphysics from you.


'Solving' the wave equation for TEM transmission lines usually means
determining the values of the v(x,t) and i(x,t) as a function of place
and time. Energy distribution, and it's movement, is easily calculated
from the knowledge of v(x,t) and i(x,t).

Whatever happened to V*I*cos(theta) being power?


Hasn't changed; works for DC out to upper microwave frequencies.

The power companies
would be surprised to learn that they are not transferring any joules/sec
to their customers.


Indeed they would. Who do you know who believes they are not
transferring energy to their customers?

bart
wb6hqk


Mike Coslo December 5th 04 06:46 PM

wrote:

"Reg Edwards" wrote in message
...

"Cecil Moore" wrote

Reg Edwards wrote:


SNIP
I wonder why I ever bothered to introduce Chipman to this newsgroup.

Try him.

----
Reg.



Reg,
This thread is purely a platform for snide remarks or for the pursuit of
appearing clever
to readers. It is not for technical education but instead it is a duking out
of smarmy comments so as to produce a suedo pecking order for onlookers
to assuage who has the most accumen with respect antenna education.


Art, I think most of us "onlookers" are just chuckling, at least those
of us who are left reading the thread.

Have you ever seen the videos of the American Prairie Chicken during
its mating ritual? That is the mental picture I keep geting from this
kind of stuff.

- Mike KB3EIA -


Richard Clark December 5th 04 06:47 PM

On Sun, 5 Dec 2004 17:30:23 +0000 (UTC), "Reg Edwards"
wrote:
You are all floundering about like fish out of water.

....
My criticism is not personal


Of course not Reggie,

But neither is it original, and if you had been following the
technical correspondence instead of the fluff offerings, you would
have observed neither of us is in danger of falling prey to all the
ills you offer cautions against. Preach to those who need redemption
and confine your comments along our technical interchanges to coin in
kind.

73's
Richard Clark, KB7QHC

Cecil Moore December 5th 04 07:49 PM

Bart Rowlett wrote:
A well
versed practioneer is familiar with the various conventions commonly in
use and will choose the one most appropriate to the problem at hand.


My point exactly, Bart. It is not up to me to define a new standard.

Indeed they would. Who do you know who believes they are not
transferring energy to their customers?


There are people who believe that energy being transferred past
a point in the transmission line is not power. However, the IEEE
dictionary says that power is the rate of generation, transfer,
or consumption of energy.
--
73, Cecil http://www.qsl.net/w5dxp

Reg Edwards December 5th 04 09:47 PM


Bart, I don't doubt that your description of how to calculate line loss is
correct.

But it's more simple than that.

The input and output currents (or voltages) of any line are very rigid and
well defined. Regardless of generator internal impedance. Just as a
transformer's input and output currents and voltages are defined.

Their ratio is even more simply defined, albeit in complex terms.

So when the line input RESISTANCE, regardless of input reactance, and the
terminating RESISTANCE, regardless of termiating reactance, are known then
the power input to power output ratio is easily directly calculated from I
squared R.

The hardest but still straightforward part of the calculation is for the
input impedance, Rin+jXin, for given line attenuation and phase shift, and
for given terminating impedance, Rt+jXt.

The power dissipated in the line, although distributed in a highly complex
manner along its length due to standing waves, is very simply Pin - Pout.

Throughout the calculations, things like reflection coefficients and SWR do
not appear, You cant use them as spin-off benefits. What practical use could
you make of them anyway? The calculations have already been done, finished,
ended, caput!
----
Reg.



Reg Edwards December 5th 04 09:47 PM

Preach to those who need redemption
and confine your comments along our technical interchanges to coin in
kind.

73's
Richard Clark, KB7QHC


==============================
I am preaching to anybody who needs redemption.

It is YOU who are taking it personally despite me explicitly letting you off
the hook.

But Rich, it's very unlike you to take cover in "off topic". ;o)
---
Reg.




All times are GMT +1. The time now is 09:03 PM.

Powered by vBulletin® Copyright ©2000 - 2025, Jelsoft Enterprises Ltd.
RadioBanter.com