RadioBanter

RadioBanter (https://www.radiobanter.com/)
-   Antenna (https://www.radiobanter.com/antenna/)
-   -   Additional Line Losses Due to SWR (https://www.radiobanter.com/antenna/2639-additional-line-losses-due-swr.html)

Robert Lay W9DMK November 25th 04 08:20 PM

Additional Line Losses Due to SWR
 
Various authors provide curves or formula for computing the "total
loss" in transmission lines, as opposed to the "matched-line" loss.
Specifically, The ARRL Antenna Book gives an equation in Chapter 24
that seems to give results consistent with other sources (See the
details at the end of this posting). However, there seems to be a
fundamental flaw in the way in which the equation is applied.

In essence, the equation provides a loss factor which is a function of
the matched-loss attenuation and the absolute reflection coefficient.
The matched-loss attenuation is the value normally expressed in dB per
100 ft. and shown in tables or shown in logarithmic plots as a
function of frequency. The reflection coefficient is introduced into
the expression in order to increase the total losses as the SWR on the
line increases.

After calculating a total loss factor it is applied to lines of any
length based on the reflection coefficient at the load. In my opinion,
it makes no sense whatsoever to provide an expression that is to
determine the losses per unit length on a line and have it based on
the reflection coefficient at the end of the line. If there is a
mismatched load, and if the line has losses, then it follows that the
SWR will become lower and lower the further we are from the
termination. That being the case, would it not make more sense to say
that the "additional" losses would be much higher at the load end of
the line, where the SWR is high, than at great distance from the load,
where the SWR is significantly lower? In fact, if the line is long
enough, we know that the SWR approaches 1:1, and in a line with an SWR
of 1:1 there should be no additional losses above the matched-line
losses.

Nonetheless, with that non-sensical approach, the numerical examples
shown at the referenced page and also in a later article on the
subject of Highly Reactive Loads makes it quite clear that the loss
factor is applied uniformly to the entire length of line.

If we take the expression for the total loss and apply it to small
increments of line wherein the SWR is relatively constant, then it not
only makes more sense, but it also predicts noticeably less total loss
in longer lines.

I have embarked on careful measurements of lines severely mismatched
(quarter wave open circuit stubs), and I can find no correlation
between my measurements and the values predicted by the "total loss"
equation. My measurements always show very low losses in comparison to
the model.

I would be interested in corresponding with anyone who has other
models for line losses, or anyone who has made measurements on
quarter-wave stubs.

##########Equation and data taken directly from The ARRL Antenna Book,
17th Ed., page 24-9 ###############
(Eq 10) Total Loss (dB) = 10 log [ {(Alpha * Alpha - (AbsRho *
AbsRho)} / {Alpha * (1- (AbsRho * AbsRho)) } ]

where

Alpha = 10^(ML/10) = matched-line loss ratio

AbsRho = (SWR - 1) / (SWR + 1)

where
ML = the matched-line loss for particular length of line, in
dB

SWR = SWR at load end of line

The text then goes on with a numeric example using a 150 ft. length of
RG-213 coax that is terminated in a 4:1 mismatch (SWR = 4:1, AbsRho =
0.6) at 14.2 MHz. The calculations for total line loss, per the above
equation, results in a total line loss of 2.107 dB.




Bob, W9DMK, Dahlgren, VA
http://www.qsl.net/w9dmk

Richard Clark November 25th 04 09:11 PM

On Thu, 25 Nov 2004 20:20:32 GMT, (Robert Lay
W9DMK) wrote:

I have embarked on careful measurements of lines severely mismatched
(quarter wave open circuit stubs), and I can find no correlation
between my measurements and the values predicted by the "total loss"
equation. My measurements always show very low losses in comparison to
the model.


Hi Bob,

Looks like our two recent postings about roughly the same topic passed
like ships in the night.

How about the numbers (your data) that leads to your suspicions?

73's
Richard Clark, KB7QHC

Robert Lay W9DMK November 25th 04 11:16 PM

On Thu, 25 Nov 2004 21:11:13 GMT, Richard Clark
wrote:

On Thu, 25 Nov 2004 20:20:32 GMT, (Robert Lay
W9DMK) wrote:

I have embarked on careful measurements of lines severely mismatched
(quarter wave open circuit stubs), and I can find no correlation
between my measurements and the values predicted by the "total loss"
equation. My measurements always show very low losses in comparison to
the model.


Hi Bob,

Looks like our two recent postings about roughly the same topic passed
like ships in the night.

How about the numbers (your data) that leads to your suspicions?

73's
Richard Clark, KB7QHC


The only one that falls immediately to hand is probably a decent
representative example. It is a piece of RG-8/U, also known by its
maker, Columbia, as 9913.

It is 5.334 meters long and is approximately 1/4 wave at 10.6 MHz,
which is where I made the measurement. In its open circuit
configuration, it measures 0.57 + j 0.3 ohms.

I am still struggling with some issues of how to interpret those
results, but two things seem to be clear - 1) the reactive component
is because I was about a degree too long for the frequency of
measurement, or there is enough stray capacitance at the open circuit
to transform into a bit of inductive reactance, and 2) the very low
resistive component doesn't seem to fit any math models that I'm
working with.

What do you think?

Bob, W9DMK, Dahlgren, VA
http://www.qsl.net/w9dmk

Dave November 26th 04 12:24 AM


"Robert Lay W9DMK" wrote in message
...
On Thu, 25 Nov 2004 21:11:13 GMT, Richard Clark
wrote:

On Thu, 25 Nov 2004 20:20:32 GMT, (Robert Lay
W9DMK) wrote:

I have embarked on careful measurements of lines severely mismatched
(quarter wave open circuit stubs), and I can find no correlation
between my measurements and the values predicted by the "total loss"
equation. My measurements always show very low losses in comparison to
the model.


Hi Bob,

Looks like our two recent postings about roughly the same topic passed
like ships in the night.

How about the numbers (your data) that leads to your suspicions?

73's
Richard Clark, KB7QHC


The only one that falls immediately to hand is probably a decent
representative example. It is a piece of RG-8/U, also known by its
maker, Columbia, as 9913.

It is 5.334 meters long and is approximately 1/4 wave at 10.6 MHz,
which is where I made the measurement. In its open circuit
configuration, it measures 0.57 + j 0.3 ohms.

I am still struggling with some issues of how to interpret those
results, but two things seem to be clear - 1) the reactive component
is because I was about a degree too long for the frequency of
measurement, or there is enough stray capacitance at the open circuit
to transform into a bit of inductive reactance, and 2) the very low
resistive component doesn't seem to fit any math models that I'm
working with.

What do you think?

Bob, W9DMK, Dahlgren, VA
http://www.qsl.net/w9dmk


the 1/4 wave open end coax looks like a short circuit at the feed point. so
your reading makes perfect sense.



Wes Stewart November 26th 04 03:51 AM

On Thu, 25 Nov 2004 20:20:32 GMT, (Robert Lay
W9DMK) wrote:

Bob,

You might want to look at this paper:

http://users.triconet.org/wesandlinda/AIEE_High_Swr.pdf



|Various authors provide curves or formula for computing the "total
|loss" in transmission lines, as opposed to the "matched-line" loss.
|Specifically, The ARRL Antenna Book gives an equation in Chapter 24
|that seems to give results consistent with other sources (See the
|details at the end of this posting). However, there seems to be a
|fundamental flaw in the way in which the equation is applied.
|
|In essence, the equation provides a loss factor which is a function of
|the matched-loss attenuation and the absolute reflection coefficient.
|The matched-loss attenuation is the value normally expressed in dB per
|100 ft. and shown in tables or shown in logarithmic plots as a
|function of frequency. The reflection coefficient is introduced into
|the expression in order to increase the total losses as the SWR on the
|line increases.
|
|After calculating a total loss factor it is applied to lines of any
|length based on the reflection coefficient at the load. In my opinion,
|it makes no sense whatsoever to provide an expression that is to
|determine the losses per unit length on a line and have it based on
|the reflection coefficient at the end of the line. If there is a
|mismatched load, and if the line has losses, then it follows that the
|SWR will become lower and lower the further we are from the
|termination. That being the case, would it not make more sense to say
|that the "additional" losses would be much higher at the load end of
|the line, where the SWR is high, than at great distance from the load,
|where the SWR is significantly lower? In fact, if the line is long
|enough, we know that the SWR approaches 1:1, and in a line with an SWR
|of 1:1 there should be no additional losses above the matched-line
|losses.
|
|Nonetheless, with that non-sensical approach, the numerical examples
|shown at the referenced page and also in a later article on the
|subject of Highly Reactive Loads makes it quite clear that the loss
|factor is applied uniformly to the entire length of line.
|
|If we take the expression for the total loss and apply it to small
|increments of line wherein the SWR is relatively constant, then it not
|only makes more sense, but it also predicts noticeably less total loss
|in longer lines.
|
|I have embarked on careful measurements of lines severely mismatched
|(quarter wave open circuit stubs), and I can find no correlation
|between my measurements and the values predicted by the "total loss"
|equation. My measurements always show very low losses in comparison to
|the model.
|
|I would be interested in corresponding with anyone who has other
|models for line losses, or anyone who has made measurements on
|quarter-wave stubs.
|
|##########Equation and data taken directly from The ARRL Antenna Book,
|17th Ed., page 24-9 ###############
|(Eq 10) Total Loss (dB) = 10 log [ {(Alpha * Alpha - (AbsRho *
|AbsRho)} / {Alpha * (1- (AbsRho * AbsRho)) } ]
|
|where
|
| Alpha = 10^(ML/10) = matched-line loss ratio
|
| AbsRho = (SWR - 1) / (SWR + 1)
|
|where
| ML = the matched-line loss for particular length of line, in
|dB
|
| SWR = SWR at load end of line
|
|The text then goes on with a numeric example using a 150 ft. length of
|RG-213 coax that is terminated in a 4:1 mismatch (SWR = 4:1, AbsRho =
|0.6) at 14.2 MHz. The calculations for total line loss, per the above
|equation, results in a total line loss of 2.107 dB.
|
|
|
|
|Bob, W9DMK, Dahlgren, VA
|http://www.qsl.net/w9dmk


Robert Lay W9DMK November 26th 04 04:19 AM

On Fri, 26 Nov 2004 00:24:13 -0000, "Dave" wrote:

the 1/4 wave open end coax looks like a short circuit at the feed point. so
your reading makes perfect sense.


Dear Dave,

Yes, I believe it does - that is, it makes perfect sense to have a low
resistance and to have a near zero reactive component. What does not
make sense is that the high SWR is supposed to produce outrageous
losses. I don't see values that I can interpret as high losses - quite
the opposite. Maybe I just don't interpret it correctly, but I would
expect it to be several ohms - not 0.57 ohms.

In fact, and this is where it gets ridiculous, the examples in the
ARRL Antenna Book would lead me to believe that the above quarter wave
line would exhibit 20 dB of total losses. In order to get those
numbers the SWR at the load of say 8000 would have to decrease to
1.01:1 at the source end in order to account for 20 dB in losses. (See
the example on page 24-9 of the 17th Edition.)


Bob, W9DMK, Dahlgren, VA
http://www.qsl.net/w9dmk

Robert Lay W9DMK November 26th 04 04:20 AM

On Thu, 25 Nov 2004 23:16:21 GMT, (Robert Lay
W9DMK) wrote:
The only one that falls immediately to hand is probably a decent
representative example. It is a piece of RG-8/U, also known by its
maker, Columbia, as 9913.


Don't ask me where I got that number - it's Columbia's number 1198 -
not 9913.

Bob, W9DMK, Dahlgren, VA
http://www.qsl.net/w9dmk

Richard Clark November 26th 04 07:33 AM

On Fri, 26 Nov 2004 04:19:06 GMT, (Robert Lay
W9DMK) wrote:

What does not
make sense is that the high SWR is supposed to produce outrageous
losses. I don't see values that I can interpret as high losses - quite
the opposite. Maybe I just don't interpret it correctly, but I would
expect it to be several ohms - not 0.57 ohms.


Hi Bob,

Thanx for the explicit results. Now what is needed is the explicit
expectation. I note that you circumspectly describe it as being
ARRL Antenna Book would lead me to believe that the above quarter wave
line would exhibit 20 dB of total losses. In order to get those
numbers the SWR at the load of say 8000 would have to decrease to
1.01:1 at the source end in order to account for 20 dB in losses. (See
the example on page 24-9 of the 17th Edition.)

which is an inference which being an interpretation is open to errors
of mis-interpretation.

Reference Data for Radio Engineers, "Mismatch and Transducer Loss,"
"One End Mismatched," pg. 22-12:
Transducer Loss = A0 + 10 · log (Pm/P) decibels
where
A0 = normal attenuation of the line
Pm = power that would be delivered were system matched
P = power delivered to the load

Of particular note is that this is one of my references as to the
nature of Source Z which is often neglected in academic treatments
with the presumption that the engineer has already been schooled in
the nature of Real sources (this may shock some complaisant readers
here). However, this citation offers that explicit lesson in figure
10 and makes use of this commonplace characteristic in illustrations
of Mismatch Uncertainty. They go as far as to explicitly offer a
section entitled "Generator and Load Mismatched." You may wish to
review this treatment as it offers the math that would present the
most loss available in a line, above and beyond the typical charts
offered for line loss (which are confined to both ends being matched).

73's
Richard Clark, KB7QHC

Dave November 26th 04 12:11 PM


"Robert Lay W9DMK" wrote in message
...
On Fri, 26 Nov 2004 00:24:13 -0000, "Dave" wrote:

the 1/4 wave open end coax looks like a short circuit at the feed point.

so
your reading makes perfect sense.


Dear Dave,

Yes, I believe it does - that is, it makes perfect sense to have a low
resistance and to have a near zero reactive component. What does not
make sense is that the high SWR is supposed to produce outrageous
losses. I don't see values that I can interpret as high losses - quite
the opposite. Maybe I just don't interpret it correctly, but I would
expect it to be several ohms - not 0.57 ohms.

In fact, and this is where it gets ridiculous, the examples in the
ARRL Antenna Book would lead me to believe that the above quarter wave
line would exhibit 20 dB of total losses. In order to get those
numbers the SWR at the load of say 8000 would have to decrease to
1.01:1 at the source end in order to account for 20 dB in losses. (See
the example on page 24-9 of the 17th Edition.)


the cases they talk about in there are figuring the loss in power that you
would be supplying to a load. in your case the load is an infinite
resistance so it receives zero power which is what the arrl book says... in
this case all the power that is sent down the line is reflected back minus a
little bit of heating so the swr at the feedpoint should be near infinite,
but not quite. the actual loss in the wave going down and coming back is
very small hence the very low impedance. this is an effect that is used to
make coaxial stub filters and transformers.



Robert Lay W9DMK November 26th 04 04:12 PM

On Thu, 25 Nov 2004 20:51:16 -0700, Wes Stewart
wrote:

On Thu, 25 Nov 2004 20:20:32 GMT, (Robert Lay
W9DMK) wrote:

Bob,

You might want to look at this paper:

http://users.triconet.org/wesandlinda/AIEE_High_Swr.pdf



Dear Wes,

I have downloaded the pdf file and printed it out. It's tough reading.
I hope that MacAlpine agrees with what Dave and Richard are telling
me, because their responses seem to be correct and are exactly what I
was afraid of - that I've been sucked into another example of the
strange terminology used to describe "losses".

I have always thought of "loss" as a conversion to another form of
energy (typically heat energy) which is lost from the system.
Apparently, the kind of "loss" being described in the example that I
gave is not a loss at all. It's more like "return loss", which is also
not a true "loss" in my thinking. In other words, it seems that the
"Additional Losses Due to SWR" are not losses at all, but are simply a
measure of the power that "could" have been delivered to the load were
it not for the mis-match.
Bob, W9DMK, Dahlgren, VA
http://www.qsl.net/w9dmk

Cecil Moore November 26th 04 04:38 PM

(Robert Lay W9DMK) wrote:
Yes, I believe it does - that is, it makes perfect sense to have a low
resistance and to have a near zero reactive component. What does not
make sense is that the high SWR is supposed to produce outrageous
losses. I don't see values that I can interpret as high losses - quite
the opposite. Maybe I just don't interpret it correctly, but I would
expect it to be several ohms - not 0.57 ohms.


Hi Bob, I'm still at my relatives' house posting through Google. I'll
expand on this when I get back to my computer.

Those equations in The ARRL Antenna Book (15th Edition) make an assumption
that may or may not be true - I don't know. What they are assuming is that
the losses are due to the additional power associated with high SWR. In
general, if the forward power is 100w for the matched case and the sum
of the forward and reflected power is 300w for the unmatched case, the
losses will be three times higher for the unmatched case. That seems a
reasonable assumption. However, rho at the shorted or open end of a stub
is equal to |1| so rho^2 will be equal to 1. That puts (1-rho^2) = 0 in
the denominator of the equation and makes the addditional losses undefined.

In fact, and this is where it gets ridiculous, the examples in the
ARRL Antenna Book would lead me to believe that the above quarter wave
line would exhibit 20 dB of total losses. In order to get those
numbers the SWR at the load of say 8000 would have to decrease to
1.01:1 at the source end in order to account for 20 dB in losses. (See
the example on page 24-9 of the 17th Edition.)


Here's an example. Assume 100w is delivered to the load for both the
matched and unmatched conditions. Assume 3dB matched line loss in the
transmission line. Assume an SWR of 5.83:1 (rho=0.707) at the load for
the mismatched condition.

Forward 200w------------3dB loss-------------Matched Load 100w


Forward 400w------------3dB loss-------------Mismatched Load 100w
Reflected 50w both Forward 200w
directions Reflected 100w

The equations gives an additional loss of 5.44dB. This is based on an
assumption that the losses are directly proportional to forward power
plus reflected power.

Remember that at the mouth of the stub, the impedance is equal to
(Vf + Vr)/(If + Ir) so, knowing the Z0, that should allow you to
calculate those four values existing at the mouth of the stub. From
that, you can calculate the total losses. More when I get back.
--
73, Cecil, W5DXP

Wes Stewart November 26th 04 05:57 PM

On Fri, 26 Nov 2004 16:12:34 GMT, (Robert Lay
W9DMK) wrote:

|On Thu, 25 Nov 2004 20:51:16 -0700, Wes Stewart
|wrote:
|
|On Thu, 25 Nov 2004 20:20:32 GMT,
(Robert Lay
|W9DMK) wrote:
|
|Bob,
|
|You might want to look at this paper:
|
|
http://users.triconet.org/wesandlinda/AIEE_High_Swr.pdf
|
|
|Dear Wes,
|
|I have downloaded the pdf file and printed it out. It's tough reading.

Yes. But the ITT Reference Data For Radio Engineers uses this paper
as a reference.

If you have Mathcad, a sheet that implements some of the equations was
included as a reference in my Balanced Transmission line paper.

http://users.triconet.org/wesandlinda/LineCalc.mcd


|I hope that MacAlpine agrees with what Dave and Richard are telling
|me, because their responses seem to be correct and are exactly what I
|was afraid of - that I've been sucked into another example of the
|strange terminology used to describe "losses".
|
|I have always thought of "loss" as a conversion to another form of
|energy (typically heat energy) which is lost from the system.
|Apparently, the kind of "loss" being described in the example that I
|gave is not a loss at all.

Yes it is. A simple-minded way of looking at it is if the SWR is
greater than unity then increased current is flowing in the line. The
line has resistive loss, so the I^2*R loss increases. The current
isn't constant (there is a current standing ratio, ISWR, just like a
VSWR) so there are peaks and valleys in the current and as you have
figured out, the longer the line and the higher its nominal loss, the
lower the ISWR is at the line input.

So the loss per unit length is non-linear and varies with distance
from the mismatch, but it is a real dissipative loss.

For those interested in the loss in the shorted or open stub case,
maybe this will be of interest:

http://users.triconet.org/wesandlind...ching_Loss.pdf



George, W5YR November 27th 04 05:16 AM

Keep in mind that real ohmic and dielectric losses measured in watts depend
upon sqrt(SWR). Thus, the higher the SWR (load mismatch) the greater the
I^2R losses in the conductors and similarly in the dielectric.

So, to me, a non-unity SWR connotes real power loss measurable in watts and
attributable to well-known loss mechanisms.

Of course, any real power lost in the line materials represents power not
delivered to the load, so this fits somewhat with the viewpoint that
Line Loss is in fact the magnitude of power undelivered to the load due to
the mismatch. But, I think that we are looking at real watts of loss here.

Another confusing factor is that one is usually interested in the total loss
attributable to the use of a mismatched line and not especially in how that
loss is distributed along the line from load to source. But there are
applications where the loss distribution with line length is of concern. An
example is the case of a complex Zo with rho unity in which the majority
of the power loss occurs in the section of the line nearest the load and
decreases toward the source. In that case of probably limited application,
the line nearest the load might be required to handle more power than that
further toward the source.

A somewhat related example concerns the W2DU balun in which is it observed
that the beads nearest the mismatched load endure the largest heat
dissipation and are commonly larger that the remainder further toward the
source.

However, since complex Zo is an issue of magnitude usually only at low r-f
and more so at audio frequencies, this is seldom a practical consideration.

Thanks for bringing this topic to light, Bob. Like most engineers, I have
been guilty of looking at "line loss" as a monolithic phenomenon and not
being concerned with the micro-structure of its distribution.

--
73, George W5YR
Fairview, TX

http://www.w5yr.com


"Robert Lay W9DMK" wrote in message
...
On Thu, 25 Nov 2004 20:51:16 -0700, Wes Stewart
wrote:

On Thu, 25 Nov 2004 20:20:32 GMT, (Robert Lay
W9DMK) wrote:

Bob,

You might want to look at this paper:

http://users.triconet.org/wesandlinda/AIEE_High_Swr.pdf



Dear Wes,

I have downloaded the pdf file and printed it out. It's tough reading.
I hope that MacAlpine agrees with what Dave and Richard are telling
me, because their responses seem to be correct and are exactly what I
was afraid of - that I've been sucked into another example of the
strange terminology used to describe "losses".

I have always thought of "loss" as a conversion to another form of
energy (typically heat energy) which is lost from the system.
Apparently, the kind of "loss" being described in the example that I
gave is not a loss at all. It's more like "return loss", which is also
not a true "loss" in my thinking. In other words, it seems that the
"Additional Losses Due to SWR" are not losses at all, but are simply a
measure of the power that "could" have been delivered to the load were
it not for the mis-match.
Bob, W9DMK, Dahlgren, VA
http://www.qsl.net/w9dmk




Frank November 27th 04 06:03 PM

Modeling a free space dipole made from a lossless conductor, 100 ft in
length, at 1.8 MHz shows an input impedance of 6.694 - j1621 Ohms. As
expected the radiation efficiency is 100%.

Adding 300 ft of 600 Ohm, 6" spaced, copper open wire transmission line
degrades the radiation efficiency to 16.75 %. The result, therefore
indicates a transmission line loss of 7.76 dB. The input impedance is
calculated as 11 - j619.7 Ohms.

The ARRL, DOS based program, "TL" computes, for 300 ft of 600 Ohm line
terminated with 6.694 - j1621 Ohms, a loss of 8.19 dB, and an input
impedance of 18.35 - j805 Ohms.

Realizing that 6" spaced, #14 AWG, is not exactly 600 Ohms, and NEC's
computation of parallel wire transmission lines is not 100% accurate; the
results do seem to confirm the validity of the ARRL's program.

Another interesting experiment with the ARRL's program also seems to verify
its accuracy:

RG8, 1000 ft, frequency 100 MHz. Matched line loss = 24.82 dB.
Load impedance 1 - j1000 Ohms. Total line loss = 61.82 dB.
The program computes the input impedance to by: 50.3 - j0.2 Ohms.

73,

Frank


"George, W5YR" wrote in message
...
Keep in mind that real ohmic and dielectric losses measured in watts
depend
upon sqrt(SWR). Thus, the higher the SWR (load mismatch) the greater the
I^2R losses in the conductors and similarly in the dielectric.

So, to me, a non-unity SWR connotes real power loss measurable in watts
and
attributable to well-known loss mechanisms.

Of course, any real power lost in the line materials represents power not
delivered to the load, so this fits somewhat with the viewpoint that
Line Loss is in fact the magnitude of power undelivered to the load due to
the mismatch. But, I think that we are looking at real watts of loss here.

Another confusing factor is that one is usually interested in the total
loss
attributable to the use of a mismatched line and not especially in how
that
loss is distributed along the line from load to source. But there are
applications where the loss distribution with line length is of concern.
An
example is the case of a complex Zo with rho unity in which the majority
of the power loss occurs in the section of the line nearest the load and
decreases toward the source. In that case of probably limited application,
the line nearest the load might be required to handle more power than that
further toward the source.

A somewhat related example concerns the W2DU balun in which is it observed
that the beads nearest the mismatched load endure the largest heat
dissipation and are commonly larger that the remainder further toward the
source.

However, since complex Zo is an issue of magnitude usually only at low r-f
and more so at audio frequencies, this is seldom a practical
consideration.

Thanks for bringing this topic to light, Bob. Like most engineers, I have
been guilty of looking at "line loss" as a monolithic phenomenon and not
being concerned with the micro-structure of its distribution.

--
73, George W5YR
Fairview, TX

http://www.w5yr.com


"Robert Lay W9DMK" wrote in message
...
On Thu, 25 Nov 2004 20:51:16 -0700, Wes Stewart
wrote:

On Thu, 25 Nov 2004 20:20:32 GMT, (Robert Lay
W9DMK) wrote:

Bob,

You might want to look at this paper:

http://users.triconet.org/wesandlinda/AIEE_High_Swr.pdf



Dear Wes,

I have downloaded the pdf file and printed it out. It's tough reading.
I hope that MacAlpine agrees with what Dave and Richard are telling
me, because their responses seem to be correct and are exactly what I
was afraid of - that I've been sucked into another example of the
strange terminology used to describe "losses".

I have always thought of "loss" as a conversion to another form of
energy (typically heat energy) which is lost from the system.
Apparently, the kind of "loss" being described in the example that I
gave is not a loss at all. It's more like "return loss", which is also
not a true "loss" in my thinking. In other words, it seems that the
"Additional Losses Due to SWR" are not losses at all, but are simply a
measure of the power that "could" have been delivered to the load were
it not for the mis-match.
Bob, W9DMK, Dahlgren, VA
http://www.qsl.net/w9dmk






Robert Lay W9DMK November 27th 04 09:43 PM

On Fri, 26 Nov 2004 07:33:04 GMT, Richard Clark
wrote:

.....snip
Reference Data for Radio Engineers, "Mismatch and Transducer Loss,"
"One End Mismatched," pg. 22-12:
Transducer Loss = A0 + 10 · log (Pm/P) decibels
where
A0 = normal attenuation of the line
Pm = power that would be delivered were system matched
P = power delivered to the load

Of particular note is that this is one of my references as to the
nature of Source Z which is often neglected in academic treatments
with the presumption that the engineer has already been schooled in
the nature of Real sources (this may shock some complaisant readers
here). However, this citation offers that explicit lesson in figure
10 and makes use of this commonplace characteristic in illustrations
of Mismatch Uncertainty. They go as far as to explicitly offer a
section entitled "Generator and Load Mismatched." You may wish to
review this treatment as it offers the math that would present the
most loss available in a line, above and beyond the typical charts
offered for line loss (which are confined to both ends being matched).


Dear Richard,

I'm finally ready to comment on the above - it is my great fortune to
be blessed with copies of both the Fourth and Fifth Editions of the
ITT Handbook.

I studied over the first 13 pages of Chapter 22 and found that, just
as Wes said, it's entirely the work of MacAlpine as published in 1953.

I went over Equations (1) through (4) in the Mismatch section very
carefully and found no heartburn with anything in that section. This
is NOT to say that I LIKE it, but I do understand it and have no
problem with the math model and the figures. My problems with the two
mismatch topics is simply that I just don't like to call it a loss
when energy that COULD have been delivered to the load does NOT get
delivered to the load as a result of mismatch. For me, lost energy in
a transmission line problem is energy actually lost in the
transmission line, not energy that is being lost elsewhere as a result
of the transmission line not being matched properly. I realize that
I'm probably alone in that thinking, but I like to feel that such
terms as efficiency and losses should be associated strongly with the
item under evaluation, namely the transmission line, and not the
ancillary equipment which feed it or terminate it. Those items get
their own hearings relative to efficiency and losses and those
evaluations do not require the presence of the transmission line. In
fact, those items are usually evaluated as to their performance in
ways that do not in any way relate to how well some transmission line
is or is not working.

However, this is not the nub of the problem that I was encountering -
a problem which has now been partly resolved. At least I think I have
a far, far better understanding of the problem now than I had a few
days ago. The problem centers on the Additional Losses Due to SWR and
how to model them. Since it is, perhaps, more appropriate to continue
that topic under the responses from Wes, I will not go into it here.

I want to thank you and Wes, both, for leading me to Chapter 22 - it
is much more readable than MacAlpine's original paper.

Bob, W9DMK, Dahlgren, VA
http://www.qsl.net/w9dmk

Robert Lay W9DMK November 27th 04 09:43 PM

On Fri, 26 Nov 2004 10:57:25 -0700, Wes Stewart
wrote:


Yes. But the ITT Reference Data For Radio Engineers uses this paper
as a reference.

If you have Mathcad, a sheet that implements some of the equations was
included as a reference in my Balanced Transmission line paper.

http://users.triconet.org/wesandlinda/LineCalc.mcd



Dear Wes,

I was happy to find that the MacAlpine paper is the first part of
Chapter 22 of the ITT Handbook, as the latter is much more readable.

I did not pick up on the MathCad files, because I do not have MathCd -
however, the material from MacAlpine and Ricardi have answered most of
my concerns.


|I hope that MacAlpine agrees with what Dave and Richard are telling
|me, because their responses seem to be correct and are exactly what I
|was afraid of - that I've been sucked into another example of the
|strange terminology used to describe "losses".
|
|I have always thought of "loss" as a conversion to another form of
|energy (typically heat energy) which is lost from the system.
|Apparently, the kind of "loss" being described in the example that I
|gave is not a loss at all.


I was premature in those two paragraphs, above. I can see now that the
Additional Losses Due to SWR really are dissipative and are unrelated
to the "Mismatch Losses" and "Transducer Losses" defined on page 22-12
of the ITT Handbook, 5th Ed.


Yes it is. A simple-minded way of looking at it is if the SWR is
greater than unity then increased current is flowing in the line. The
line has resistive loss, so the I^2*R loss increases. The current
isn't constant (there is a current standing ratio, ISWR, just like a
VSWR) so there are peaks and valleys in the current and as you have
figured out, the longer the line and the higher its nominal loss, the
lower the ISWR is at the line input.


My interpretation of your "Yes it is." is that you mean that the
Additional Losses Due to SWR are truly heat losses and are due to the
ohmic losses in the hot spots of the line. Then we agree on that
point. Your paragraph above is much more succinct than the papers by
MacAlpine and Ricardi, but it certainly tells the story.

So the loss per unit length is non-linear and varies with distance
from the mismatch, but it is a real dissipative loss.


I don't know that I would have used the term "non-linear", but I would
certainly agree that it varies along the line in accordance with the
current loops.

For those interested in the loss in the shorted or open stub case,
maybe this will be of interest:
http://users.triconet.org/wesandlind...ching_Loss.pdf


I took that pdf and added it to the collection. There were several
things about that paper that filled-in gaps of detail in MacAlpine.
However, neither paper gives us much hope for a simple model of these
losses. Nonetheless, it makes hash out of the material in The ARRL
Antenna Book. In all fairness, the Antenna Book cannot cover all
aspects of these topics in detail. Unfortunately, the material in the
Antenna Book is, in my opinion, very misleading in several specific
areas, as follows:
- The Antenna Book gives only one expression for Total Line
Loss (combining ML loss and the Additional Loss Due to SWR). If we
accept Macalpine's model, there are different relationships for the
range of SWR from 0 to 6 and for the range from 6 upwards.
- Antenna Book does not explain that the hot spots are very
localized and that the additional losses can be quite dependant upon
the length of the line in wavelengths. For example, the losses in a
segment of line less than 1/3 wavelength might be insignificant in
comparison with a segment of line greater than 1/3 wavelength simply
because the shorter segment may not contain a hot spot. In other
words, one cannot apply the Antenna Book equations, blindly, because
of several factors that are not even mentioned, and for short line
segments it is quite possible that there would be no signicant losses
due to SWR.
- The most misleading information in The Antenna Book is on
pages 24-11 and 24-12 where it is shown that a 100 foot RG-213
feedline will suffer 25 dB of Additional Loss Due to SWR at 1.83 MHz
because of the very short antenna. I believe that when the equations
from the ITT Handbook are used instead, that the actual losses will be
far, far less.

Just today, I made a careful measurement on an RG-8/U line of 5.33
meters length at 30 MHz and terminated with a 4700 + j 0 load. The
Matched Line Loss of that line at 30 MHz is 0.9 dB per 100 feet, and
its Velocity Factor is between 0.75 and 0.80 The input impedance was
actually measured at 2.45 -j15 ohms for an SWR at the input of 22.25.
The SWR at the load end was 94. Those two SWR's establish a total loss
on the line of 0.15 dB. If one were to blindly apply the formula in
The Antenna Book on page 24-9, the result obtained would be 4.323 dB.


Bob, W9DMK, Dahlgren, VA
http://www.qsl.net/w9dmk

Cecil Moore November 28th 04 03:38 PM

Robert Lay W9DMK wrote:
Just today, I made a careful measurement on an RG-8/U line of 5.33
meters length at 30 MHz and terminated with a 4700 + j 0 load. The
Matched Line Loss of that line at 30 MHz is 0.9 dB per 100 feet, and
its Velocity Factor is between 0.75 and 0.80 The input impedance was
actually measured at 2.45 -j15 ohms for an SWR at the input of 22.25.
The SWR at the load end was 94. Those two SWR's establish a total loss
on the line of 0.15 dB. If one were to blindly apply the formula in
The Antenna Book on page 24-9, the result obtained would be 4.323 dB.


For your 1/4WL open stub on 10.6 MHz, with a stub impedance of 0.57 ohms,
I calculate total losses of about 0.2 dB.
--
73, Cecil http://www.qsl.net/w5dxp

Robert Lay W9DMK November 28th 04 05:22 PM

On Sun, 28 Nov 2004 09:38:28 -0600, Cecil Moore
wrote:

Robert Lay W9DMK wrote:
Just today, I made a careful measurement on an RG-8/U line of 5.33
meters length at 30 MHz and terminated with a 4700 + j 0 load. The
Matched Line Loss of that line at 30 MHz is 0.9 dB per 100 feet, and
its Velocity Factor is between 0.75 and 0.80 The input impedance was
actually measured at 2.45 -j15 ohms for an SWR at the input of 22.25.
The SWR at the load end was 94. Those two SWR's establish a total loss
on the line of 0.15 dB. If one were to blindly apply the formula in
The Antenna Book on page 24-9, the result obtained would be 4.323 dB.


For your 1/4WL open stub on 10.6 MHz, with a stub impedance of 0.57 ohms,
I calculate total losses of about 0.2 dB.
--
73, Cecil http://www.qsl.net/w5dxp


Dear Cecil,

I hope I'm not misinterpreting your values - I assume that you are
starting with a theoretical open circuit and a theoretical RG-8 line
and calculating a theoretical impedance seen looking into that line of
0.57 + j 0. From that you then calculate a theoretical 0.2 dB. When I
say calculate, I assume that you may instead by using a nomogram.
Anyway, based on all of that being the situation up to but not
including the loss figure, when I take the 0.57 + j0 and calculate the
SWR as 87.7 I get a loss more like .05 dB, theoretically, so I'm not
sure in what ways we are coming up with these numbers. I can explain
exactly how I got mine, which was via measurements followed by a
theoretical cacluation of loss based on the two SWR's formula which is
built into all Smith Charts.

Bob, W9DMK, Dahlgren, VA
http://www.qsl.net/w9dmk

Richard Clark November 28th 04 06:41 PM

On Sat, 27 Nov 2004 21:43:14 GMT, (Robert Lay
W9DMK) wrote:

I can see now that the
Additional Losses Due to SWR really are dissipative and are unrelated
to the "Mismatch Losses" and "Transducer Losses" defined on page 22-12
of the ITT Handbook, 5th Ed.


Hi Bob,

I've let this simmer for a while, but I have to return to this because
you've erred in interpretation of this particular page and those
particular subjects. They are entirely caloric losses, not what you
dismiss as the myth of mismatch loss.

You need only review the math offered to observe they use the
conventional "real" line loss and add more "real" line loss in
proportion to the reflections at either one or two interfaces. The
equations are quite literal to this and explicitly state:
A0 = normal attenuation of line

If you want deeper math, one source can be found in Chipman's (as
unread as any here) "Transmission Lines."

This is yet another of my references that attend to my recent, short
thread on the nature of power determination error, and mismatched
loads AND sources. In fact ALL of these references I've offered
explicitly describe that the source MUST be matched for ANY of these
equations about transmission lines bandied about to accurately offer
true answers. The naive presumptions that Source Z is immaterial to
the outcome of analysis is quite widespread here.

Chipman offers the rigorous math that attends explicitly to the Smith
Chart loss nomograph you reference elsewhere in this thread. If you
lack access to this work, I can munge up the equations here for you.
I will add, this math is for "lossless" lines, as is the implication
of the Smith Chart nomograph; but it only requires you to add that in
for yourself by restructuring the math to include loss. At that level
of granularity, it won't be pretty; but you can rest assured it will
be complete.

73's
Richard Clark, KB7QHC

Cecil Moore November 28th 04 07:28 PM

Robert Lay W9DMK wrote:
..For your 1/4WL open stub on 10.6 MHz, with a stub impedance of 0.57 ohms,
I calculate total losses of about 0.2 dB.


I hope I'm not misinterpreting your values - I assume that you are
starting with a theoretical open circuit and a theoretical RG-8 line
and calculating a theoretical impedance seen looking into that line of
0.57 + j 0. From that you then calculate a theoretical 0.2 dB. When I
say calculate, I assume that you may instead by using a nomogram.


Not using a nomogram but everything is 100% theoretical. It doesn't
matter what line is being used as long as it's Z0 is 50 ohms. Matched
line loss didn't enter into my calculations. It's only total loss.

Anyway, based on all of that being the situation up to but not
including the loss figure, when I take the 0.57 + j0 and calculate the
SWR as 87.7 I get a loss more like .05 dB, theoretically, so I'm not
sure in what ways we are coming up with these numbers.


Is that the additional loss due to SWR or the total loss? My theoretical
loss is total loss and the matched line loss need not be known. The
measured resistance of the resonant stub is all one needs to know besides
Z0.

I can explain
exactly how I got mine, which was via measurements followed by a
theoretical cacluation of loss based on the two SWR's formula which is
built into all Smith Charts.


I can't remember where the following formula came from. I think it
was from an RF guru at Intel, but I can't be sure. I have a hand-
written notebook of useful formulas covering 25 years but I didn't
record where they all came from.

The formula for theoretical TOTAL losses in a *resonant* stub:

Total loss = 10*log{[(Z0-R)/(Z0+R)]^2}

where R is the measured resistance of the resonant stub and Z0
is the characteristic impedance of the stub material. You can
see the [(Z0-R)/(Z0+R)]^2 term is akin to a virtual rho^2 at
the mouth of the stub. Since rho^2 = Pref/Pfor, the losses in
the stub are equivalent to the losses in an equivalent resistance
equal to the measured virtual resistance at the mouth of the stub.
--
73, Cecil http://www.qsl.net/w5dxp

Cecil Moore November 28th 04 09:00 PM

Cecil Moore wrote:
The formula for theoretical TOTAL losses in a *resonant* stub:

Total loss = 10*log{[(Z0-R)/(Z0+R)]^2}

where R is the measured resistance of the resonant stub and Z0
is the characteristic impedance of the stub material. You can
see the [(Z0-R)/(Z0+R)]^2 term is akin to a virtual rho^2 at
the mouth of the stub. Since rho^2 = Pref/Pfor, the losses in
the stub are equivalent to the losses in an equivalent resistance
equal to the measured virtual resistance at the mouth of the stub.


In other words, replace the stub with a resistor having the same
value of measured resistance as the stub, and calculate the I^2*R
losses in the resistor. That will be the same value as the total
losses in the stub.
--
73, Cecil http://www.qsl.net/w5dxp

Wes Stewart November 28th 04 11:53 PM

On Sun, 28 Nov 2004 18:41:44 GMT, Richard Clark
wrote:

|On Sat, 27 Nov 2004 21:43:14 GMT, (Robert Lay
|W9DMK) wrote:
|
| I can see now that the
|Additional Losses Due to SWR really are dissipative and are unrelated
|to the "Mismatch Losses" and "Transducer Losses" defined on page 22-12
|of the ITT Handbook, 5th Ed.
|
|Hi Bob,
|
|I've let this simmer for a while, but I have to return to this because
|you've erred in interpretation of this particular page and those
|particular subjects. They are entirely caloric losses, not what you
|dismiss as the myth of mismatch loss.
|
|You need only review the math offered to observe they use the
|conventional "real" line loss and add more "real" line loss in
|proportion to the reflections at either one or two interfaces. The
|equations are quite literal to this and explicitly state:
| A0 = normal attenuation of line
|
|If you want deeper math, one source can be found in Chipman's (as
|unread as any here) "Transmission Lines."
|
|This is yet another of my references that attend to my recent, short
|thread on the nature of power determination error, and mismatched
|loads AND sources. In fact ALL of these references I've offered
|explicitly describe that the source MUST be matched for ANY of these
|equations about transmission lines bandied about to accurately offer
|true answers. The naive presumptions that Source Z is immaterial to
|the outcome of analysis is quite widespread here.
|
|Chipman offers the rigorous math that attends explicitly to the Smith
|Chart loss nomograph you reference elsewhere in this thread. If you
|lack access to this work, I can munge up the equations here for you.

Richard,

If you wouild cite the pages to which you refer, I would gladly scan
then to pdf and post them for all to reference.

Wes


|I will add, this math is for "lossless" lines, as is the implication
|of the Smith Chart nomograph; but it only requires you to add that in
|for yourself by restructuring the math to include loss. At that level
|of granularity, it won't be pretty; but you can rest assured it will
|be complete.
|
|73's
|Richard Clark, KB7QHC


Robert Lay W9DMK November 29th 04 12:02 AM

On Sun, 28 Nov 2004 18:41:44 GMT, Richard Clark
wrote:

On Sat, 27 Nov 2004 21:43:14 GMT, (Robert Lay
W9DMK) wrote:

I can see now that the
Additional Losses Due to SWR really are dissipative and are unrelated
to the "Mismatch Losses" and "Transducer Losses" defined on page 22-12
of the ITT Handbook, 5th Ed.


Hi Bob,

I've let this simmer for a while, but I have to return to this because
you've erred in interpretation of this particular page and those
particular subjects. They are entirely caloric losses, not what you
dismiss as the myth of mismatch loss.

You need only review the math offered to observe they use the
conventional "real" line loss and add more "real" line loss in
proportion to the reflections at either one or two interfaces. The
equations are quite literal to this and explicitly state:
A0 = normal attenuation of line



I goofed on the part that is talking about transducer loss. I should
NOT have included the "Transducer Losses" in my statement above. The
Transducer losses do, as you say, include the normal attenuation of
the line, which is indeed a dissipative loss.

If you want deeper math, one source can be found in Chipman's (as
unread as any here) "Transmission Lines."

This is yet another of my references that attend to my recent, short
thread on the nature of power determination error, and mismatched
loads AND sources. In fact ALL of these references I've offered
explicitly describe that the source MUST be matched for ANY of these
equations about transmission lines bandied about to accurately offer
true answers. The naive presumptions that Source Z is immaterial to
the outcome of analysis is quite widespread here.

Chipman offers the rigorous math that attends explicitly to the Smith
Chart loss nomograph you reference elsewhere in this thread. If you
lack access to this work, I can munge up the equations here for you.
I will add, this math is for "lossless" lines, as is the implication
of the Smith Chart nomograph; but it only requires you to add that in
for yourself by restructuring the math to include loss. At that level
of granularity, it won't be pretty; but you can rest assured it will
be complete.


I'm not sure what you are saying about the loss nomograph on the Smith
Chart. If that's wrong too, then we're in big trouble. Everything ever
written that I have seen about the Smith Charts agrees that the actual
losses in the transmission line are indicated by the collapsing of the
circle as one traverses the transmission line. All you have to do is
read the "loss in 1 dB steps" scale to determine those losses.


Bob, W9DMK, Dahlgren, VA
http://www.qsl.net/w9dmk

Richard Clark November 29th 04 12:28 AM

On Sun, 28 Nov 2004 16:53:59 -0700, Wes Stewart
wrote:

If you wouild cite the pages to which you refer, I would gladly scan
then to pdf and post them for all to reference.


Hi Wes,

The math is on the bottom of pg. 203 which is supporting Fig. 9-26.

There is also a section entitled 8.8 Multiple reflections on ppg
174...176.

Then there is the specific math of fully specified matches at both
ends, that is at the source and the load, found in Fig. 10-7 that is
supported by discussion on ppg. 225...227.

All of this bears on discussion around and about the necessary
treatment of the Z of the Source, but I haven't supplied all the
citations within this one reference by any means.

Thanx, Wes. You needn't do all these scans. The group needs to do
their own heavy lifting to escape their naivety about source Z.

73's
Richard Clark, KB7QHC

Richard Clark November 29th 04 01:08 AM

On Mon, 29 Nov 2004 00:02:10 GMT, (Robert Lay
W9DMK) wrote:
I'm not sure what you are saying about the loss nomograph on the Smith
Chart. If that's wrong too, then we're in big trouble.


Hi Bob,

Chipman devotes an entire chapter on the Smith Chart, covering each
scale completely (I wonder why Reg thinks it would take so many months
to accumulate this information if he, as he alludes, is already aware
of Chipman's work.).

However, the nomograph discusses nothing in terms of any particular
line's dissipative loss as that is outside of purpose of the chart.
I'm afraid you are back in the mythical mismatch loss there. When Wes
puts that particular page online, then perhaps you may find a way to
fully describe your situation - including loss specific to your tests.

Chipman states quite bluntly:
"IF the transmission line of Fig. 9-26 is lossless...."

The point of my posts is that few actually read this material to
appreciate the very carefully stated premises. The problems arise
when derivative work is used as a source wherein that author presumes
that the reader is educated in the particulars that go left unsaid....
like all Sources' Z MUST match the line for any analysis to be valid.
Instead we get these trivializations of the matter that this is only a
concern inhabiting only specialty sources in specialty labs.

However, as applied to your recent work, the degree of mismatch
offered by your source is low enough to be negligible; but as you are
not aware of its degree, then neither are you aware of the scope of
your error.

73's
Richard Clark, KB7QHC

Reg Edwards November 29th 04 04:09 AM

Just a few meandering thoughts -

For anyone assembling a collection of exact transmission line formulae, of
which there are dozens, some more applicable to practical problems than
others, it is best to begin with the most commonly used and the most
complicated formulae. Don't incorporate approximate formulae or you will
later wish that you hadn't.

Clear your minds of superfluous Smith Charts, standing waves, reflected
power, virtual short circuits, conjugate matches, etc. A clear understanding
of how transmission lines work is essential. You should be familiar with
complex hyperbolic functions. Only metric line dimensions should be used.

What are required are calculating procedures which accepts all possible
input data and finish with preferably a single number. In some cases, if not
needed, input data can be set to zero but the facility must exist.

You will then have designed a set of step-by-step routines as in computer
programs but which can be tediously and logically worked through with a
pocket calculator. The number of intermediate variables can be large. But
there can be only one unambiguous straight-line path through subroutines.

For example, in a large number of cases the single output quantity is
related to line loss, such as insertion loss in dB, or load power in watts,
or transmission efficiency in percent, or percent of input power lost in the
line itself.

But before this can be calculated it is essential to calculate input
impedance Rin+jXin for given attenuation in dB or nepers, given phase shift
in radians and given terminating impedance Rt+jXt. Then include generator
impedance Rg+jXg and internal generator volts. Having done this you are
half-way through.

Some intermediate results may be useful. Such as input impedance which
terminates a tuner or provides a source for a receiver.

Such intermediate results as reflection coefficient magnitudes and angles
may be explicitly available but may be of no practical use. What can you do
with them? The calculation is already complete. You might find an SWR
somewhere in there if you recognise it but who cares.

Well, you get the idea. But if you had the source codings of some of my
programs I can assure you they would not be of the slightest use. You may
just as well start at the begining. There are many ways of accomplishing the
same task. A mathematical program is a work of art as much as it is a set
of logical rules. But only the programmer can fully appreciate the beauty.

First prepare a list of proposed interrelated calculating formulae or
routines.
Then write the routines on paper.
Then test them on a computer.
Then spend the next 12 months removing the bugs.
Ditto, removing the bugs caused by the debugging operations.
Then publish them in the ARRL Handbook, 2009 edition, using a better
printer.
----
Reg.




Richard Clark November 29th 04 07:50 AM

On Mon, 29 Nov 2004 04:09:50 +0000 (UTC), "Reg Edwards"
wrote:

But only the programmer can fully appreciate the beauty.


Hi Reggie,

Nice posting.

Once, some many (few in your perspective) years ago, you once retorted
to my style with "this is not rec.radio.amateur.antenna.poetry."
There is more than the bouquet of that romantic tendency in your last
posting. However, neither of us is really surprised to find that in
the other. ;-)

73's
Richard Clark, KB7QHC

Wes Stewart November 29th 04 05:27 PM

On Mon, 29 Nov 2004 00:28:22 GMT, Richard Clark
wrote:

|On Sun, 28 Nov 2004 16:53:59 -0700, Wes Stewart
|wrote:
|
|If you wouild cite the pages to which you refer, I would gladly scan
|then to pdf and post them for all to reference.
|
|Hi Wes,
|
|The math is on the bottom of pg. 203 which is supporting Fig. 9-26.
|
|There is also a section entitled 8.8 Multiple reflections on ppg
|174...176.
|
|Then there is the specific math of fully specified matches at both
|ends, that is at the source and the load, found in Fig. 10-7 that is
|supported by discussion on ppg. 225...227.
|
|All of this bears on discussion around and about the necessary
|treatment of the Z of the Source, but I haven't supplied all the
|citations within this one reference by any means.
|
|Thanx, Wes. You needn't do all these scans. The group needs to do
|their own heavy lifting to escape their naivety about source Z.

Hi Richard,

I did it anyway. [g] Hope this covers it:

http://users.triconet.org/wesandlind...rdClarkRef.pdf

Regards,

Wes

Richard Clark November 29th 04 06:02 PM

On Mon, 29 Nov 2004 10:27:37 -0700, Wes Stewart
wrote:
I did it anyway. [g] Hope this covers it:
http://users.triconet.org/wesandlind...rdClarkRef.pdf


Hi Wes,

Thanx very much. I can see one of two results from this general
availability. The readership here can:
1. Avoid it in stunned shame (the embarrassment in coming of age);
2. Accept it as a remarkable revelation (because it's on the web).

I would hope for a third response from those who could argue what
follows from these first principles, but the lazier ones would
complain of my "attitude" and hobble back to their beauty contests on
their crutches. ;-)

To quote one of my favorite authors, Raymond Chandler, when in "The
Big Sleep" Doghouse Reilly is admonished about the same defect, he
avers "I don't mind if you don't like my manners. They're pretty bad.
I grieve over them during the long winter evenings."

73's
Richard Clark, KB7QHC

Roy Lewallen November 29th 04 08:57 PM

I offer a third third response.

On p. 175, Chipman states:

"Equation (8.27) demonstrates explicitly that the shape of a standing
wave pattern representing |V(d)| as a function of d on a transmission
line is in no way affected by the quantities Vs, Zs and [rho]s at the
source."

And equation 8.29 on p. 176, the calculation of reflection coefficient,
contains no source-dependent terms. I'm sure that somewhere in the book,
the author derives SWR in terms of reflection coefficient.

These are the facts:

1. The SWR, positions of the standing waves, reflection coefficient seen
looking into the line, impedance seen looking into the line, and dB line
loss are independent of source impedance.
2. The actual amount of power delivered to a line for a given Thevenin
source voltage will, of course, depend on the source impedance, just as
it would if the source were directly connected to a load. Therefore, the
absolute amount of power dissipated in the load depends on source
impedance. The dB line loss, however, doesn't. Also, the length of time
the line requires to reach equilibrium after initially turning on the
source depends on the source impedance.

These can be found, explicitly stated and/or in easily interpreted
equation form, in a host of references.

I see nothing in the text Wes has kindly posted which contradicts these
facts, and I'm sure there's nothing elsewhere in the text that does.

I often have a hard time understanding Richard's postings, so it's
possible that he's not disagreeing with the statements I've made,
either. If so, I apologize for the misinterpretation.

Roy Lewallen, W7EL

Richard Clark wrote:

On Mon, 29 Nov 2004 10:27:37 -0700, Wes Stewart
wrote:

I did it anyway. [g] Hope this covers it:
http://users.triconet.org/wesandlind...rdClarkRef.pdf



Hi Wes,

Thanx very much. I can see one of two results from this general
availability. The readership here can:
1. Avoid it in stunned shame (the embarrassment in coming of age);
2. Accept it as a remarkable revelation (because it's on the web).

I would hope for a third response from those who could argue what
follows from these first principles, but the lazier ones would
complain of my "attitude" and hobble back to their beauty contests on
their crutches. ;-)

To quote one of my favorite authors, Raymond Chandler, when in "The
Big Sleep" Doghouse Reilly is admonished about the same defect, he
avers "I don't mind if you don't like my manners. They're pretty bad.
I grieve over them during the long winter evenings."

73's
Richard Clark, KB7QHC


Roy Lewallen November 29th 04 09:26 PM

Thanks.

So between equations 8.29 and 8.30 the author calculates VSWR without
any source-related terms -- as every other textbook author does.

Roy Lewallen, W7EL

Wes Stewart wrote:
On Mon, 29 Nov 2004 12:57:16 -0800, Roy Lewallen
wrote:

|I offer a third third response.
|
|On p. 175, Chipman states:
|
|"Equation (8.27) demonstrates explicitly that the shape of a standing
|wave pattern representing |V(d)| as a function of d on a transmission
|line is in no way affected by the quantities Vs, Zs and [rho]s at the
|source."
|
|And equation 8.29 on p. 176, the calculation of reflection coefficient,
|contains no source-dependent terms. I'm sure that somewhere in the book,
|the author derives SWR in terms of reflection coefficient.

Indeed he does---on the next page.

http://users.triconet.org/wesandlind...manPage177.pdf

Equation (8.30)

1 + |rho|
VSWR -------------
1 - |rho|




Wes Stewart November 29th 04 09:58 PM

On Mon, 29 Nov 2004 12:57:16 -0800, Roy Lewallen
wrote:

|I offer a third third response.
|
|On p. 175, Chipman states:
|
|"Equation (8.27) demonstrates explicitly that the shape of a standing
|wave pattern representing |V(d)| as a function of d on a transmission
|line is in no way affected by the quantities Vs, Zs and [rho]s at the
|source."
|
|And equation 8.29 on p. 176, the calculation of reflection coefficient,
|contains no source-dependent terms. I'm sure that somewhere in the book,
|the author derives SWR in terms of reflection coefficient.
|
|These are the facts:
|
|1. The SWR, positions of the standing waves, reflection coefficient seen
|looking into the line, impedance seen looking into the line, and dB line
|loss are independent of source impedance.
|2. The actual amount of power delivered to a line for a given Thevenin
|source voltage will, of course, depend on the source impedance, just as
|it would if the source were directly connected to a load. Therefore, the
|absolute amount of power dissipated in the load depends on source
|impedance. The dB line loss, however, doesn't. Also, the length of time
|the line requires to reach equilibrium after initially turning on the
|source depends on the source impedance.
|
|These can be found, explicitly stated and/or in easily interpreted
|equation form, in a host of references.
|
|I see nothing in the text Wes has kindly posted which contradicts these
|facts, and I'm sure there's nothing elsewhere in the text that does.
|
|I often have a hard time understanding Richard's postings, so it's
|possible that he's not disagreeing with the statements I've made,
|either. If so, I apologize for the misinterpretation.

In an earlier post to this thread, Richard stated:

|"This is yet another of my references that attend to my recent, short
|thread on the nature of power determination error, and mismatched
|loads AND sources. In fact ALL of these references I've offered
|explicitly describe that the source MUST be matched for ANY of these
|equations about transmission lines bandied about to accurately offer
|true answers. The naive presumptions that Source Z is immaterial to
|the outcome of analysis is quite widespread here."

I almost demurred, much as Roy did, because this statement is not
universal, but I held off because I believe (and hope) that Richard is
talking only about *power* measurement errors.

Wes

Wes Stewart November 29th 04 10:10 PM

On Mon, 29 Nov 2004 12:57:16 -0800, Roy Lewallen
wrote:

|I offer a third third response.
|
|On p. 175, Chipman states:
|
|"Equation (8.27) demonstrates explicitly that the shape of a standing
|wave pattern representing |V(d)| as a function of d on a transmission
|line is in no way affected by the quantities Vs, Zs and [rho]s at the
|source."
|
|And equation 8.29 on p. 176, the calculation of reflection coefficient,
|contains no source-dependent terms. I'm sure that somewhere in the book,
|the author derives SWR in terms of reflection coefficient.

Indeed he does---on the next page.

http://users.triconet.org/wesandlind...manPage177.pdf

Equation (8.30)

1 + |rho|
VSWR -------------
1 - |rho|




Roy Lewallen November 29th 04 11:14 PM

Once again, it's not clear to me just what you're trying to prove.

Do you disagree with either of the two numbered statements made in my
posting? If so, which part(s) of which one(s) -- I'm sure I can
demonstrate their correctness. If not, we probably don't disagree.

Roy Lewallen, W7EL

Richard Clark wrote:
On Mon, 29 Nov 2004 12:57:16 -0800, Roy Lewallen
wrote:


I'm sure that somewhere in the book,
the author derives SWR in terms of reflection coefficient.



Hi Roy,

No doubt. As I am not immediately interested in the reductionist art
of SWR, then the remainder seemed of little relevance to line losses
and the contribution of source Z to power determination error.

You continue, in part quote of a part quote:

representing |V(d)| as a function of d


which given you offer no more comment upon it, gives me the impression
you are unaware of what function d is. The point of the matter is that
this very equation you chose is examined in isolation, by you, but is
returned to on several occasions by Chipman where he quite
"explicitly" exhibits how V(d) ranges wildly for situations where both
ends of the line are terminated by forced mismatches. This is a
uncommon technique for determining SWR (still not my point, but
nonetheless an obvious example).

And yes, I realize

I often have a hard time understanding Richard's postings


and I often grieve over this on long winter evenings. Roy, you are
too coy by half. ;-)

However, your aside into SWR shape and the focus on reductions to
typical applications (source matches line) does leave a dilemma
because there is now conflict between your isolated quote of Chipman
and the demonstration of EZNEC as reported by my late, short lived
thread. I would offer that EZNEC fully supports Chipman's other
comments on this same quoted material you drew from him, and goes to
the matter I offered of an uncommon technique for SWR determination.
My EZNEC reports are also supported by bench results, and other
sources also recited here. All this seems to leave you on the outside
looking in. As it broaches upon topics that you have long cautioned
me that discussion would not "change your mind," I doubt this will go
any further.

73's
Richard Clark, KB7QHC


Cecil Moore November 29th 04 11:18 PM

Roy Lewallen wrote:
I see nothing in the text Wes has kindly posted which contradicts these
facts, and I'm sure there's nothing elsewhere in the text that does.


None of us are perfect. All of us (except Jim Kelley :-) will admit to
being human, i.e. capable of making a mistake. The Z(s) of the source,
no doubt, has an effect on the power sourced by the source. But the
"power sourced by the source" has no effect on SWR, which is independent
of source impedance. Given a steady-state forward power, nothing else
depends upon source impedance. If a one ohm source is capable of
supplying the same voltage as a one megohm source, the steady-state
results will be identical.

Given any source with any source impedance, there exists a forward
power. Given any forward power, the source impedance during steady-
state is completely irrelevant.
--
73, Cecil http://www.qsl.net/w5dxp

Richard Clark November 29th 04 11:30 PM

On Mon, 29 Nov 2004 12:57:16 -0800, Roy Lewallen
wrote:

I'm sure that somewhere in the book,
the author derives SWR in terms of reflection coefficient.


Hi Roy,

No doubt. As I am not immediately interested in the reductionist art
of SWR, then the remainder seemed of little relevance to line losses
and the contribution of source Z to power determination error.

You continue, in part quote of a part quote:
representing |V(d)| as a function of d

which given you offer no more comment upon it, gives me the impression
you are unaware of what function d is. The point of the matter is that
this very equation you chose is examined in isolation, by you, but is
returned to on several occasions by Chipman where he quite
"explicitly" exhibits how V(d) ranges wildly for situations where both
ends of the line are terminated by forced mismatches. This is a
uncommon technique for determining SWR (still not my point, but
nonetheless an obvious example).

And yes, I realize
I often have a hard time understanding Richard's postings

and I often grieve over this on long winter evenings. Roy, you are
too coy by half. ;-)

However, your aside into SWR shape and the focus on reductions to
typical applications (source matches line) does leave a dilemma
because there is now conflict between your isolated quote of Chipman
and the demonstration of EZNEC as reported by my late, short lived
thread. I would offer that EZNEC fully supports Chipman's other
comments on this same quoted material you drew from him, and goes to
the matter I offered of an uncommon technique for SWR determination.
My EZNEC reports are also supported by bench results, and other
sources also recited here. All this seems to leave you on the outside
looking in. As it broaches upon topics that you have long cautioned
me that discussion would not "change your mind," I doubt this will go
any further.

73's
Richard Clark, KB7QHC

Richard Clark November 30th 04 02:28 AM

On Mon, 29 Nov 2004 15:14:42 -0800, Roy Lewallen
wrote:
Once again, it's not clear to me just what you're trying to prove.


Hi Roy,

Troubles me too....

In the interim I have recognized where I went off the deep end in the
thread I have alluded to. The attempt there was to reproduce, in
EZNEC, results obtained at the bench and offered through various
references which demonstrate Mismatch Uncertainty. Although the model
of the transmission line was certainly of the highest quality, EZNEC
lacks the capacity to separate forward and reverse waves for analysis.
In that regard I mistakenly attributed the results I obtained to my
bench results.

Situation is that with a SWR meter moving along a line mismatched at
both ends, there is a distinct variation in the computed Power. When
I did this at the bench, I could evidence about a 30% variation which
was consistent with theory and clearly exhibits the contribution of
Source Z when it is other than 50 Ohms. When I recently attempted to
model this in EZNEC, I again saw the wild fluctuation of power that
seduced me with its complementary results into thinking I had achieved
the same results. When I revisited those results (EZNEC ones that
is), all I had done was prove the mismatch through the abstraction of
the power reported at my moving test load. When I reverse engineered
the voltages from the known R, it became obvious that the VSWR
corresponded to every expectation - or was close enough given the
degree of resolution I had available with 20 test points distributed
along the line. Chipman describes this in his late chapters - one of
which Wes has provided.

However, this does nothing to detract from Chipman's work that
includes the FULL treatment of all variables that lead to the common
usages. Such treatments include the Source with full
characterizations and goes on to discuss the R of the Source and not
just its Z. That so many texts disregard this level of examination
does not deny its importance to issues that go beyond SWR. Those
lesser texts presume Source Z unlike Chipman, and its significance is
lost to the student who hasn't been grounded in the fundamentals. And
thus we arrive at the topic at hand and listed in the Subject Line:
Additional Line Losses Due to SWR. In that regard, the Source Z is
entirely an active player and any additional mismatch that it presents
to the system eventually finds additional loss (caloric) injected into
it. Chipman's work in that regard is complete enough to offer Bob the
framework to render a complete solution and to explain how and why
this additional loss appears. It may not bear on his measurements
directly (the measure of a stub's Q as it eventually turns out), but
it is related closely enough to provide tangible leads.

73's
Richard Clark, KB7QHC

Cecil Moore November 30th 04 04:18 AM

Richard Clark wrote:
Chipman's work in that regard is complete enough to offer Bob the
framework to render a complete solution and to explain how and why
this additional loss appears. It may not bear on his measurements
directly (the measure of a stub's Q as it eventually turns out), but
it is related closely enough to provide tangible leads.


The fact remains that a transmission line/antenna system has the
same characteristics whether one watt, 100 watts, or 1000 watts
are input to it, i.e. the efficiency and SWR of the antenna system
does not depend upon the source impedance.
--
73, Cecil http://www.qsl.net/w5dxp

Richard Clark November 30th 04 07:32 AM

On Mon, 29 Nov 2004 22:18:56 -0600, Cecil Moore
wrote:
the efficiency and SWR of the antenna system
does not depend upon the source impedance.

Life's like a box of chocolates, hmmm? Get off the bench.

Richard Harrison November 30th 04 07:50 PM

Roy, W7EL wrote:
"I`m sure that somewhere in the book the author (Chipman) derives SWR in
terms of reflection coefficient."

I`ve read, here I believe, that Chipman`s book is one of the "Schaum`s
Outline" series. It would need to derive SWR in terms of reflection
coefficient to be complete.

Attenuation of a uniform transmission line is a function of the loss per
unit length and the total length. A line with SWR has higher voltage and
current in spots than a matched line. Thus it has higher loss. Analysis
is complicated in lossy lines due to decline in SWR back from the
reflection point. If SWR at the reflection point is less than 2:1, added
loss due to SWR is hardly detectable. Such a line is considered perfect.

The ARRL Antenna Book has graphs relating SWR to fopward and reflected
power readings as given by a Bird wattmeter. The "Antenna Book" also has
a graph of additional loss due to standing waves versus the SWR at the
load for values between SWR=1.5 and SWR=20.

I don`t have a dog in this fight. There is nothing particularly strange
about solutions to equations which describe particular relations on a
transmission line. The functions are not erratic but continuous and
predictable. Selection of the right formulas is all that`s needed to get
the right answer from the right data.

Best regards, Richard Harrison, KB5WZI



All times are GMT +1. The time now is 03:24 PM.

Powered by vBulletin® Copyright ©2000 - 2025, Jelsoft Enterprises Ltd.
RadioBanter.com