RadioBanter

RadioBanter (https://www.radiobanter.com/)
-   Antenna (https://www.radiobanter.com/antenna/)
-   -   Pulling Cable in Conduit (https://www.radiobanter.com/antenna/86949-pulling-cable-conduit.html)

jimbo January 22nd 06 08:47 PM

Pulling Cable in Conduit
 
jimbo wrote:
I am getting close to pulling some cable through a 1 1/4 inch PVC
conduit that runs about 20 feet from the third floor attic to the
basement. The contractor claims the conduit is a "straight shot" with no
bends. I have three LMR240 cables with PL259 connectors on each end. And
I would also like to pull a 450 ohm length of ladder line. (Measures
about 1 inch.) And I would like to pull at least two 16 gage insulated
control wires.

Any advice would be appreciated.

Thanks, jimbo


Thanks for the great advice. I will leave the ladder line for another
day, another route from attic to basement.

Thanks, jimbo

gb January 22nd 06 08:48 PM

Pulling Cable in Conduit
 
"Ralph Mowery" wrote in message
ink.net...

"gb" wrote in message
...
"jimbo" wrote in message
. ..
I am getting close to pulling some cable through a 1 1/4 inch PVC
conduit
that runs about 20 feet from the third floor attic to the basement. The
contractor claims the conduit is a "straight shot" with no bends. I have
three LMR240 cables with PL259 connectors on each end. And I would also
like to pull a 450 ohm length of ladder line. (Measures about 1 inch.)

And
I would like to pull at least two 16 gage insulated control wires.

Any advice would be appreciated.

Thanks, jimbo


A Google search should get you the electrical handbooks and codes (e.g.
NEC ) for the maximum fill for each conduit size. As a rough rule NEVER
fill a conduit more than 70% to 75%.


The NEC is mostly for wires for the AC lines. It will not apply for the
antenna wires.

The ladder line is not going to work too well in the conduit with the
other
wire. There is a minimum distance that it should be placed from other
conductors.

Ralph -

I am not referring to the AC portion of the NEC, RATHER I am trying to
highlight the maximum fill (diameter of each cable and maximum pull).
ever try to "pull conductors" through conduit when this rule is NOT followed
??

I have, it's pain .. in the xxxx.
Easy read and math calculations are minimal with tables supplied --- number
of conductors and O.D. versus the I.D. on conduit.



Ralph Mowery January 23rd 06 12:07 AM

Pulling Cable in Conduit
 

"gb" wrote in message
...
"Ralph Mowery" wrote in message
ink.net...

"gb" wrote in message
...
"jimbo" wrote in message
. ..
I am getting close to pulling some cable through a 1 1/4 inch PVC
conduit
that runs about 20 feet from the third floor attic to the basement.

The
contractor claims the conduit is a "straight shot" with no bends. I

have
three LMR240 cables with PL259 connectors on each end. And I would

also
like to pull a 450 ohm length of ladder line. (Measures about 1 inch.)

And
I would like to pull at least two 16 gage insulated control wires.

Any advice would be appreciated.

Thanks, jimbo


A Google search should get you the electrical handbooks and codes (e.g.
NEC ) for the maximum fill for each conduit size. As a rough rule

NEVER
fill a conduit more than 70% to 75%.


The NEC is mostly for wires for the AC lines. It will not apply for the
antenna wires.

The ladder line is not going to work too well in the conduit with the
other
wire. There is a minimum distance that it should be placed from other
conductors.

Ralph -

I am not referring to the AC portion of the NEC, RATHER I am trying to
highlight the maximum fill (diameter of each cable and maximum pull).
ever try to "pull conductors" through conduit when this rule is NOT

followed
??

I have, it's pain .. in the xxxx.
Easy read and math calculations are minimal with tables supplied ---

number
of conductors and O.D. versus the I.D. on conduit.


Yes, I have. I work at a large industral plant. Some of the wire I have
pulled has been in 1 inch conduit that was probably 90% full of # 12 wire
already. Still needed to get another pair of wires through that. I have
cut a couple of wires in the conduit and used them to pull in wire to
replace them and two new wires. No room in the conduit to push a snake
through and pull the new wire in. Use lots of the wire pulling grease.
Most of the wires are control wires and only have about an amp or less on
them. We are not worried about overheating the wires in the conduit, but
need to add new control circuits to a 40 year old plant. As you said it is
a pain.



Jim - NN7K January 23rd 06 01:54 AM

Pulling Cable in Conduit
 
Run the Ladder line to near the entrance of the PVC, and then use a
BALUN, to COAX, for the run down your PVC, BUT remember: PVC stands
for: PIPE VERY CROWDED! Jim NN7K

Dan Richardson wrote:
On Sun, 22 Jan 2006 08:29:29 -0700, jimbo wrote:


I am getting close to pulling some cable through a 1 1/4 inch PVC
conduit that runs about 20 feet from the third floor attic to the
basement. The contractor claims the conduit is a "straight shot" with
no bends. I have three LMR240 cables with PL259 connectors on each
end. And I would also like to pull a 450 ohm length of ladder line.
(Measures about 1 inch.) And I would like to pull at least two 16 gage
insulated control wires.

Any advice would be appreciated.



Forget the ladder line! It will be a disaster.





email: k6mheatarrldotnet
http://www.k6mhe.com/


gb January 23rd 06 04:16 AM

Pulling Cable in Conduit
 
"Ralph Mowery" wrote in message
ink.net...
Ever try to "pull conductors" through conduit when this rule is NOT

followed ??

I have, it's pain .. in the xxxx.
Easy read and math calculations are minimal with tables supplied ---

number
of conductors and O.D. versus the I.D. on conduit.


Yes, I have. I work at a large industral plant. Some of the wire I have
pulled has been in 1 inch conduit that was probably 90% full of # 12 wire
already. Still needed to get another pair of wires through that. I have
cut a couple of wires in the conduit and used them to pull in wire to
replace them and two new wires. No room in the conduit to push a snake
through and pull the new wire in. Use lots of the wire pulling grease.
Most of the wires are control wires and only have about an amp or less on
them. We are not worried about overheating the wires in the conduit, but
need to add new control circuits to a 40 year old plant. As you said it
is
a pain.

Ha ha ha .. well we did follow up work behind the same guy !! :-)

Sadly, the grease did not help in one of my situations with 3/4" conduit ..
had to finally tear out of wall and then replace with 2 conduits for the
wire runs.

gb




All times are GMT +1. The time now is 08:28 PM.

Powered by vBulletin® Copyright ©2000 - 2024, Jelsoft Enterprises Ltd.
RadioBanter.com