Home |
Search |
Today's Posts |
|
#1
![]() |
|||
|
|||
![]()
I am getting close to pulling some cable through a 1 1/4 inch PVC
conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Thanks, jimbo |
#2
![]() |
|||
|
|||
![]()
"jimbo" wrote in message
. .. I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Thanks, jimbo A Google search should get you the electrical handbooks and codes (e.g. NEC ) for the maximum fill for each conduit size. As a rough rule NEVER fill a conduit more than 70% to 75%. gb |
#3
![]() |
|||
|
|||
![]() "gb" wrote in message ... "jimbo" wrote in message . .. I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Thanks, jimbo A Google search should get you the electrical handbooks and codes (e.g. NEC ) for the maximum fill for each conduit size. As a rough rule NEVER fill a conduit more than 70% to 75%. The NEC is mostly for wires for the AC lines. It will not apply for the antenna wires. The ladder line is not going to work too well in the conduit with the other wire. There is a minimum distance that it should be placed from other conductors. |
#4
![]() |
|||
|
|||
![]()
"Ralph Mowery" wrote in message
ink.net... "gb" wrote in message ... "jimbo" wrote in message . .. I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Thanks, jimbo A Google search should get you the electrical handbooks and codes (e.g. NEC ) for the maximum fill for each conduit size. As a rough rule NEVER fill a conduit more than 70% to 75%. The NEC is mostly for wires for the AC lines. It will not apply for the antenna wires. The ladder line is not going to work too well in the conduit with the other wire. There is a minimum distance that it should be placed from other conductors. Ralph - I am not referring to the AC portion of the NEC, RATHER I am trying to highlight the maximum fill (diameter of each cable and maximum pull). ever try to "pull conductors" through conduit when this rule is NOT followed ?? I have, it's pain .. in the xxxx. Easy read and math calculations are minimal with tables supplied --- number of conductors and O.D. versus the I.D. on conduit. |
#5
![]() |
|||
|
|||
![]() "gb" wrote in message ... "Ralph Mowery" wrote in message ink.net... "gb" wrote in message ... "jimbo" wrote in message . .. I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Thanks, jimbo A Google search should get you the electrical handbooks and codes (e.g. NEC ) for the maximum fill for each conduit size. As a rough rule NEVER fill a conduit more than 70% to 75%. The NEC is mostly for wires for the AC lines. It will not apply for the antenna wires. The ladder line is not going to work too well in the conduit with the other wire. There is a minimum distance that it should be placed from other conductors. Ralph - I am not referring to the AC portion of the NEC, RATHER I am trying to highlight the maximum fill (diameter of each cable and maximum pull). ever try to "pull conductors" through conduit when this rule is NOT followed ?? I have, it's pain .. in the xxxx. Easy read and math calculations are minimal with tables supplied --- number of conductors and O.D. versus the I.D. on conduit. Yes, I have. I work at a large industral plant. Some of the wire I have pulled has been in 1 inch conduit that was probably 90% full of # 12 wire already. Still needed to get another pair of wires through that. I have cut a couple of wires in the conduit and used them to pull in wire to replace them and two new wires. No room in the conduit to push a snake through and pull the new wire in. Use lots of the wire pulling grease. Most of the wires are control wires and only have about an amp or less on them. We are not worried about overheating the wires in the conduit, but need to add new control circuits to a 40 year old plant. As you said it is a pain. |
#6
![]() |
|||
|
|||
![]()
"Ralph Mowery" wrote in message
ink.net... Ever try to "pull conductors" through conduit when this rule is NOT followed ?? I have, it's pain .. in the xxxx. Easy read and math calculations are minimal with tables supplied --- number of conductors and O.D. versus the I.D. on conduit. Yes, I have. I work at a large industral plant. Some of the wire I have pulled has been in 1 inch conduit that was probably 90% full of # 12 wire already. Still needed to get another pair of wires through that. I have cut a couple of wires in the conduit and used them to pull in wire to replace them and two new wires. No room in the conduit to push a snake through and pull the new wire in. Use lots of the wire pulling grease. Most of the wires are control wires and only have about an amp or less on them. We are not worried about overheating the wires in the conduit, but need to add new control circuits to a 40 year old plant. As you said it is a pain. Ha ha ha .. well we did follow up work behind the same guy !! :-) Sadly, the grease did not help in one of my situations with 3/4" conduit .. had to finally tear out of wall and then replace with 2 conduits for the wire runs. gb |
#7
![]() |
|||
|
|||
![]()
jimbo wrote:
I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. I specified a similar PVC conduit when our home was built. I simply "dropped" the cables down the conduit from the attic, and let gravity do all the work. If you drop them all down together at the same time you should have no problems. The LMR240 and control wires will be fine, but ladder line in the same conduit with all those other wires probably won't work very well. 73, John NU3E |
#8
![]() |
|||
|
|||
![]() I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. I think you can get those three coax lines down the straight conduit if you stagger the PL-259 connectors, however, once you have a couple cables in the conduit, you may find there isn't enough room for a PL-259 to squeeze by, so you may need to remove the connectors, pull the cables and then reinstall them. Three LMR240s and two control cables are going to fill that conduit more than you realize! As far as the Ladder line goes, DON'T ! It will be nearly useless packed in with all that coax and wire as it needs several inches of SPACE around it to function properly, with no nearby metal objects. That coax braid in close proximity will drastically reduce its effectiveness. Ed K7AAT |
#9
![]() |
|||
|
|||
![]()
Jimbo,
It's going to be crowded in that conduit, so don't rely upon gravity to get that stuff down the pipe. Three suggestions: 1. Buy a 25 foot electrician's steel snake (Home Depot, Lowe's, ...), use this to pull the wires through; or drop a length of poly line/guy string as a pull line. If gravity does not get the pull string through the conduit, tie a lightweight object to the line and suck/pull with a leaf blower or vacuum cleaner. 2. Stagger the pl-259's and open cable ends as much as possible so that this looks like a pointed, rather than a blunt, object going through the conduit. 3. When you're pulling the wires into the conduit, do your best at the feed point to keep the wires "straight" and not twisting into the conduit. This takes less space and permits you to do item #4 . 3. ADD A PULL STRING IN THE CONDUIT WITH THE WIRES! So when you're all done, three months from now, and you realize you just want to add one more little 4 conductor cable (or whatever!), you can do it without completely dismantling the cables. {been there, done that} -- -larry K8UT "jimbo" wrote in message . .. I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Thanks, jimbo |
#10
![]() |
|||
|
|||
![]()
On Sun, 22 Jan 2006 08:29:29 -0700, jimbo wrote:
I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Forget the ladder line! It will be a disaster. email: k6mheatarrldotnet http://www.k6mhe.com/ |
Reply |
|
Thread Tools | Search this Thread |
Display Modes | |
|
|
![]() |
||||
Thread | Forum | |||
The "TRICK" to TV 'type' Coax Cable [Shielded] SWL Loop Antennas {RHF} | Antenna | |||
The "TRICK" to TV 'type' Coax Cable [Shielded] SWL Loop Antennas {RHF} | Shortwave | |||
Poor quality low + High TV channels? How much dB in Preamp? | Antenna | |||
Poor quality low + High TV channels? How much dB in Preamp? | Shortwave | |||
Massachusetts. Cambridge. Community access television. | Broadcasting |