![]() |
|
Pulling Cable in Conduit
I am getting close to pulling some cable through a 1 1/4 inch PVC
conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Thanks, jimbo |
Pulling Cable in Conduit
"jimbo" wrote in message
. .. I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Thanks, jimbo A Google search should get you the electrical handbooks and codes (e.g. NEC ) for the maximum fill for each conduit size. As a rough rule NEVER fill a conduit more than 70% to 75%. gb |
Pulling Cable in Conduit
"gb" wrote in message ... "jimbo" wrote in message . .. I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Thanks, jimbo A Google search should get you the electrical handbooks and codes (e.g. NEC ) for the maximum fill for each conduit size. As a rough rule NEVER fill a conduit more than 70% to 75%. The NEC is mostly for wires for the AC lines. It will not apply for the antenna wires. The ladder line is not going to work too well in the conduit with the other wire. There is a minimum distance that it should be placed from other conductors. |
Pulling Cable in Conduit
jimbo wrote:
I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. I specified a similar PVC conduit when our home was built. I simply "dropped" the cables down the conduit from the attic, and let gravity do all the work. If you drop them all down together at the same time you should have no problems. The LMR240 and control wires will be fine, but ladder line in the same conduit with all those other wires probably won't work very well. 73, John NU3E |
Pulling Cable in Conduit
|
Pulling Cable in Conduit
I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. I think you can get those three coax lines down the straight conduit if you stagger the PL-259 connectors, however, once you have a couple cables in the conduit, you may find there isn't enough room for a PL-259 to squeeze by, so you may need to remove the connectors, pull the cables and then reinstall them. Three LMR240s and two control cables are going to fill that conduit more than you realize! As far as the Ladder line goes, DON'T ! It will be nearly useless packed in with all that coax and wire as it needs several inches of SPACE around it to function properly, with no nearby metal objects. That coax braid in close proximity will drastically reduce its effectiveness. Ed K7AAT |
Pulling Cable in Conduit
Yes a very negative effect and not a good idea.. If you look in the
history of this NG you will see some numbers about minimum separation distance from other metal. If you really want to run a balanced feeder you can use two pieces of coax with the shields connected at each end. The Z will be twice that of the original coax. (I use this as a Q section on 20m feeding a loop of about 170 ohms) Dunno about losses in this case (which open wire feeder are great for reducing) and of course the Z is going to be kind of lower than 450r. Cheers Bob VK2YQA jimbo wrote: Thanks for the replies. The ladder line would be used when the other lines were not being used. Does the proximity of other unpowered lines affect the ladder line operation for receive and transmit? Thanks, jimbo |
Pulling Cable in Conduit
Jimbo,
It's going to be crowded in that conduit, so don't rely upon gravity to get that stuff down the pipe. Three suggestions: 1. Buy a 25 foot electrician's steel snake (Home Depot, Lowe's, ...), use this to pull the wires through; or drop a length of poly line/guy string as a pull line. If gravity does not get the pull string through the conduit, tie a lightweight object to the line and suck/pull with a leaf blower or vacuum cleaner. 2. Stagger the pl-259's and open cable ends as much as possible so that this looks like a pointed, rather than a blunt, object going through the conduit. 3. When you're pulling the wires into the conduit, do your best at the feed point to keep the wires "straight" and not twisting into the conduit. This takes less space and permits you to do item #4 . 3. ADD A PULL STRING IN THE CONDUIT WITH THE WIRES! So when you're all done, three months from now, and you realize you just want to add one more little 4 conductor cable (or whatever!), you can do it without completely dismantling the cables. {been there, done that} -- -larry K8UT "jimbo" wrote in message . .. I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Thanks, jimbo |
Pulling Cable in Conduit
jimbo wrote:
Thanks for the replies. The ladder line would be used when the other lines were not being used. Does the proximity of other unpowered lines affect the ladder line operation for receive and transmit? Especially transmit. You will lose a lot of your transmitted power to the conductors surrounding the ladder-line. Ladder- line should be run a few inches away from anything. -- 73, Cecil http://www.qsl.net/w5dxp |
Pulling Cable in Conduit
On Sun, 22 Jan 2006 08:29:29 -0700, jimbo wrote:
I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Forget the ladder line! It will be a disaster. email: k6mheatarrldotnet http://www.k6mhe.com/ |
All times are GMT +1. The time now is 10:33 AM. |
|
Powered by vBulletin® Copyright ©2000 - 2025, Jelsoft Enterprises Ltd.
RadioBanter.com