Home |
Search |
Today's Posts |
#11
![]() |
|||
|
|||
![]() "Roy Lewallen" wrote Dave Shrader wrote: . . . A major point of caution is required. The NEC requires ONLY ONE ground connection. Multiple ground connections introduce VERY SERIOUS ground loops that may violate the NEC criteria. This opens a VERY LARGE loop hole in your home owner's insurance policy. If you are adding a second earth [ground] connection at your station use an isolation transformer to break up the ground loops in the basic 120 VAC connection. Consult with an electrician regarding your local and NEC codes. . . . My NEC book is getting pretty old now, 1990, but at that time, multiple grounds were often not only permitted, but required. And a *minimum* spacing was sometimes specified. Outdated only regarding water pipe Roy, but good advice. And Dave's above interpretation of NEC is a misunderstanding of the subject - easy to do so consult a professional if you have any douvbt whatsoever about what your are doing. Isolation transformers are not an option for isolating a station ground from AC service entrance. They are permitted only in lmited cases where independent grounding is required, and in other cases where HV isolating transformers or fiber optic isolate feedlines. No one in this group will likely have that requirement, so put that out of your mind Dave. You *MUST* bond your station ground to the AC service main ground. Ignore this at the peril of your entire system, which had better be 100% isolated from all power and external feedlines and grounds. That is an option for protection, isolating from *everything*. But it means unplugging and shorting to ground all feedlines, disconnecting and removing RF ground connections, disconnecting computer modems, telephone, and AC power to all of your connected equipment. A really poor option in my opinion, because if you forget something, or risk your life trying to disconnect during a surprise thunderstorm, what was it worth? For example, section 250-84, Resistance of Made Electrodes: "A single electrode consisting of a rod, pipe, or plate which does not have a resistance to ground of 25 ohms or less shall be augmented by one additional electrode of any of the types specified in Sections 250-81 or 250-83. Where multiple rod, pipe, or plate electrodes are installed to meet the requirements of this section, they shall be not less than 6 feet (1.83m) apart." Or section 250-81(a), Metal Underground Water Pipe: ". . .A metal underground water pipe shall be supplemented by an additional electrode of a type specified in Section 250-81 or in Section 250-83. The supplemental electrode shall be permitted to be bonded to the grounding electrode conductor, the grounded service-entrance conductor, the grounded service raceway, any grounded sevice enclosure, or the interior metal water piping at any convenient point." When I replaced the service (in 1979) in my 1952 house, the system ground was a water pipe connection and I was required to add a ground rod. Neither was considered adequate in itself; both were required by the code at that time. I agree wholeheartedly about consulting an electrician. Non-electricians (including me) often have mistaken ideas about the content of the NEC. It doesn't hurt to have an up to date copy of the NEC for reference, either, if you anticipate doing any of the work yourself. Roy Lewallen, W7EL Jack Painter Virginia Beach VA |
#12
![]() |
|||
|
|||
![]()
Roy Lewallen wrote:
Dave Shrader wrote: . . . A major point of caution is required. The NEC requires ONLY ONE ground connection. Multiple ground connections introduce VERY SERIOUS ground loops that may violate the NEC criteria. This opens a VERY LARGE loop hole in your home owner's insurance policy. If you are adding a second earth [ground] connection at your station use an isolation transformer to break up the ground loops in the basic 120 VAC connection. Consult with an electrician regarding your local and NEC codes. . . . My NEC book is getting pretty old now, 1990, but at that time, multiple grounds were often not only permitted, but required. And a *minimum* spacing was sometimes specified. For example, section 250-84, Resistance of Made Electrodes: "A single electrode consisting of a rod, pipe, or plate which does not have a resistance to ground of 25 ohms or less shall be augmented by one additional electrode of any of the types specified in Sections 250-81 or 250-83. Where multiple rod, pipe, or plate electrodes are installed to meet the requirements of this section, they shall be not less than 6 (1.83m) apart." Is it something like this? Multiple ground rods are permitted (encouraged, even) in order to establish one good ground connection; but the wiring system can have only one ground connection. -- 73 from Ian G3SEK 'In Practice' columnist for RadCom (RSGB) http://www.ifwtech.co.uk/g3sek |
#13
![]() |
|||
|
|||
![]()
Jack Painter wrote:
Right Ian, having equipment spread out over a wide area is an undesireable condition, but a reality for many operators. Running 3" wide or greater copper strapping in individual paths to one single bus "collector" is a challenge, but one worth trying. Equipment stacked or racked together could certainly be "grouped" and a common bonding strap run for each group to the SPG. But 20 linear feet of bus bar could have huge transient voltages developed across it from a nearby strike. As in a few hundred thousand volts between supposedly "grounded' equipment. Hence the importance of all equipment connecting to the same ground point, not via a long run of common bus bar to that ground point. Make your compromises according to your individual requirements and station layout. Thanks very much for those thoughts, Jack. As I'd guessed, you had some good suggestions, but you can see their practical problems too. The same applies to an alternative method, which is to group related items of equipment as closely as possible, and connect them by the shortest possible straps to a large sheet of metal. The key feature is that this sheet should be *very wide*, to create a very low inductance and help minimize any voltage drops along its length. Conductor thickness doesn't matter in this location, so a sheet of copper-clad PC board is fine. It's also very easy to solder short grounding straps onto the PC board, and move them around without having to disconnect the whole sheet to drill it. Some people put the sheet on the table, and the gear on top of the sheet. If there is a shelf carrying another level of equipment above, another practical way is to fasten the sheet to the underside of the shelf. The reason why conductor thickness doesn't matter in this location is that we don't expect full-bore lightning surges through the station itself. The ground bonding at the common service entrance should have diverted the main surge safely to ground, so the equipment bonding inside the station should only need to deal with very much smaller currents - smaller, but still large enough to damage sensitive electronics. Also, the higher-frequency components of the surge will only run along the surface anyway, so what matters most is width and surface area rather than thickness of copper. As Jack says, busbars are a particular invitation to develop voltage drops along their length. This "ground-sheet" system accepts there will be some voltage drop along its length, but does everything practicable to minimize it. A wide sheet is vastly better than busbars, and solid copper busbars are a particular waste of money - a large sheet of scrap PC board will do it far better, for almost nothing. If I had the luxury of a large station, I'd use these sheets as part of a wider-scale "grouping" system, as Jack suggests. Just realize that in a nearby-by strike, lightning will find the weak points in any system and exploit that weakness to the fullest possibility. In this climate, lightning is actually quite a minor hazard. What has driven me to organize and bond equipment together is the need to control RFI due to ground currents (of which I generate rather a lot). What's good for the one is generally good for the other... and often good for received noise reduction too. -- 73 from Ian G3SEK 'In Practice' columnist for RadCom (RSGB) http://www.ifwtech.co.uk/g3sek |
#14
![]() |
|||
|
|||
![]() Ian White, G3SEK wrote: Roy Lewallen wrote: My NEC book is getting pretty old now, 1990, but at that time, multiple grounds were often not only permitted, but required. And a *minimum* spacing was sometimes specified. For example, section 250-84, Resistance of Made Electrodes: "A single electrode consisting of a rod, pipe, or plate which does not have a resistance to ground of 25 ohms or less shall be augmented by one additional electrode of any of the types specified in Sections 250-81 or 250-83. Where multiple rod, pipe, or plate electrodes are installed to meet the requirements of this section, they shall be not less than 6 (1.83m) apart." Is it something like this? Multiple ground rods are permitted (encouraged, even) in order to establish one good ground connection; but the wiring system can have only one ground connection. Well, yes and no. As I read it, all the ground electrodes have to be connected to the service box, as they are at my house. I have a water-pipe ground and a ground rod; they're physically widely separated, and each has its own conductor going back to the service box. So I guess you could call the service box a single "ground connection". The neutral and safety ground conductors of each circuit are individually grounded at the service box also, giving further support to interpreting its function as a single ground connection. A number of ground methods and devices are approved, such as buried rods or plates, concrete grounds, or (in my old code book anyway), water pipe ground. Some can be used alone and others need a second ground device as a supplement. When multiple ground rods are used, the code has requirements for bonding them to each other. Roy Lewallen, W7EL |
#15
![]() |
|||
|
|||
![]() "Roy Lewallen" wrote in message ... Ian White, G3SEK wrote: Roy Lewallen wrote: My NEC book is getting pretty old now, 1990, but at that time, multiple grounds were often not only permitted, but required. And a *minimum* spacing was sometimes specified. For example, section 250-84, Resistance of Made Electrodes: "A single electrode consisting of a rod, pipe, or plate which does not have a resistance to ground of 25 ohms or less shall be augmented by one additional electrode of any of the types specified in Sections 250-81 or 250-83. Where multiple rod, pipe, or plate electrodes are installed to meet the requirements of this section, they shall be not less than 6 (1.83m) apart." Is it something like this? Multiple ground rods are permitted (encouraged, even) in order to establish one good ground connection; but the wiring system can have only one ground connection. Well, yes and no. As I read it, all the ground electrodes have to be connected to the service box, as they are at my house. I have a water-pipe ground and a ground rod; they're physically widely separated, and each has its own conductor going back to the service box. So I guess you could call the service box a single "ground connection". The neutral and safety ground conductors of each circuit are individually grounded at the service box also, giving further support to interpreting its function as a single ground connection. A number of ground methods and devices are approved, such as buried rods or plates, concrete grounds, or (in my old code book anyway), water pipe ground. Some can be used alone and others need a second ground device as a supplement. When multiple ground rods are used, the code has requirements for bonding them to each other. Roy Lewallen, W7EL Using a cold water pipe is a bad idea and is not allowed by some local codes even though it may be allowed by the national code. This is partly because it should only be connected to the ground system at one point and it is too easy to connect it at more than one. Also there is the possible interaction with gas lines and plumbers and home owners sometimes modify plumbing in ways that make them poor grounds.. |
#16
![]() |
|||
|
|||
![]()
Jimmy wrote:
"Using a cold water pipe is a bad idea and is not allowed by some local codes even though it may be allowed by the national code." You don`t want to be electrocuted when holding an electric appliance and a cold water valve simultaneously. My electric company, the former Houston Lighting and Power Company, writes: "All services shall be properly grounded. Note - NEC requires grounding to a "metallic underground water piping system" if available. Acceptable alternatives include a driven ground rod which is preferred by HL&P Co. regardless of the type grounding electrode used. NEC requires that the "interior cold water pipimg system" be bonded to it." Best regards, Richard Harrison, KB5WZI |
#17
![]() |
|||
|
|||
![]()
Richard Harrison wrote:
My electric company, the former Houston Lighting and Power Company, writes: "All services shall be properly grounded. Note - NEC requires grounding to a "metallic underground water piping system" if available. Acceptable alternatives include a driven ground rod which is preferred by HL&P Co. regardless of the type grounding electrode used. NEC requires that the "interior cold water pipimg system" be bonded to it." That last point is the same in the UK. Gas and water supplies are never relied on to provide an electrical ground, but they must be bonded to the electrical supply ground. Additional local bonding is also required for all metalwork in bathrooms and shower rooms. -- 73 from Ian G3SEK 'In Practice' columnist for RadCom (RSGB) http://www.ifwtech.co.uk/g3sek |
#18
![]() |
|||
|
|||
![]() |
#20
![]() |
|||
|
|||
![]()
On Sat, 04 Sep 2004 20:28:58 GMT, "ku4yp" wrote:
i thank you all for the comments. to tie into the electirical service will be a pain as the electrical gound is on the total oposite end of the house from the shack. i'll have to work something out there. water pipe grounding will not be a problem. i can see i have much more reading to do. thanks agian, mike When we had an electrician upgrade the incoming electrical service box on my mother's house (circa 1960), he ran a large 8 gauge wire from the box at the end of the garage, along the wall of the house all the way to the incoming water line from the street near the other end of the basement, where he tied it to ground next to the water meter. The National Electrical Code has changed, and those in older houses might consider upgrading to current code (no pun intended) even if not actually required. In industrial situations, I have had to deal with ground loop problems, which are a PITA to find. Do your grounding correctly, and you will be safer, and have an easier time of it. Happy trails, Gary (net.yogi.bear) ------------------------------------------------ at the 51st percentile of ursine intelligence Gary D. Schwartz, Needham, MA, USA Please reply to: garyDOTschwartzATpoboxDOTcom |
Reply |
Thread Tools | Search this Thread |
Display Modes | |
|
|
![]() |
||||
Thread | Forum | |||
CD Player Receives FM Station | Antenna | |||
Newbie - Studying for Tech & planning station setup - Vertical antennaquestion | Antenna | |||
Antenna mast grounding question | Antenna | |||
Grounding for Vertical Question | Antenna | |||
Grounding question - this is wierd..... | Antenna |