Home |
Search |
Today's Posts |
#11
|
|||
|
|||
Pulling Cable in Conduit
jimbo wrote:
I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Thanks, jimbo Thanks for the great advice. I will leave the ladder line for another day, another route from attic to basement. Thanks, jimbo |
#12
|
|||
|
|||
Pulling Cable in Conduit
"Ralph Mowery" wrote in message
ink.net... "gb" wrote in message ... "jimbo" wrote in message . .. I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Thanks, jimbo A Google search should get you the electrical handbooks and codes (e.g. NEC ) for the maximum fill for each conduit size. As a rough rule NEVER fill a conduit more than 70% to 75%. The NEC is mostly for wires for the AC lines. It will not apply for the antenna wires. The ladder line is not going to work too well in the conduit with the other wire. There is a minimum distance that it should be placed from other conductors. Ralph - I am not referring to the AC portion of the NEC, RATHER I am trying to highlight the maximum fill (diameter of each cable and maximum pull). ever try to "pull conductors" through conduit when this rule is NOT followed ?? I have, it's pain .. in the xxxx. Easy read and math calculations are minimal with tables supplied --- number of conductors and O.D. versus the I.D. on conduit. |
#13
|
|||
|
|||
Pulling Cable in Conduit
"gb" wrote in message ... "Ralph Mowery" wrote in message ink.net... "gb" wrote in message ... "jimbo" wrote in message . .. I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Thanks, jimbo A Google search should get you the electrical handbooks and codes (e.g. NEC ) for the maximum fill for each conduit size. As a rough rule NEVER fill a conduit more than 70% to 75%. The NEC is mostly for wires for the AC lines. It will not apply for the antenna wires. The ladder line is not going to work too well in the conduit with the other wire. There is a minimum distance that it should be placed from other conductors. Ralph - I am not referring to the AC portion of the NEC, RATHER I am trying to highlight the maximum fill (diameter of each cable and maximum pull). ever try to "pull conductors" through conduit when this rule is NOT followed ?? I have, it's pain .. in the xxxx. Easy read and math calculations are minimal with tables supplied --- number of conductors and O.D. versus the I.D. on conduit. Yes, I have. I work at a large industral plant. Some of the wire I have pulled has been in 1 inch conduit that was probably 90% full of # 12 wire already. Still needed to get another pair of wires through that. I have cut a couple of wires in the conduit and used them to pull in wire to replace them and two new wires. No room in the conduit to push a snake through and pull the new wire in. Use lots of the wire pulling grease. Most of the wires are control wires and only have about an amp or less on them. We are not worried about overheating the wires in the conduit, but need to add new control circuits to a 40 year old plant. As you said it is a pain. |
#14
|
|||
|
|||
Pulling Cable in Conduit
Run the Ladder line to near the entrance of the PVC, and then use a
BALUN, to COAX, for the run down your PVC, BUT remember: PVC stands for: PIPE VERY CROWDED! Jim NN7K Dan Richardson wrote: On Sun, 22 Jan 2006 08:29:29 -0700, jimbo wrote: I am getting close to pulling some cable through a 1 1/4 inch PVC conduit that runs about 20 feet from the third floor attic to the basement. The contractor claims the conduit is a "straight shot" with no bends. I have three LMR240 cables with PL259 connectors on each end. And I would also like to pull a 450 ohm length of ladder line. (Measures about 1 inch.) And I would like to pull at least two 16 gage insulated control wires. Any advice would be appreciated. Forget the ladder line! It will be a disaster. email: k6mheatarrldotnet http://www.k6mhe.com/ |
#15
|
|||
|
|||
Pulling Cable in Conduit
"Ralph Mowery" wrote in message
ink.net... Ever try to "pull conductors" through conduit when this rule is NOT followed ?? I have, it's pain .. in the xxxx. Easy read and math calculations are minimal with tables supplied --- number of conductors and O.D. versus the I.D. on conduit. Yes, I have. I work at a large industral plant. Some of the wire I have pulled has been in 1 inch conduit that was probably 90% full of # 12 wire already. Still needed to get another pair of wires through that. I have cut a couple of wires in the conduit and used them to pull in wire to replace them and two new wires. No room in the conduit to push a snake through and pull the new wire in. Use lots of the wire pulling grease. Most of the wires are control wires and only have about an amp or less on them. We are not worried about overheating the wires in the conduit, but need to add new control circuits to a 40 year old plant. As you said it is a pain. Ha ha ha .. well we did follow up work behind the same guy !! :-) Sadly, the grease did not help in one of my situations with 3/4" conduit .. had to finally tear out of wall and then replace with 2 conduits for the wire runs. gb |
Reply |
|
Thread Tools | Search this Thread |
Display Modes | |
|
|
Similar Threads | ||||
Thread | Forum | |||
The "TRICK" to TV 'type' Coax Cable [Shielded] SWL Loop Antennas {RHF} | Antenna | |||
The "TRICK" to TV 'type' Coax Cable [Shielded] SWL Loop Antennas {RHF} | Shortwave | |||
Poor quality low + High TV channels? How much dB in Preamp? | Antenna | |||
Poor quality low + High TV channels? How much dB in Preamp? | Shortwave | |||
Massachusetts. Cambridge. Community access television. | Broadcasting |